Laserfiche WebLink
GABIf-END- <br />HIP ROOF � " >k <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-16 <br />ZONE 1 = 58.00 PSF (68.00) <br />ZONE 3 =. 66.50 PSF (76.50) <br />ZONE 2e = 66.50 PSF (76.50) <br />ZONE 3e = 76.60 PSF (86.60) <br />ZONE 2n = 76.60 PSF (86.60) <br />ZONE 3r = 91.70 PSF (101.70) <br />ZONE 2r = 76.60 PSF (86,60) <br />"A"- 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />EXPOSURE CATEGORY: "C" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT: +/- 0.18 <br />ROOF DgPHRAW <br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/32' STRUCTURAL SHEATHING <br />EXP 1 (40/20). FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN. <br />19/32" STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL <br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN <br />NAILS @ 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF <br />GABLE END. <br />ROOF/ WALU FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />SIZE <br />HEAD <br />LENGTH <br />CIA <br />7ENSILESTR. <br />SHANK <br />ASTM <br />10d <br />RING SHANK <br />2 12" <br />0.131 <br />P667 <br />170,000 <br />RING <br />116-20 RINGS <br />RSRS-03 <br />Bd <br />RING SHANK, <br />2 3/8" <br />0.113 <br />F1667 <br />SCREW SWANK <br />PER INCH) <br />RSRS-01 <br />Bd <br />RING SHANK, <br />PNEUMATIC <br />23/9' <br />0,113 <br />F1667 <br />SCREW -NAILS <br />RSRS-01 <br />EXTERIOR SHEATHING <br />USE 1/2" CDX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4" <br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 6' O.C. AT <br />INTERMEDIATE SUPPORTS OR 7116" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS,) SEE DETAIL, <br />ZONE 1: 10d NAILS @ 4" O.C. ON EDGEAND6 O.C. IN FIELD <br />ZONE 2e, 2n, 2r: 10d NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />ZONE 3,3e, 3r: 1 Od NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />NOTE', ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />M RING SHANK GUN NAAS Q4'OC <br />., TOP B BOTTgA EDGES .. <br />W <br />z� Z LL <br />I Z <br />0 <br />_ Z O <br />TYP. EXT.SHEATHING ATTACHMENT <br />A7 <br />8 <br />oa <br />RAFTER OR TRUSS <br />ROOF SHEATHING <br />Z <br />o � <br />m <br />)� BUILDING LENGTH <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />NOTE GABLES -DROP GABLE END &(1)ADDILDROPPED <br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING <br />16"O.C. IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP <br />BLOCKING C 16" O:C, FIRST 4 BAYS W/(2)12d NAILS EA <br />END, ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />10d RING SHANKGUN NAILS - <br />SEE"ROOF SHEATHING ATTACHMENT' <br />TABLE FOR FIELD SPACING <br />TYP. EXT. SHEATHING ATTACHMENT FOR STRUCTURAL ROOF <br />SHEATHING <br />(-..'2" DECK SCREWS @ 6"-8" O C. MAX <br />EDGES & 12" O.C. MAX INFIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33/C33M. MAXIMUM AGGREGATE SIZE SHALL BE W. <br />STRUCTURAL DRAWINGS SHALL BE USED IN COWUNCTION VITH JOB SIDE Cl FICATIONS AND <br />WOOD: <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />PROVIDE B%AIR ENTRAINED CONCRETED(POSER TO EARTH OR WEATHER <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAW NGS FOR SLEEVE S,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAW NGS. APPLICABLE BUILDING CODE STANDARDS: PBC-R 2020, 7th EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE 70 BE CHAMFERED 3/4' . <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318.14, BUILDING CODE REQUIREMENTS <br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDERALL SLPBSONGPOUIND WHERE INDICATED ON <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. F4= 1100 PSI ANDA MODULUS OF <br />FOR STRUCTURAL CONCRETE, TMS 4021602-16 ANSI SPECIFICATION FOR THE DESIGN OF <br />DRAWINGS. BEAMS LAPPED 61NCHES AND SEALEDN4THPIXESIWETPPE <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED WOOD FOR NON8TRUCTURAL USES <br />SMALL BERATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORM -WORK: <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANV <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPTMERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WTH ACI 347 LATEST <br />W/ COT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITION,'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN Ye" OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2020, 71h EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL. DEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />THE STRICTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDINGON <br />THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />IS COMPLETE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE INDIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH: <br />AT BEARING LOCATIONS W THOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DO MS. <br />WELDED HIRE MESH, SHALL BE ASTM A7084/A1084M, GRADE 85 AND BE PLACED IN ACCORDANCE WTH THE <br />WOOD TRUSSES: <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />AG TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />BE SUPPORTED WTH 2" CHAIRS SPACED 3'-O' OC, EACH WAY. <br />TO 13E DESIGNED <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE "NATIONAL DESIGN SPECIFICATIONS FOR <br />REQUIREMENTS AND SLAB-0N-GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SHALL BE ASTM A615A615M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />GRADE 80 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED <br />DESIGN LOADS: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND 'SCSI LATEST EDITION' <br />ROOF: LIVE LOAD FLOOR' LIVE LOAD 40 psf <br />E AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS A <br />R SUBJECT -T OENGINEER 'S <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METALfLATECONNECTED <br />20 psf TOP CHORD ­wcurrent <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36" <br />WOOD TRUSSES. <br />10 psf BTM CHORD +1 oncumnt <br />#5 BAR - 30" #7 BAR - 42" <br />TRUSS MANUFACTURER W ILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD FOR THE ROOF <br />PROVIDE 36"z 36"CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />LOCATIONS WTH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONALL ROOF <br />ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88:1990. <br />18 pof TOP CHORD 20 psf TOP CHORD <br />(7 psf 4ASPHALT SHINGLES w/ No GYPCRETE) <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />5 p sf BTM CHORDpsf <br />10 psf BTM CHORD 5 p <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST HIND UPLIFT: tOpsf <br />MINIMUM 101NCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 psf <br />WALL <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 psf <br />HIND: DEAD LOAD SPEED MPH GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USEDASA GUIDE FOR BEARING <br />R2020) EXPOSURE C, RISK CATEGORY II) <br />(ASCE 7-16 (NBC SUSECONDC,RI <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />ATTIC <br />LIVE LOADS: UNINHABITABLE ATTIC STORAGE: UNINHABITABLE ATTIC WTH LIMITED <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />ANDATWITHOUT <br />STORAGE: HABITABLE AND WITH <br />SERVED WITH FIXED STAIRS: BALCONIES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />; 40p AND HA 20 NTS: <br />AND DECKS: 40pef, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: SOpBf, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER, <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES, THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND FULLY DIMENSIONED ERECTION <br />40psf <br />MASONRY: <br />PLAN SHOW NG COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRYCONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />M <br />C RACTORO <br />PROVIDED BY THE TRUSS ENGINEER. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL BLOCK WALLS SHALL R TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK OF THE DELEGATED TRUSS ENGINEER. W ND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-i6 COMPONENT <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT, MANUFACTURED IN CONFORMANCE WITH ASTM C-00, GRADE fm = 2000 PSI. BLOCK SHALL BE PLACED USING AND CLADDING WHO LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL A RESPONSIBLE FOR <br />DRAW NGS SUBMITTED WTHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM RUNNING BOND UNLESS OTHERWISE SE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WTH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER IN ALL INSTANCES, THE CONTRACT ASTM C-476, AND SHALL PROVIDE A MI MMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />DOCUMENTS HILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWSE SPECIFIED IN SPECIFICALLY NOTED OTHERMSE ON FOUNDATION PLAN. THE GROUT MIX SHALL WAVE A MAXIMUM 3/8" <br />WRITING BY THE ARCHITECT. COURSE AGGREGATE, AND SHALL BE PLACED W A SLUMP OF 8" TO 10'. USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATIOW SITE PREPARATION: TYPE'M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2.000 psf, FOOTING PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WTH ASTM D7557. TREATALL CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />THE ONMER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RECOMPACTED AND RETESTEDAT THE <br />CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS RAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 26 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB-ON-GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5" d- PRIOR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94IC94M OR MEASURNG, MIXING, TRANSPORTING, <br />ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MNUTES THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />8E THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WITH THE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER REBARSHNU. BEASFOLLOW3 <br />A WFOR CONCRETE CAST AGAINST AND PERMANENRYEXPDSEDTO EARTH(FOUNDATIONS) <br />B. FOR CONCRETE EXPOSED TO EARTH MY/OR WEATHER <br />1-1/2' FOR 05 AND SMALLER <br />2" FOR#6 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3/4" FOR SLABS WALLS AND JOISTS <br />1-1/2' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES STIRRUPS <br />FILL CM CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS ANDIOR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.0 <br />STRUCTURALSTEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WTH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36/A36M, Fy = 36 ksi FOR ANGLES, PLATES, AND WSRAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A500/A500M, GRADE B, Fy = 46 W. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S, Fy = <br />35 ksi. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WTH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM F3125/F3125M BOLTS WTH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WTH THE TURN-0FF-THE-NUT METHOD <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL, JZOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK FASTENERS <br />FASTENER <br />--ON <br />sim <br />-TON <br />Sig <br />TTFE <br />ISPAONG <br />RE. - <br />I. l FIRING TO <br />MASONRTICONC. <br />SOF <br />GARAUEDDOR- <br />NRTIC w <br />tM'PA <br />NO WASHER <br />TAPCON MA9J,WY <br />FASTENER <br />S PC <br />MBED., x'6DLIST, <br />2'FCGE 019T. <br />SGDK.IXT. OOOR6 <br />CASE INRDEN®CqL <br />wNIFASTENED <br />pONppOOR <br />ARGUE WOR BLCK <br />PAOR <br />f6-.0 (3' F DW <br />EMBED., VEND PST., <br />pT, SEENOTEB <br />sT EKED <br />INTO MA9JN2TIODNC. <br />TO_NRTICONC. <br />-1. <br />WASHER <br />E-SIONEOLT <br />2A"OO.C(trz'OIA) <br />9'EWEDST . <br />WIN eJPc <br />CASE ED-1 <br />wtRDEN <br />S,m <br />wINDD... FASTENED <br />METAL STRAPTO <br />CONTACT THIS ENGINEER FOR SPACING <br />. PT SEENDTE6 <br />N.LII LONG <br />STAGGERED <br />ncoNc. <br />MASONRTICONC. <br />REQUIREMENTS <br />ODOR <br />(2)9I1SPA <br />TAPOON' <br />tS'QC <br />1I2'EMBEOB'END. <br />NON <br />NONE ­ <br />a'EMBED.a'END <br />PT, SEE NOTES <br />NO WA6HER <br />NASTIER <br />DIST., 112"E EDST. <br />DUAL L TO CONC, SIPB <br />2- <br />D16T., 3"EDGE PET. <br />"WBUCK 0130'PAF,216" PTTO STEEL ODL.,I .1 WASHY STAGGERED EE.. .I.T .12 <br />OTEB <br />NOTES <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI XZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REtlUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. ix MEMBERS ARE NAILED AND <br />2z MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE. <br />1 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL32750 <br />PH: 407-774,6078 <br />FAX: 407-7744078 <br />www.abdesigngroup.com <br />AA M: 0003325 J <br />0 <br />E <br />� <br />r <br />O <br />C <br />oulwiv. & LOT: <br />ABBOTT PARK <br />LOT #32 <br />BLK #11 <br />PROJECTM <br />04181. 00-32113 <br />MODEL. <br />4EHB <br />rr2605-HAYDEN" <br />GAtiAGE 8WtNG: <br />RIGHT <br />PAGE: <br />DETAILS <br />60 MPH EXP. Cj <br />