ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-16 <br />ZONE 1 = 58.00 PSF (68.00) <br />ZONES = 66.50 PSF (76.50) <br />ZONE 2e = 66.50 PSF (76.50) <br />ZONE 3e 76.60 PSF (86.60) <br />ZONE 2n = 76.60 PSF (86.60) <br />ZONE 3r = 91,70 PSF (101.70) <br />ZONE 2r = 76.60 PSF (86.60) <br />"A"= 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />EXPOSURE CATEGORY: "C" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT: +/-0.18 <br />ROOF DNPFitAW <br />FOR ASPHALT SHINGLE ROOF USE MIN 19132' STRUCTURAL SHEATHING <br />EXP 1 (40120), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN. <br />19/32" STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL <br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SWANK GUN <br />NAILS 0 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS WIN 4' OF <br />GABLE END. <br />ROOF/ WALU FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL REQUIREMENTS <br />SIZE <br />HEAD <br />LENGTH <br />DIA <br />TENSILE STIR. <br />SHANK <br />ASTM <br />10d <br />RING SHANK <br />2 12" <br />0,131 <br />F1067 <br />170.000 <br />RING <br />(16-20 RINGS <br />RSRS-03 <br />8d <br />RING SHANK <br />2 3/8" <br />0.113 <br />F1867 <br />SCREW SHANK <br />PER INCH) <br />RSRS RSRS-01 <br />8d <br />RING SHANK, <br />PNEUMATIC <br />2 VIT' <br />0,113 <br />F1667 <br />SCREW -NAILS <br />RSRS-01 <br />EXTERIOR SHEATHING <br />USE 12" CDX OR 7116" O.S.B. PLY WITH Bd RING SHANK GUN NAILS AT 4" <br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 6"O.C. AT <br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL <br />ZONE 1: 10d NAILS 0 4" O.C. ON EDGE AND T O.C. IN FIELD <br />ZONE 2e, 2n, 2r 10d NAILS ® 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />ZONE 3,3e, 3, 10d NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />9tl RING SHANK GUN NAILS @4'OC. <br />TOP S BOTTOM EDC£9 <br />�o <br />z <br />TYP. EXT. SHEATHING ATTACHMENT <br />RAFTER OR TRUSS <br />ROOF SHEATHING <br />r <br />o <br />m <br />I. BUILDING LENGTH �- <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />NOTE: GABLES -DROP GABLE END & (1) ADD'L DROPPED <br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W BLOCKING H <br />16"O.C. IF NO DROPPED GABLE END, ATTACH 2x4#2 SYP <br />BLOCKING 0 18" O.C. FIRST 4 SAYS W (2)12d NAILS EA <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />- 101 RING SHANK GUN NAILS <br />SEE"ROOF SHEATHING ATTACHMENT" <br />TABLE FOR FIELD SPACING <br />C#8 2" DECK SCREWS C 6"-S' O.C. MAX C <br />EDGES & 12" O.C. MAX IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WTH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCHTECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAW NGS. APPLICABLE BUILDING CODE STANDARDS: FSGR 2020, AT EDITION <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, TMS 4021602-16 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SI MILAR SITUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAW NGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />OF THE WORK, <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION, THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR I ECOWHS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />DESIGN LOADS: <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 pef <br />20 pst TOP CHORD-nconcunent <br />10 psf BTM CHORD nonconcunent <br />DEAD LOAD DEAD LOAD <br />18 pIM TOP CHORD 20 psf TOP CHORD <br />(7 PSI W/ ASPHALT SHINGLES) (10 psf w/ No GYPCRETE) <br />10 psf BTM CHORD 5 psf BTM CHORD <br />DEAD LOAD TO RESIST W ND UPLIFT: 1 DPsf <br />BALCONY LIVE LOAD 60 psf <br />STAIRS LIVE LOAD 40 psf <br />WIND: DEAD LOAD SPEED-160 MPH 3-SECOND GUST <br />(ASCE 7-16 (FBC R2020) EXPOSURE C, RISK CATEGORY II) <br />LIVE LOADS: UNNHABITABLE ATTIC WITHOUT STORAGE: 1Opsf, UNNHABITABLE ATTIC WTH LIMITED <br />STORAGE: 20Psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30pef, BALCONIES (EXTERIOR) <br />AND DECKS: 40paf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50pef, PASSENGER <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40P0, SLEEPING ROOMS: 30Nf, STAIRS: <br />40psf <br />SHOP DRAWING REVIEW: <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WTH THE DESIGNING INTENT <br />OF THE CONTRACT DOCLNENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />COMPLIANCE WTH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL SHOP DRAW NGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />DRAWINGS SUBMITTED WTHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAW NGS IN THE FORM <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCE$, THE CONTRACT <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERW SE SPECIFIED IN <br />WRITING BY THE ARCHITECT. <br />FOUMATIOW SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2000 pL FOOTING <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WTH ASTM D-1557. TREAT ALL <br />SOIL FOR TERMITE PROTECTION. <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33/C33M. MAXIMUM AGGREGATE SIZE SHALL SEW. <br />WOOD: <br />PROVIDE 6%AIR ENTRAINED CONCRETEEXPOSEDTO EARTHORWEATHER NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3/4'. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SJBSONGROWID WHBRE INDICATED ON <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fe = 1100 PSI AND A MODULUS OF <br />DRAWINGS. SEAMS LAPPED 61NCHES AND SEALED NTH ADHESIVE TAPE <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />PRESSURE TREATED, PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL LOSES <br />SHALL LEVELS OF O25 PCF OF A BORATE AVBE <br />f (DOT). <br />FORM -WORK <br />CORROBORATE TETRAHEDRAL WOOD FOR STRUCTURAL USE SHALL TREATEED FOR ANYR <br />FORMWORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WTH ACI 347 LATEST <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITiON,'RECOMMENDED PRACTICE FOR CONCRETE FORMWORK. <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />EXCLUSION FROM THESE PLAN; <br />MINIMUM NAILING PER FBCR 2020, 781 EDITION. SEE NAILING SCHEDULE ON PLANS. <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENRXNG PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP f2. <br />WELDED WIRE MESH: <br />WELDED W RE MESH, SHALL BE ASTM Al 064/A1064M. GRADE 65 AND BE PLACED I N ACCORDANCE W TH THE <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. W RE MESH FOR SLABS SHALL <br />BE SUPPORTED W TH 2' CHAIRS SPACED 3'-0" OC, EACH WAY. <br />i',4fIIil ;TIC1Tc�]1377: <br />REBAR SHALL BE ASTM A615A615M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />WI THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE AG STANDARDS AND SPECIFICATIONS. <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION HORIZONTAL <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEERS <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36" <br />#5 BAR - 30" #7 BAR - 42" <br />PROVIDE 38' x 36'CORNER BARS, BOND BEAM ONLY, LAPPEDAND TIED TO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION. <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />WALL. <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />MASONRY: <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WTH ALL REQUIREMENTS OF THE <br />"SPECIFICATION MASONRY STRUCTURES" (INS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />MANUFACTURED IN CONFORMANCE WTH ASTM "0, GRADE f m = 2000 PSI. BLOCK SHALL BE PLACED USING <br />RUNNING BOND UNLESS OTHERW SE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WTH <br />ASTM G476, AND $WALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/9' <br />COURSE AGGREGATE, AND SHALL BE PLACED W A SLUMP OF 8" TO 10", USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />SHALL BE 3/6" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />CELLS TO BE FILLED. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT CEO -TECHNICAL ENGINEER TO VERIFY <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />MUCTi.IRAL STEEL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />CiowpE m: <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION, STRUCTURAL STEEL SHALL BE ASTM <br />A38/A36M, Fy - 36 ksi FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM <br />GRADE B, Fy = 46 ksi. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S, Fy = <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />W. TUBE AND PIPE COLUMNS SHALL BE CONCRETEFILLED IN THE SHOP, <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WTH DOUBLE -NUT LEVELING. ALL <br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS, WITH HSTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIORTO <br />OTHER BOLTS SHALL BE ASTM F3125/F3125M BOLTS WTH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5'4- PRIOR TO THE ADDITION OF PLASTICIZER <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94/C94M OR MEASURING, NIXING TRgaMnNG ALL ANCHOR BOLTS SHALL BE GALVANZED STEEL.J-BOLTS ARE TO BE STEEL. <br />ETC. CONCRETE TICKETS SHU1 BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF DNA' <br />NON COMPLIANCE NTH THE ABOVE <br />REQUIRED CONCRETE COVERAGE OVER FEW SHW-L BE AS FOLLOWS <br />A 3" FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH(FOUNDATIONS$ <br />B FOR CONCRETE EXPOSED TO EARTH ANDICRWEATHEt <br />1-1/2' FOR #5 AND SMALLER <br />2' FOR #6 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TOWEATHBR <br />3/4" FOR SLABS, WALLS AND JOISTS <br />1.112" FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES STIRRUPS <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WTH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />AT BEARING LOCATIONS WTHOUT WOODEN TOP PLATES. <br />WOOD TRUSSES: <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE "NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS" SY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A, AND SHALL BE HOT -UPPED GALVANIZED. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />STANDARDS FOR METAL-PLATECONNECTEDaNOOD TRUSS CONSTRUCTION:, AND "BCSI LATEST EDITION' <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />WOOD TRUSSES. <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WTH ANSI/ASCE 7 88: 1990. <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAW NGS FOR ALTERNATE CONNECTION DETAILS AT <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USEDAS A GUIDE FOR BEARING <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LAYOUT, SPANS 8 ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />PROVIDE ENGINEERED SHOP DRAW NGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />PLAN SHOW NG COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />LICENSED PROFESSIONAL ENGINEER, <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />PROVIDED BY THE TRUSS ENGINEER. <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />OF THE DELEGATED TRUSS ENGINEER. W ND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-18 COMPONENT <br />AND CLADDING W ND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK FASTENERS <br />FASTENER <br />AFPLIGTCN <br />Slg <br />ttPE <br />SPAgNG <br />REWORKS <br />APPDGIIIXJ <br />SI. <br />TYPE <br />SPACINGI <br />REWORKS <br />1. PT NRRNO TO <br />MA90NRylCONC. <br />CASE HARDENED COIL <br />NHLI III-W, <br />9QC <br />GARAGE DOOR &ICK <br />TO W90NRy/OJNC <br />1N"DIA <br />NO WASHER <br />TA-INM1I6HOIIRY <br />FgSTENER <br />30.0 <br />11Y1'EMBED.. d'ENDgST, <br />114'EDOE DIST. <br />SGO.AL.EXT.DOORS <br />CA9EHARDENm LqL <br />O.0 <br />FASTENED <br />PRPGE DOOR 9.. A( <br />9eT tlAOR <br />P�M��i <br />D W <br />d°EMBED., <br />16 PT, 8EENOTES <br />eT pGGQt® <br />TOWIDOORl <br />WWMYIOJNC. <br />iMS.L9TR.w <br />wl WA9HHR <br />]YOx: I 11rr GeV <br />EDIOOIST, <br />q9r <br />CASE HA SD CqL <br />I.- <br />WINOOwIWORIFASTBNw <br />TO <br />CONTACT THIS ENGINEER <br />FOR SPACING <br />PIT. 9EENOTEB <br />rs•LONG. <br />STAGGERED <br />INTOMASONRv1pONc. <br />q9 W-C <br />REQUIREMENTS <br />EM. HYING ODOR No)3ne'tlA 'TAPOON' 18.E 1 TR'EMBFD. e'BNO <br />]r PT, -NOTES FASTNER 1 /Y•EOGEDIST. <br />h TOW9UG1( 9.t30'PAFv]19' 9-CIC VEND. DIST.,11Q' <br />PT N EL C,._ WI WAEHa2 9Ta00EAE➢ EC-DSTIlM <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND/OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILT X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. W NDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. ix MEMBERSARE NAILED AND <br />2x MEMBERB ARE SECURED W/TAPOONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-7744078 <br />FAX: 407-7744078 <br />www.abde9Igngroup.Dom <br />AA #: 0003325 <br />b <br />h <br />C <br />E <br />b <br />O <br />11 <br />lie6 <br />C <br />mi sDiv at r om <br />ABBOTT PARK <br />LOT #2 <br />BLK #14 <br />PHASE 4C <br />pao" CT# <br />04181.04C-02141 <br />moDELt <br />4EHB <br />"2605- HAYDEN" <br />GARAGE 8WINGS <br />RIGHT <br />PAGE: <br />DETAILS <br />160 MPH EXP. C <br />I <br />DAT c 10/26/21 <br />SCALE 1/4"=1'-0" <br />SN1 <br />