HVAC NOTES <br />I. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH PROPER CLEARANCE, FOR SERVICING, PER <br />MFG. REQUIREMENTS. <br />2. ALL DUCT SYSTEMS INSTALLED IN NON -CONDITIONED AREAS SMALL BE CONSTRUCTED OF A VALUE <br />OF NO LESS THEN R-6 RATING. ALL SEAMS SHALL BE SEALED WITH GLASS PAS 4 MASTIC. AND <br />INSTALLED AS PER FBC 1TH EDITION (2020) MECHANICAL BLDG. CODE SECTION 603, <br />3. ALL FLEX DUCTS SHALL BE APPROVED UL 181 CLASS I AIR DUCT AS PER NFPA WA 2-3.1 <br />4. FRESH AIR INTAKES SHALL NOT BE LOCATED CLOSER THAN 10 FT. FROM ANY CHIMNEY OR VENT <br />OUTLET, OR SANITARY SEWER VENT OUTLET <br />5. ALL EXHAUST AND OUTSIDE AIR INLET DUCTS, SHALL. BE CONSTRUCTED OF SMOOTH GALV. METAL. <br />OR OTHER MATERIALS AS PER FBC 1TH EDITION (2020) MECHANICAL CODE SECTION 603 <br />6. ENCLOSED SUPPORT PLATFORMS SHALL BE CONSTRUCTED IN ACCORDANCE TO PBC 1TH EDITION <br />(2020) MECHANICAL CODE 603J <br />1. BATHROOMS CONTAINING BATHTUBS, SHOWERS, SPAS AND SIMILAR BATHING FIXTURES SHALL BE <br />MECHANICALLY VENTED IN ACCORDANCE WITH FBC 1TH EDITION (2020) MECHANICAL CODE SECTION <br />403. <br />8. ALL EXHAUSTED BATH ROOMS, SHALL HAVE UNDER -CUT DOORS FOR MAKE-UP AIR TO BE <br />RETURNED, TO EQUAL AIR EXHAUSTED. <br />9, ALL FIRE RATED CEILINGS AND WALLS SHALL HAVE AN APPROVED FIRE OR FIRE/SMOKE <br />DAMPER'S LOCATED AT CEILNG OR WALL PENETRATION AND BE SLEEVED WITH ACCESS DOORS TO <br />RESET DAMPER ALL DAMPERS SHALL BE INSTALLED TO t'FG. RECOMMENDATIONS AND FBC 1TH <br />EDITION (2020) MECHANICAL CODE SECTION 601. <br />10. GRILLES AND DIFFUSERS SHALL BE PROVIDED WITH BALANCING DAMPERS. <br />11. DRYER BOOSTER TO BE A FANTECH OBF BOOSTER FAN OR EQUAL. <br />FANTECH DBF 110 DRYER BOOSTER CAPACITY 60 LINEAR FEET WITH MAX. SIX ELBOWS, <br />LEGEND <br />® <br />SUPPLY AIR DIFFUSER <br />RETURN AIR GRILL <br />® <br />SIDE -WALL OR I WAY DIFFUSER <br />— <br />SOLID LINE- SUPPLY TRUNK <br />BROKEN LINE- RETURN TRUNK <br />l <br />BALANCNG DAMPER OR OBD <br />0 <br />CEILING EXHAUST FAN <br />CEILING EXHAUST FAN 4 LIGHT <br />O/A <br />OUTSIDE AIR <br />® <br />THERMOSTAT <br />m <br />PASS-THRU AIR GRILL <br />HOSE: <br />HVAC TO HAVE PROPER <br />PANS W/ DRAINS <br />>ALL <br />ATTICCEILING <br />EXTERIOR WALL <br />PLENUM <br />T <br />y <br />AIR RETURN <br />SUCTION AND LIQUID <br />AIR SUPPLY <br />y <br />REFRIGERANT LINES <br />SECURE STRAP TO CONC. <br />CONDENSER <br />W/ (2)-3/16'X2' TAPCONS <br />UNIT <br />SIMPSON WB ROLL STRAP <br />y <br />OR EQUAL <br />AIR HANDLER <br />EXTERIOR WALL <br />y <br />3/4' PVC CONDENSATE DRAIN LINE <br />SECURE STRAP TO UNIT W/ (2) <br />EVAP. TRAY <br />y <br />PVC SLEEVE TO LINES BELOW SLAB <br />4' CONCRETE BLAB fSXI 1/4' SHT. MTL. SCREWS <br />T <br />REFRIGERANT LINES TO <br />CONDENSER UNIT <br />PLATFORM <br />RAN <br />CONDENSING UNIT <br />TRAP DRAIN LINE AND TERMINATE <br />CONNECTION TO PAD <br />AN APROVED DRAM,PER <br />CR 1T14 EDITION (2020) <br />POOR <br />NOTE: MAIN COND. DRAIN 3/4' DfA <br />MECHANICAL BLDG. CODE <br />SECTION 301]4 <br />OVER HEAD • 12' FROM STRUCTURE <br />HVAC <br />DRAINS <br />I - - - - a <br />I <br />I <br />I <br />DiNiNr <br />14' <br />FROM OM <br />I <br />ABOVE <br />BEDROOM #2 <br />I�-------+---------- - 1 12X8 <br />12X12 I� 14X6 ------ <br />11 PASS <br />- t �I II THRU � <br />D' I------------------- I I----�o . <br />- -X <br />,I I <br />KIT HEN <br />I I t gTOR• I l f <br />I <br />0 CLIP <br />i <br />12X8 - SX - <br />�� S' WA <br />FROM <br />ABOVE <br />� III <br />�11 9X9/rim <br />FOYER <br />III <br />ul /Q <br />P RCH <br />SGORIATED NICKEL ///---FIN. FLOOR I <br />BRONZE FL. PL. / OR WALL COUNTERSUNK <br />CA. PLUG <br />FITTING OR EXTENSION TO <br />SOIL OR WASTE AS <br />REG IRED <br />WADE 8240-K JOSAM 56000 <br />INSIDE SERIES NICKEL BRASS TOP <br />CAULK P.V.0 OPTI/SPEC <br />FLOOR SLAB CLEAN -OUT (TYP. <br />N <br />FIN. GRADE <br />OR PAVING <br />SEE SPEC. <br />I'-S'XW CONC. <br />FITTING OR <br />EXTENSION TO SOIL <br />OR WASTE AS <br />REQUIRED <br />nEXT. GROUND CLEAN -OUT (TY�P, <br />GARAGE <br />FIRST FLOOR <br />MECHANICAL PLAN <br />SCALE: 1/4 • I'-0' <br />IN <br />• <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL32750 <br />PH: 407-7748078 <br />FAX: 407-7744078 <br />www.abdesigngroup.com <br />AA $: 0003325 <br />n <br />till <br />� <br />r <br />11111 lV ABBOTT PARK <br />LOT #32T <br />11A <br />BLK # <br />PROJECT <br />04181.006-32112 <br />MODET. <br />4EHB <br />"2605- HAYDEN" <br />GARAGE 9`11111MG: <br />RIGHT <br />PAGE: <br />FIRST FLOOR <br />MECHANICAL <br />PLAN <br />60 MM EXP. <br />