Laserfiche WebLink
HVAC NOTES <br />I. ALL MECHANICAL EQUIPMENT SMALL 15E PROVIDED WITH PROPER CLEARANCE, FOR SERVICING, PER <br />MFG. RECAAREMENTS. <br />2. ALL DUCT SYSTEMS INSTALLED IN NON -CONDITIONED AREAS SHALL BE CONSTRUCTED OF A VALUE <br />OF NO LESS THEN R-6 RATING. ALL SEAMS SHALL BE SEALED WITH GLASS FAB 4 MASTIC. AND <br />INSTALLED AS PER FBC 6TH EDITION (2011) MECHANICAL BLDG. CODE SECTION 603. <br />3, ALL FLEX DUCTS SHALL BE APPROVED UL 181 CLASS I AIR DUCT AS PER NFPA WA 2-3J <br />4. FRESH AIR INTAKES SHALL NOT BE LOCATED CLOSER THAN 10 FT. FROM ANY CHIMNEY OR VENT <br />OUTLET, OR SANITARY SEWER VENT OUTLET <br />S. ALL EXHAUST AND OUTSIDE AIR INLET DUCTS, SHALL BE CONSTRUCTED OF SMOOTH GALV. METAL. <br />OR OTHER MATERIALS AS PER FBC 6TH EDITION (2011) MECHANICAL CODE SECTION 603 <br />6. ENCLOSED SUPPORT PLATFORMS SHALL BE CONSTmUcTED IN ACCORDANCE TO FBC 6TH EDITION <br />(2011) MECHANICAL CODE 603.1 <br />1. BATHROOMS CONTAINING BATHTUBS, SHOWERS, SPAS AND SIMILAR BATHING FIXTURES SHALL BE <br />MECHANICALLY VENTED IN ACCORDANCE WITH FBC 6TH EDITION (2041) MECHANICAL CODE SECTION <br />403. <br />S. ALL EXHAUSTED BATH ROOMS, SHALL HAVE UNDER -CUT DOORS FOR MAKE-UP AIR TO BE <br />RETURNED, TO EQUAL AIR EXHAUSTED. <br />3 ALL FIRE RATED CEILINGS AND WALLS $HALL HAVE AN APPROVED FIRE OR FIRE/SMOKE <br />DAMPER'S LOCATED AT CEILING OR WALL PENETRATION AND BE SLEEVED WITH ACCESS DOOR$ TO <br />RESET DAMPER ALL DAMPERS SHALL BE INSTALLED TO MFG, RECOMMENDATIONS AND FBC 6TH <br />EDITION (2011) MECHANICAL CODE SECTION 601. <br />10. GRILLES AND DIFFUSERS SHALL BE PROVIDED WITH BALANCING DAMPERS. <br />11, DRYER BOOSTER TO BE A FANTECH DBF BOOSTER FAN OR EQUAL. <br />FANTECH DBF 110 DRYER BOOSTER CAPACITY 60 LINEAR FEET WITH MAX. SIX ELBOWS. <br />LEGEND <br />® <br />SUPPLY AIR DIFFUSER <br />RETURN AIR GRILL <br />® <br />SIDE -WALL OR I WAY DIFFUSER <br />— <br />SOLID LINE- SUPPLY TRUNK <br />— <br />BROKEN LINE• RETURN TRUNK <br />BALANCING DAMPER OR OBD <br />O <br />CEILING EXHAUST FAN <br />CEILING EXHAUST FAN 4 LIGHT <br />O/A <br />OUTSIDE AIR <br />® <br />THERMOSTAT <br />m <br />PASS-THRU AIR GRILL <br />14' DIA &A FROM <br />CHASE ABOVE <br />1 <br />I <br />12X8� <br />12XB <br />■ <br />NOTE: <br />�\7 <br />-------- <br />I <br />ALL HVAC TO HAVE PROPER <br />g <br />1 e • I <br />PANS W/ DRAINS <br />ATTIC <br />CEILING <br />O <br />O <br />EXTERIOR WALL <br />SECURE STRAP TO CONC. <br />CONDENSER <br />PLENUMy <br />AIR RETURN <br />W/ (2)-3/16'X2' TAPGON$ <br />T <br />SIMM WB ROLL STRAP <br />41,11,111, <br />12X8 <br />SUCTION AND LIQUID <br />--AIR <br />O <br />SUPPLY <br />y <br />REFRIGERANT LINES <br />HANDLER <br />4'CONCRETE SLAB SECURE STRAP TO UNIT W/ (2)'8XI I/4' SHT. MTL. SCREWS <br />VT�ENTAIR <br />EXTERIOR WALL <br />WAL <br />WALL <br />FOYER <br />y <br />CONDENSER UNIT <br />l <br />3/4' PVC CONDENSATE DRAIN LINE <br />EVAP. TRAY <br />y <br />PVC SLEEVE TO LINES BELOW SLAB <br />CONNECTION TO PAD <br />" <br />? <br />REFRIGERANT LINES TO <br />NOTE: MAIN COND. DRAIN 3/4' DIA <br />PLATFORM <br />lF <br />RETURN <br />CONDENSING UNIT <br />OVER HEAD li' FROM STRUCTURE <br />TRAP DRAIN LINE AND TERMINATE <br />IN AN APROVEO DRAIN, AS PER <br />--- <br />FBCR 6TH EDITION (2011) <br />--- <br />MECHANICAL SLOG. CODE <br />SECTION 301.2.4 <br />HVAC <br />DRAINS <br />GARAGE <br />--------J <br />ENTRY <br />SCORIATED NICKEL <br />BRONZE FL. PL. <br />FIN. FLOOR <br />OR WALL <br />COUNTERSUNK <br />C.O. PLUG <br />- - - - - - - <br />BRASS PLUG <br />�—FITTING OR EXTENSION TO <br />SOIL OR WASTE AS <br />REQUIRED <br />INSIDE SERIES NICKEL BRASS TOP <br />CAULK P.V.0 OPTVSPEC <br />FLOOR SLAB CLEAN -OUT (TYP ) <br />FIN. GRADE <br />OR PAVING <br />SEE SPEC. <br />I'-$'X8' CONC. <br />FITTING OR <br />EXTENSION TO SOIL <br />OR WASTE AS <br />REQUIRED <br />nEXT. GROUND CLEAN -OUT (TYP. ) <br />FIRST FLOOR <br />MECHANICAL PLAN <br />SCALE: 1/4 - 1'-0' <br />1441 N. RONALD REAGAN BLVD <br />LONGWOOD, FL32750 <br />PH: 407-774-6078 <br />FAX: 407-7744078 <br />www.abdesigngroup.com <br />` AA #: 0003325 J <br />Y <br />R <br />ABBOTT PARK <br />LOT #36 <br />BLK #12 <br />P]ltOJMCT# <br />04181.000-36121 <br />MODELS <br />3EEB <br />"2260—ELSTON" <br />CtARAGZ BVnNa: <br />LEFT <br />p'I'IRST <br />FLOOR <br />MECHANICAL <br />PLAN <br />160 MPH EXP. C <br />DRINT -1 <br />ATE: 04/06/21 <br />SCALE: 1/4"=1'-0" <br />SHEET <br />M1 <br />