ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-16 <br />ZONE 1 = 58.00 PSF (68.00) <br />ZONE 3 = 66.50 PSF (76.50) <br />ZONE 2e = 66.50 PSF (76.50) <br />ZONE 3e = 76.60 PSF (86.60) <br />ZONE 2n = 76.60 PSF (86.80) <br />ZONE 3r = 91.70 PSF (101.70) <br />ZONE 2r = 76.60 PSF (86.60) <br />"A"- 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />EXPOSURE CATEGORY: "C. <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT: +/-0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/32" STRUCTURAL SHEATHING <br />EXP 1 (40120), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN. <br />19132" STRUCTURAL SHEATHING EXP 1 (40R0).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL <br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN <br />NAILS @ 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS WIN 4' R <br />GABLE END. <br />ROOF/ WALU FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL REQUIREMENTS <br />SIZE <br />HEAD <br />LENGTH <br />CA. <br />I TENSILE STR. <br />SHANK <br />ASTM <br />10d <br />RING SHANK, <br />2 1I7 <br />0131 <br />F1807 <br />K <br />170,000 <br />NG <br />((11I6--20 RINGS <br />RSRS-03 <br />8d <br />RING SHANK, <br />2 31V <br />0,113 <br />F1667 <br />SCREW SHANK <br />PER INCH) <br />RSRS-01 <br />Sd <br />RING SHANK <br />PNEUMATIC <br />23/8" <br />0,113 <br />F1887 <br />SCREW -NAILS <br />RSRS-01 <br />RAFTER OR TRUSS <br />ROOF SHEATHING <br />EXTERIOR SHEATHING <br />USE 1/2" CDX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4" <br />o <br />O.C. AT PANEL SIDES AND Bd RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 6" O.C. AT <br />m <br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL <br />1. BUILDING LENGTH <br />1. <br />ZONE 1: 10d NAILS @ 4" O.C. ON EDGE AND 6.O.C. IN FIELD <br />ZONE 2e, 211, 2,'. 10d NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />ZONE 3,3e, 3r. 10d NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />NOTE ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />H <br />2® <br />yo <br />Ba RING SHANK GUN NAIS 0-C. <br />TOP A BOTTOMEDC£S <br />TYP. EXT. SHEATHING ATTACHMENT <br />ROOF SHEATHING LAYOUT <br />AND ENOWALL BRACING <br />FOR GABLE ENO FRAMING <br />NOTE: GABLES -DROP GABLE END & (1) ADD'L DROPPED <br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING @ <br />16"O. C. IF NO DROPPED GABLE END, ATTACH 2x4#2 SYP <br />BLOCKING @ 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />6 <br />IN RING SHANK GUN NAILS <br />a SEE "ROOF SHEATHING ATTACHMENT' <br />m o TABLE FOR FIELD SPACING <br />ze <br />8 <br />TYP. EXT. SHEATHING ATTACHMENT FOR STRUCTURAL ROOF <br />SHEATHING <br />#8 2" DECK SCREWS 0 6'-8" O.C. MAX @ <br />EDGES & 12" O.C. MAX IN FIELD. UNTHREADED <br />0 o SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING <br />�e <br />TYP. 3/4" TOG SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCHITECTURAL DRAW NGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAW NGS. APPLICABLE BUILDING CODE STANDARDS: FBC4R 2020, 7th EDITION <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CoNCRETE, TMS 4021602-16 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 ANDAISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAW NGS. FOLLOW WRITEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />TO THE ATTENTION OF THE HI ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />OF THE WORK. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REQUIREMENTS AND SLAB-0N-GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />DESIGN LOADS: <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psi <br />20 pV TOP CHORD non -concurrent <br />10 psf BTM CHORD no -current <br />DEAD LOAD DEAD LOAD <br />18 PM TOP CHORD 20 psf TOP CHORD <br />(7 psf Nd ASPHALT SHINGLES) (10 paf W/ W GYPCRETE) <br />10 PST BTM CHORD 5 psf BTM CHORD <br />DEAD LOAD TO RESIST WND UPLIFT: 1 Opsf <br />BALCONY LIVE LOAD 60 psf <br />STAIRS LIVE LOAD 40 psf <br />WND: DEAD LOAD SPEED =160 MPH 3-SECOND GUST <br />(ASCE 7-10 (FBC R2020) EXPOSURE C, RISK CATEGORY II) <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10psf, UNINHABITABLE ATTIC WTH LIMITED <br />STORAGE: 2Dpsf, 14481TABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARDINFILL COMPONENTS: 50psf, PASSENGER <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS: <br />40Psf <br />SHOP DRAWING REVIEW: <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />COMPLIANCE WTH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />DRAW NGS SUBMITTED WITHOUT REVIEW WLL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWSE SPECIFIED IN <br />WRITING BY THE ARCHITECT. <br />FOUNDATION/ SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FORAN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 PSI, FOOTING <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL <br />SOIL FOR TERMITE PROTECTION, <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEERS REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTEDAT THE <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 P31 REGULAR WEIGHT FOR FOOTINGS, AND SLAB ON -GRADE <br />3,000 PSI REGULAR VVEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5' d- PRIOR TO THE ADDITION OF PLASTICIZER <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33/C33M. MAJOMUM AGGREGATE SIZE SIALL BE 31C. <br />WOOD: <br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3/4'. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb = 1100 PSI AND MODULUS OF <br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SIABSONGRIXRJD WHERE INDICATED ON <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />DRAWINGS. SEAMS LAPPED 6INCHES AND SEALED WITH ADHESIVE TAPE. <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NO STRUCTURAL USES <br />RATEDSHALL BE TO TREATMENT: UM <br />PSTR <br />FORMWORK <br />HALL BE TREATED FOR ANY <br />CORROBIDRA ETETTRA EDRALN(DOT). WOOD FOR UC URAL USE THAT SHAA <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WTH ACI 347 LATEST <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITION,'RECOMMENDED PRACTICE FOR CONCRETE FORMWORK, <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2D20, 7th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDNG PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND NDOD COLUMNS WTH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #Y2. <br />WELDED WIRE MESH: <br />WELDED WIRE MESH, SHALL BE ASTM Al 054/A1064M, GRADE 65 AND BE PLACED IN ACCORDANCE WTH THE <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. W RE MESH FOR SLABS SHALL <br />BE SUPPORTED WTH 2' CHAIRS SPACED T-0.00, EACH WAY. <br />REINFORCING STEEL: <br />REBAR SHALL BE ASTM AOISA615M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />GRADE 601N MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED INACCORDANCE <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE AG STANDARDS AND SPECIFICATIONS. <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEERS <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 26' #6 BAR - 36" <br />#5 BAR - 30" #7 BAR - 42' <br />PROVIDE 36' x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIEDTO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION. <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />WALL. <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES VMEREVER POSSIBLE. <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />MASONRY: <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WTH ALL REQUIREMENTS R THE <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fm - 2000 PSI. BLOCK SHALL BE PLACED USING <br />RUNNING BOND UNLESS OTHERW SE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WTH <br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8" <br />COURSE AGGREGATE, AND SHALL BE PLACED NA SLUMP OF 8" TO 10'. USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />CELLS TO BE FILLED. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS ANCOR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />STRUCTURALSTEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THESPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL SE ASTM <br />A36/A36M, Pj = 36 ksl FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A500tA500M, GRADE B, P/ = 46 ksi. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S, Fy = <br />35 ksi. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WTH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM F3125/1`3125M BOLTS WTH WASHERS UNDER THE TURNED ELEMENT, BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WTH THE TURN-0FF-TEWLT METHOD. <br />CONCRETE SHKL COMPLY WITH ALL THE REQUIREMENTS OF AC1318 AND ASTM C94IC94M OR MEASURING, MANG, TRANSPORTING, ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. JEOLTS ARE TO BE STEEL. <br />ETC. CONCRETE TICKETS SIALL BE TIME4TAMPE2 WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM:Mf31 <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES IF FOR ANY REASON <br />TEE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WTH THEABOVE <br />REQUIRED CONCRETE COVERAGE OVER REBARSHALL BE AS FOLLOWS <br />A YFOR CONCRETE CAST AGAINST AND PERMANENTLYEGIOSEDTO EARTH(FOUNDATIONSt <br />B FOR CONCRETE EXPOSED TO EARTH ANDIOR WEATHER <br />1-1/2 FOR 05 AND SMALLER <br />2 FOR #5 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3/4' FOR SLABS, WALLS AND JOISTS <br />1.12' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WTH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />AT BEARING LOCATIONS W THOUT WOODEN TOP PLATES. <br />WOOD TRUSSES: <br />TO BEDESIGNED AND FABRICATEDIN ACCORDANCE WITH THE "NATIONL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' SY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTMA446/A446M, GRADE A, AND SHALL BE HOT -UPPED GALVANIZED. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPIA4, "DESIGN NATIONAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "SCSI LATEST EDITION' <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL-PLATECONNECTED <br />WOOD TRUSSES. <br />TRUSS MANUFACTURER W LL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WTH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WTH ANSI/ASCE 7 SO: 1990. <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS GUIDE FORBEARING <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />LICENSED PROFESSIONAL ENGINEER. <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDEDTO FACILITATE THE <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />PROVIDED BY THE TRUSS ENGINEER. <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />OF THE DELEGATED TRUSS ENGINEER. WND UPLIFT VALUES RAVE BEEN BASED ON ASCE 706 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK FASTENERS <br />FASTENER <br />A-GAnON <br />Siff <br />1. <br />SPA.H. <br />REMARM8 <br />APPUG m <br />film <br />TYPE <br />SR1gNG <br />REMApx3 <br />-P-RRING TO <br />GASEHARD@1E _ <br />-111/S LONG. <br />OMAOE DOCK BI!q( <br />TO RASDNRYIOONC. <br />H'OA <br />NO�N <br />MA60MtI <br />EMBEMA6011RY/GONG. <br />1DIET6GOpK. <br />rE' <br />IXT DOORSOfSE <br />HARDEHEDCOIL <br />S'o0 <br />WINDOW9WIXLFASTENEO <br />OMOOEDOOR SN-K <br />ORIFOIC <br />EXPANSION BOLT <br />816"ON.SEO., <br /><' ENDpST., <br />x T, SEEN01E6 <br />NAIL NYC LONG. <br />3TAGOSR. <br />IMOMASONRY INC. <br />TO M4�MrvICON4 <br />]p_01TDW <br />3'EDOE q3P. <br />wINOJWBUCK <br />GMEHARDENEDCOIL <br />S.- <br />WIWO DOOR)-T.. <br />METAL STRAP TO <br />CONTACT THIS ENGINEER <br />FOR SPACING <br />1. PT, SEEN 6 <br />NA 11ff'L0NO. <br />STAGGeRED <br />INIOMASDNRYNONC. <br />...NRYICONC <br />REQUIREMENTS <br />E. SNAG DOOR GGp3_ "TAPOJN' ITO. MBEGS"END. <br />OF <br />BUCK 3. PT, SEE NOTE6 WASHER FASTNER 16 OIST.,11R"EDGE-T. <br />T TWINDOW .-RA1.1- a"OTC <"END. DI6T.11? <br />PO STEEL CCL..9E£ W/ WA91ER STAGOQtEO DOE O44l. <br />NOTE6 <br />NOTSEI <br />11. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND/ NOA <br />3. ALL FASCA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI XZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS VIDE OR UDDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. ix MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-774,6078 <br />FAX: 407-774.4078 <br />www.ebdesigngroup.com <br />AA #: 0003325 <br />O <br />fee! <br />G <br />aunDiv. Ae LrOT. <br />ABBOTT PARK <br />LOT #39 <br />BLK #7 <br />P1toamTo <br />04 ,000-39 7 <br />MODZU <br />4EHB <br />"2605-HAYDEN" <br />GARAGE aWMxG: <br />RIGHT <br />PAGE: <br />DETAILS <br />160 MPH EXP. C <br />202 <br />ROIJW A ABOUC ACRA <br />L AR NO 933723 J <br />DvmcT <br />ATIL. 09/21/52'1 <br />MICALIE: 1/4"=1'-0" <br />omzzT <br />S N1 <br />