q <br />INBLE-END <br />ROOF VWND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-16 <br />ZONE 1 = 52.70 PSF (62.70) <br />ZONE 3 = 60.50 PSF (70.50) <br />ZONE 2e = 60.50 PSF (70.50) <br />ZONE 3e = 69.80 PSF (79.80) <br />ZONE 2n = 69.80 PSF (79.80) <br />ZONE 3r = 83.80 PSF (93.80) <br />ZONE 2r = 69.80 PSF (79.60) <br />"A"= 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />EXPOSURE CATEGORY: "C" <br />RISK CATAGORY: It <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT: +1- 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/32" STRUCTURAL SHEATHING <br />EXP 1 (4020). FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN. <br />19/37' STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN <br />NAILS 0 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF <br />GABLE END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />SIZE <br />HEAD <br />LENGTH <br />DIA. <br />TENSILE STIR. <br />SHANK <br />ASTM <br />10d <br />RING8HANK, <br />S EW SHANK <br />212" <br />0.131 <br />170,000 <br />RING <br />Q 20 RINGS <br />F1667 <br />Bd <br />RING SHANK <br />2 3/6' <br />0.113 <br />SCREW SHANK <br />PER INCH) <br />R R5-01 <br />Sd <br />RINGSHANK, <br />PNEUMATIC <br />23/8' <br />0,113 <br />F1667 <br />RSRS-01 <br />SCREW -NAILS <br />RAFTER OR TRUSS — <br />ROOF SHEATHING <br />EXTERIOR SHEATHING <br />Z r <br />USE 12" CDX OR 7/16' O.S.B. PLY WITH Sd RING SHANK GUN NAILS AT 4" <br />0 <br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />3 <br />BOTTOM PANEL AND Sd RING SHANK GUN NAILS AT 6' O.C. AT <br />DT <br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF, SPECS.) SEE DETAIL. <br />BUILDING LENGTH L <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />ROOF SHEATHING ATTACHEMENT SPAC1140 <br />GABLES -DROP GABLE END 8 (1) ADD'L DROPPED <br />ZONE is tOd NAILS 0 4" O.C. ON EDGE AND 6" O.C. IN FIELD <br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING 0 <br />ZONE 2e, 2n, 2r: tOd NAILS 0 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />1S'O.C. IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP <br />ZONE 3,3e, 3r: 10d NAILS 0 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />BLOCKING 016" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA. <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />RI fl(`KIN(: PFR NAIL INf: Cf:HFf]I 11 F <br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />8d RING SHANK GUN NAILS 0 4" O.C. <br />TOP & BOTTOM EDGES D <br />rn <br />—a <br />a <br />zw <br />zo <br />OW <br />ZYZ <br />QU <br />�O <br />Z <br />10d RING SHANK GUN NAILS <br />SEE "ROOF SHEATHING ATTACHMENT' <br />TABLE FOR FIELD SPACING <br />C#8 2' DECK SCREWS 0 6"4' O.C. MAX 0 <br />EDGES & 17O.C. MAX IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING ` <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C3.VC33M MAXIMUM AGGREGATE SIZE SHALL BE Mr.. <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WTH JOB SPECIFICATIONS AND <br />Wow: <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CWIMFERE031C. <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 7th EDITION <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />PROVIDE 641L CONTINUOUS POLYETHYLENE VAPOR BARBER MEMBRANE UNDER ALL SLABS -ON -GROUND WHERE INDICATED ON <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO, 2 OR BETTER. Fb - 1100 PSI AND A MODULUS OF <br />FOR STRUCTURAL CONCRETE, TM& 40EMBER AISI SPECIFICATION FOR THE DESIGN IO <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2018, ASCE 7-78 AND AISC SPECIFICATIONS <br />DRAWINGS. SEAMS LAPPED 6INCHE'S AND SEALED WITH ADHESIVE TAPE. <br />PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL A <br />ELASTICITY = TREATED. <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONSTRUCTURAL USES <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORM -WORK: <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN W OF HEARTWOOD, <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FSCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL. DEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH' <br />AT BEARING LOCATIONS WTHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />WELDED WIRE MESH, SHALL BE ASTM A1064/A1064M, GRADE 85 AND BE PLACED IN ACCORDANCE WITH THE <br />WOOD TRUSSES: <br />THE CONTRACTOR SHALL SUPPLEMENTBE <br />THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES, WRE MESH FOR SLABS SHALL <br />SUPPORTED WTH 2- CHAIRS SPACED T-O' OC EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE 'NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SHALL BE ASTM A615A615M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />GRADE 601N MASONRY DEFORMED BARS FREE FROM OIL SCALE AND RUST AND PLACED IN ACCORDANCE <br />DESIGN LOADS: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WTH TPI-14, "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "SCSI LATEST EDITION' <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />ATIONS FOR <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />20 psf TOP CHORD npncpn M <br />REVIEW <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - W' <br />WOOD TRUSSES. <br />10 psf BTM CHORD -npn ffent <br />#5 BAR - 30' #7 BAR - 42" <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36" x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88: 1090. <br />18 p#f TOP CHORD D TOP CHORD <br />(7 psf HSHINGLES) (1 p e W/ No GYPCRETE) <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />10 psf BTM TM CHORD 5 5 psf STM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: 10psf <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 psf <br />WALL. <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 Psf <br />WHO: DEAD LOAD SPEED MPH 3- SECOND GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />(ASCE (FBC 020) EXPOSURE C, RISK CATEGORY 10 <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />BIT ATTIC ATTIC WITH LIMITED <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: tWT <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />FIXED STAIRS: <br />STORAGE: 20psf, HABITABLE ATTICS ANDATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES, THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50pST, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAW NGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40psf <br />MASONRY: <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WTH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL SHOP DRAW NGS SHALL BE REVIEWED THE CONTRACTORS PRIOR SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WTH ASTM C-90, GRADE Pm = 2000 PSI. BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WHO UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />AND CLADDING WND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAW NGS SUBMITTED WITHOUT REVIEW WILL L BE RETURNED UNCHECKED.. SSHOP DRAWINGS IN THE FORM <br />I <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS, <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />ACT <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM ENGINEER. ALL INSTANCES, THE CONTRACT <br />ASTM C 476 AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS UNLESS <br />S C L OTHERWISE SPECIFIED IN <br />DOCUMENT6 WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS <br />SPECIFICALLY NOTED OTHERW SE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8" <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED W/A SLUMP OF V TO 10", USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATION/ SITE PREPARATION' <br />"M" "S" <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 PSI, FOOTING <br />TYPE OR MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE <br />SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED, REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WTH ASTM D-1557. TREAT ALL <br />CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION, <br />FILLCMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />REINFORCING. <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS, LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL REBAR 6 X BAR NO.146 BAR DIAMETERS)., U.N.O. <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />STRUCTURAL STEEL: <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLA -ON-GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED S"* PRIOR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C9#C94M OR MEASURING, MIXING, TRANSPORTING, <br />ETC. CONCRETE TICKETS SHALL BE TIMESTAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN <br />WATER IS ADDED TO THE MIX UNTIL 1T IS DEPOSITED IN ITS FINAL POSMON SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON <br />THERE 13 A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />RE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WITH THE ABOVE. <br />REWIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A T FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS): <br />B. FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER <br />1-1/1' FOR 45 AND SMALLER <br />2' FOR#8 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />314- FOR SLABS, WALLS AND JOISTS <br />1 <br />-1/7' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WTH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION, STRUCTURAL STEEL SHALL BE ASTM <br />A36/A36M, Fy = 36 ksi FOR ANGLES, PLATES, AND WSRAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A500/A500M, GRADE B, Fy = 46 k ii. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S, Fy = <br />35 ksi. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM F3125/F3125M BOLTS WTH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APPLICARdJ <br />SITE <br />TYPE <br />SPADNG <br />REMARKS <br />APPLICATON <br />SIZE <br />TYPE <br />6PACING <br />REMAPKB <br />1#PTPURRING TO <br />MASONRYIWNC <br />CA6EHARDENEDCDL <br />—11 IIY L.N.. <br />6 Q'C <br />GPAAGE OO i6UCK <br />To— <br />1N'd0. <br />NO —ER <br />TAPNN M0.40NRT <br />ASTENER <br />. qC <br />I Ifl EMBEG.,<`-S <br />11rz'EDGE dBT. <br />SGop w WORE <br />CASEHARCENEDCDL <br />— <br />WINOONAWgNFABTENED <br />GARAOEOOIX2— <br />YB'DA OR <br />18'dC(31B'DN <br />IEMEED..4'ENDdST. <br />1 T,SEENOTE. <br />STAGGERED <br />I_MABONRY,CONC. <br />OMABONRYKUNG. <br />—DAEXPANSION <br />W <br />BOLT <br />--o—N <br />SEDGE DST. <br />WINDOW SUCK <br />CASE HARDENED COIL <br />9"OTC <br />wNDOWpOOP/FA6TENED <br />METAL SiRPPT. <br />CONTACT THIS ENGINEER FOR SPACING <br />x PT, SEE NOTE. <br />NNLI1/PL01G. <br />STAGGERED <br />IMO MA&xiRYICOHC. <br />MABCNRYICONC. <br />REQUIREMENTS <br />IXT. BWINGDOOR <br />L2)114 <br />IA— <br />I - EMBED, S END. <br />NONBEARIEGWDOD <br />I- I EXPPNSON x`EMBEO 4'FND <br />34 0� <br />_ 3r M, SEE NOTES <br />NO WASHER <br />FPSTNER <br />18" OF <br />D18T., 1113' EDGE deT. <br />WAIL TO CONC. BVe <br />WI WASHER BOLT D16T., 3" EDOE DST. <br />PT TO STTLDOW .,SEE St3S°P Iff 9'DC YEN.. dST., i I? <br />NOTES WI WASHER 6TAGGERED EDGE dBTNO <br />11. STTAAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS AP <br />2, FASTENING OF GARAGE DOORS, W NDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />e. W NDOW AND DOOR BUCKS SHALL BE AS W DE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SW NG DOOR WTH A WOOD DOOR FRAME. 1. MEMBERS ARE NAILED AND <br />2, MEMBERS ARE SECURED W TAPCONS OR PAF TO THE SUBSTRATE. <br />44 <br />J."I N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-774-6078 <br />FAX: 407-7744078 <br />www.abdesigngroup.com <br />AA #: 0003326 <br />U <br />64 <br />J <br />8 <br />yJ <br />a <br />DVBDM Ae LOT: <br />ABBOTT PARK <br />LOT #34 <br />BLK. #12 <br />PROJECT* <br />04181.000-34121 <br />MODEL: <br />3EAB <br />"1504- ALLEX/' <br />GARAGE SUING: <br />LEFT <br />PAGE: <br />DETAILS <br />160 MPH EXP. C <br />