A'
<br />ROOF WIND DESIGN PRESSURES
<br />NET (GROSS) ASCE 7-16
<br />ZONE 1 = 81.20 PSF (71.20) ZONE 3 = 70.70 PSF (80.70)
<br />ZONE 2e = 70.70 PSF IS0.70) ZONE 3e = 82.90 PSF (92.90)
<br />ZONE 2n • 82.90 PSF (92.90) ZONE 3r = 90.80 PSF (f00.80)
<br />ZONE 2r = 82.90 PSF (92.90)
<br />'A"= 4'-0" END ZONE DISTANCE
<br />BASIC WIND SPEED: 160 MPH
<br />EXPOSURE CATEGORY: "C"
<br />RISK CATAGORY: II
<br />APPLICABLE INTERNAL
<br />ROOF DIAPHRAGM.
<br />FQR ASPHALT SHINGLE ROOF, USE MIN 19/32" STRUCTURAL SHEATHING
<br />EXP 1 (40201. FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN.
<br />19/37' STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD
<br />AND EDGE SPACING) SEE DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE tOd RING SHANK GUN
<br />NAILS 0 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF
<br />C*BLE END.
<br />ROOF/ WALL/ FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />SIZE
<br />HEAD
<br />LENGTH
<br />DIM.
<br />TENSILE STR.
<br />SHANK
<br />I ASTM
<br />10d
<br />RING SHANK
<br />21/7'
<br />0.131
<br />SCREW SHANK
<br />170000
<br />RING
<br />ZING RINGS
<br />P6-
<br />RSRS 03
<br />Bd
<br />RING SHANK,
<br />23/8"
<br />0.113
<br />F1667
<br />SCREW SHANK
<br />ER INCH)
<br />Bd
<br />RING SHANK,
<br />PNEUMATIC
<br />23/S'
<br />0.113
<br />F1667
<br />SCREW -NAILS
<br />RSRS-01
<br />EXTERIOR SHEATHING
<br />USE 11Z' CDX OR 7116" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4"
<br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP &
<br />BOTTOM PANEL AND Bd RING SHANK GUN NAILS AT 6" O.C. AT
<br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL
<br />ROOF SHEATHING ATTACHEMENT SPACING
<br />ZONE 1: tOd NAILS 0 4" O.C. ON EDGE ANDS' O.C. IN FIELD
<br />ZONE 2e, 2n, 2r. 1Od NAILS 0 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />ZONE 3,3s, 3r: 10d NAILS 0 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED
<br />AND ADHERES TO ASCE 7-16
<br />8d RING SHANK GUN NAILS Q 4" O.C.
<br />TOP & BOTTOM EDGES
<br />a
<br />J
<br />z
<br />z
<br />ZQ�W
<br />S
<br />C/
<br />'0
<br />Z
<br />li
<br />ZW
<br />So
<br />w
<br />Y c
<br />U
<br />rn O
<br />Z �
<br />8
<br />SW
<br />L (7
<br />19
<br />RAFTER OR TRUSS
<br />RDOF CHFATHINr:
<br />U nulL.ulrv�Lervuln
<br />T-
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />NM GABLES -DROP GABLE END & (1) ADO'L DROPPED
<br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING 0
<br />160
<br />.C. IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP
<br />BLOCKING 0 16" O.C. FIRST 4 BAYS N (2)12d NAILS EA
<br />END. ATTACH ROOF SHEATHING TO RAFTERS 2J
<br />BLOCKING PER NAILING SCHEDULE
<br />C1od RING SHANK GUN NAILS
<br />SEE "ROOF SHEATHING ATTACHMENT'
<br />TABLE FOR FIELD SPACING ,
<br />C#8 2' DECK SCREWS R 6"-8" O.C. MAX
<br />EDGES & 17' O.C. MAX IN FIELD. UNTHREADED
<br />SHANK TO EXTEND BEYOND THICKNESS OF
<br />SUB -FLOOR SHEATHING \
<br />TYP. 314" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL. NOTES'
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C331C3314 MAXIMUM AGGREGATE SIZE SHALL BE 3/B.
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION NTH JOB SPECIFICATIONS AND
<br />WOOD.
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />PROVIDE B%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 7d1 EDITION
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED Mr.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb - 1100 PSI AND MODULUS OF
<br />FOR STRUCTURAL CONCRETE, TMS 402(802-16 AISI SPECIFICATION FOR THE DESIGN OF
<br />PROVIDE 64MIL CONDNUOIIS POIYETHYIENEVAPOR BARBER MEMBRANE UNDERALL SU&S-0NC-ROlRA N4B:PE INDICATED ON
<br />ELASTICITY- 1,400,000 PSI. ALL WOOD IN CONTACT MATH CONCRETE OR CONCRETE SMOCK SHALL BE
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS
<br />DRAWINGS SEAMS LAPPED B INCHES AND SEALED WITH ADHESIVE TAPE
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A SORATE PRESERVATIVE TREATMENT: DISODIUM
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />FORMWORK:
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DDT OR MORE. NAILS, SPIKE, BOLTS USED
<br />EXCEPT VWHEREA DIFFERENT DETAIL IS SHOWN.
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST
<br />W/ DOT SHALL BE HOT DIPPED CALM. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORMWORK
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FBCR 2020, 71h EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />OF THE WORK.
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING
<br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYP NZIS
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />WELDED WIRE MESH'
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS
<br />WELDED WIRE MESH, SHALL BE ASTM A1064/A7064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE
<br />WOOD TRUSSES:
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL
<br />BE SUPPORTED NTH 2' CHAIRS SPACED 3'-0' OC, EACH WAY.
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE "NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS' THE NFTRUSS DESIGNS SHALL SIGNED AND
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED 1N FLORIDA.O SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />REINFORCING STEEL•
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.038" AND BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />REBAR SHALL BE ASTM A615A615M GRADE 401N CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615
<br />MEETING THE REQUIREMENTS OF ASTM A448/A448M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED.
<br />GRADE 601N MASONRY BARS DEFORMED FREE FROM OIL SCALE AND RUST AND PLACED IN ACCORDANCE
<br />E E
<br />DESIGN LOADS:
<br />N THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14,'DESIGN NATIONAL
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />STANDARDS FOR METAL-PLATECONNECTEDWOOD TRUSS CONSTRUCTION:, AND "BCSI LATEST EDITION"
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf
<br />AND VERTICAL BARS SHALL LAP e x BAR NO, UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />20 psf TOP CHORD —on —rem
<br />REVIEW.
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: 04 BAR - 25" #6 BAR - 3e"
<br />WOOD TRUSSES.
<br />10 Psf BTM CHORD-n—oncurmnt
<br />#5 BAR - 30" #7 BAR - 42"
<br />PROVIDE 38' x 3W CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />DEAD LOAD
<br />DEAD LOAD
<br />FOR ADDITIONAL INFORMATION.
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSUASCE 7 88: 1990,
<br />18 W9 TOP CHORDHAT
<br />20 pet 70P CHORD
<br />psf ASPHALT SHINGLES)
<br />N. OYPCRETE)
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURERS INSTRUCTIONS.
<br />1
<br />10 psf BTM CHORD
<br />B
<br />5 p ST
<br />5 pd BTM CHORD
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />DEAD LOAD TO RESIST WIND UPLIFT: 1 Opsf
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />BALCONY LIVE LOAD 80 Psf
<br />STAIRS LIVE LOAD 40 psf
<br />Wes'
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />WIND: DEAD LOAD SPEED =160 MPH 3- SECOND GUST
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />(ASCE 7-10 (FBC R2020) EXPOSURE C, RISK CATEGORY II)
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10psf, UNINHABITABLE ATTIC WITH LIMITED
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />STORAGE: 20ps( HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR)
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER
<br />WTHOUT THE APPROVAL OF THE ENGINEER.
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />VEHICLE GARAGES: 50pO, ROOMS OTHER THAN SLEEPING ROOM: 40pef, SLEEPING ROOMS: 30psf, STAIRS:
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />MASONRY'
<br />PROVIDE
<br />NG COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM NTH ALL REQUIREMENTS OF THE
<br />LICENSED PROFESSIONAL ENGINEER.
<br />SHOP DRAWING REVIEW:
<br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPUANCE NTH THE DESIGNING INTENT
<br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED By
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />THE MASONRY STANDARDS JOINT COMMITTEE.
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />COMPLIANCE NTH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC
<br />ALL BLOCK WALLS SHALL BE HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT.
<br />ANCE VOL
<br />MANUFACTURED IN CONFORMANCE NTH ASTM GBO, GRADE Pm 2000 PSI. BLOCK SHALL BE PLACED USING
<br />OF THE DELEGATED TRUSS ENGINEER. W ND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT
<br />AND CLADDING W ND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />ASTM 0J76, AND SWILL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8"
<br />WRITING BY THE ARCHITECT.
<br />COURSE AGGREGATE, AND SHALL BE PLACED N A SLUMP OF S" TO 10", USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />FOUNDATION/ SITE PREPARATION:
<br />"M"
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 Psf, FOOTING
<br />TYPE OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270, HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE
<br />SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL
<br />CELLS 70 BE FILLED.
<br />SOIL FOR TERMITE PROTECTION.
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />REINFORCING.
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O.
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />STRUCTURAL .STEEL:
<br />BE MADE BY THE GE0.TECH. ENGINEER,
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY NTH THE
<br />CONCRETE:
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />BTH EDITION BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A38/A38M, Fy = 36 ksi FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM
<br />A500/A500M GRADE B F = 46 W. STRUCTURAL PIPE SHAM BE ASTM A53/A53M GRADES TYPE E ORS F =
<br />y L y
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />35 kti. TUBE AND PIPE COLUMNS SHALL BE CONCRETEfILLEO IN THE SHOP.
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS NTH DOUBLE -NUT LEVELING. ALL
<br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO
<br />OTHER BOLTS SHALL
<br />ACCORD STM 25/EWT BOLTSNTHWASHERSUNDEHOD. TURNED ELEMENT. BOLTS
<br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5'd- PRIOR TO THE ADDITION OF PLASTICIZER
<br />IN
<br />SHALL BE TIGHTENED IN ACCORDANCE NTH THE TURN -OFF -THE -NUT METHOD.
<br />CONCRETE SHALL COMPLYWITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94IC94MOR MEASURING, MIXING, TRANSPORTING,
<br />ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN
<br />WATER IS ADDED TO THE MU( UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON
<br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. R SHALL
<br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY
<br />NON COMPLIANCE WITH THE ABOVE
<br />REQUIRED CONCRETE COVERAGE OVER RERAR SHAD. BE AS FOLLOWS:
<br />A 3' FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS):
<br />B FORCONCRETE EXPOSED TO EARTH ANDIORWEATHER
<br />1-Ur FOR MI5 AND SMALLER
<br />2" FOR NO AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />314' FOR SLABS, WALLS ANDJOISTS
<br />14/2" FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />APPUCATON
<br />EIZE
<br />TYPE
<br />SPACING
<br />REMARKS
<br />APPUGAngB
<br />SIZE
<br />TYPE
<br />SPACING
<br />REMMK6
<br />1,Q PT FURRING TO
<br />CAGE HARO@Im Gdl
<br />B.�
<br />GARAGE DOOR BLCx
<br />00.
<br />TAP:ON MASONRt
<br />B OC
<br />I I?EMBED.,4'E ST.,
<br />MPSONRYICONG.
<br />NNL11?LONG.
<br />M19QVRY,NNC
<br />NOWl%R
<br />FASTENER
<br />11?EIX3E018T.
<br />BGD�AL. EM DOORS
<br />CABS HARDENED COIL
<br />B'p'G
<br />YNNOOMMWOR/FMTENED
<br />GPAAOE ODOR &CAI
<br />18`O'C (3/S"WI
<br />EMBE0.. 4"ENDgBT..
<br />v ,eEE NmEe
<br />11?MONO.
<br />6TAOGEREO
<br />N TO MAB(xIRYKUrIC.
<br />TO MPeONRYCUNC.
<br />xtl WASHER
<br />IXPANeION BOL T
<br />y. dCI120W
<br />SEDGE DI6T.
<br />W1ND01NBlCK
<br />EHIROENEDCOIL
<br />O'OIG
<br />V4NDOVADD�UFPST..
<br />METAL STRAP TO
<br />CONTACT THIS ENGINEER FOR SPACING
<br />1x PT SEE NOTE6
<br />NAIL 11?LONG.
<br />STAGGERED
<br />INTO
<br />REQUIREMENTS
<br />IXT. SWINp DOOR
<br />BtHY[3 Pr. SEE NOlEB
<br />(T b16dA.
<br />NO WASHER
<br />"TAPCOM
<br />HASTIER
<br />t6 OC
<br />11R`EMBED,B"ENO.
<br />gST.,11?EDGE GIST.
<br />NClLBEAPoNG WOOD
<br />WALL TO CONC. 6lAe
<br />1?° E%PPKSION 4"EMBFD4°ETA
<br />MB WASHER BOLT 14 OC q&T.. 3'EDGE qST.
<br />L PT WINDOW BUIX 0.138°p— fA' B'GC 4` ENO. ..T. 11?
<br />IT T09TEEL COL., SEE WI —HER STAGGERED EDGE D18T
<br />NOTES
<br />NOM
<br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SLANG DOOR$ TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4, PAF SHALL BE HILTI X-Zf HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />6. W NDOW ANO DOOR BUCKS SHALL BE AS W DE OR W DER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR NTH A WOOD DOOR FRAME. ix MEMBERS ARE NAILED AND
<br />2x MEMBERS ARE SECURED N TAPCONS OR PAF TO THE SUBSTRATE.
<br />1441 N. RONALD REAGAN BLVD
<br />LONGWOOD, FL 32750
<br />PH: 407-774"6078
<br />FAX: 407-774-4078
<br />www,abdosigngroup.com
<br />AA #: 0003325 _ _.
<br />p
<br />G
<br />O
<br />C
<br />9VHDIV. a LOT:
<br />ABBOTT PARK
<br />LOT #32
<br />BLK #12
<br />PROJECT#
<br />04181.000-32121
<br />1LODEIA
<br />3EEB
<br />"2260-ELSTON"
<br />GARAGE STII/ING:
<br />LEFT
<br />PAGE:
<br />DETAILS
<br />160 MPH EXP. C
<br />
|