HVAC NOTES <br />1. ALL MECHANICAL EQUIPMENT SMALL BE PROVIDED WITH PROPER CLEARANCE, FOR SERVICING, PER <br />MF& REQUIREMENTS. <br />2. ALL DUCT SYSTEMS NOTALLED IN NON -CONDITIONED AREAS SMALL BE CONSTRUCTED OF A VALUE <br />OF NO LESS THEN R-6 RATING. ALL SEAMS SHALL BE SEALED WITH GLASS FAB 4 MASTIC, AND <br />INSTALLED AS PER FBC 1TH EDITION (2020) MECHANICAL BLDG CODE SECTION 603. <br />S. ALL FLEX DUCTS SHALL BE APPROVED UL 181 CLASS I AIR DUCT AS PER NFPA WA 2-3.1 <br />4. FRESH AIR INTAKES NA i � BE LOCATED CLOSER THAN 10 FT. FROM ANY CHIMNEY OR VENT <br />OUTLET, OR SANITARY SEWER VENT OUTLET <br />5. ALL EXHAUST AND OUTSIDE AIR INLET DUCTS, SMALL BE CONSTRUCTED OF SMOOTH GALV. METAL. <br />OR OTHER MATERIALS AS PER I = 1TH EDITION (2020) MECHANICAL CODE SECTION 603 <br />6. ENCLOSED SUPPORT PLATFORMS SHALL BE CONSTRUCTED IN ACCORDANCE TO MC 'ITH EDITION <br />(2020) MECHANICAL CODE 603.1 <br />1. BATHROOMS CONTAINING BATHTUBS, SHOWERS, SPAS AND SIMILAR BATHING FIXTURES SHALL BE <br />MECHANICALLY VENTED IN ACCORDANCE WITH MC 1TH EDITION (2020) MECHANICAL CODE SECTION <br />403. <br />S. ALL EXHAUSTED BATH ROOMS, SHALL HAVE UNDER -CUT DOORS FOR MAKE-UP AIR TO BE <br />RETURNED, TO EOLAL AIR EXHAUSTED. <br />9 ALL FIRE RATED CEILINGS AND WALLS SMALL HAVE AN APPROVED FIRE OR FIRE/dMOKE <br />DAMPER'S LOCATED AT CEILING OR WALL PENETRATION AND BE SLEEVED WITH ACCESS DOORS TO <br />RESET DAMPER. ALL DAMPERS SHALL DE INSTALLED TO MFG. RECOMMENDATIONS AND FOG 1TH <br />EDITION (2020) MECHANICAL CODE SECTION 601. <br />10. GRILLES AND DIFFUSERS SHALL BE PROVIDED WITH BALANCING DAMPERS. <br />IL DRYER BOOSTER TO BE A FANTEC 4 DBF BOOSTER FAN OR EQUAL. <br />FANTEC 4 DBF 110 DRYER BOOSTER CAPACITY 60 LINEAR FEET WITH MAX SIX ELBOWS. <br />SCORIATED NICKEL FIN. FLOOR <br />BRONZE FL PL. "-I— OR WALL <br />—FITTING OR EXTENSION TO <br />SOIL OR WASTE AS <br />r REQUIRED <br />INSIDE / RIES NICKEL BRASS TOP <br />CAULK / P.V.0 OPTI/SPEC <br />XFL00R SLAB CLEAN -OUT (TYQ <br />COUNTERSIAIC <br />C.O. PLUG <br />SEE SPEC. <br />r-8'Xe' CONC. <br />FN GRADE <br />OR PAVING <br />O <br />■ <br />FITTING OR <br />EXTENSION TO SOIL <br />OR WASTE AS <br />REQUIRED <br />nEXT. GROUND CLEAN -OUT (TYPN� <br />LEGEND <br />® <br />SUPPLY AIR DIFFUSER <br />RETURN AIR GRILL <br />® <br />SIDE -WALL OR I WAY DIFFUSER <br />— <br />SOLID LINE- SUPPLY TRINK <br />— <br />BROKEN LINE- RETURN TRNK <br />1 <br />BALANCING DAMPER OR ODD <br />0 <br />CEILING EXHAUST FAN <br />CEILING EXHAUST FAN 4 LIGHT <br />O/A <br />OUTSIDE AIR <br />® <br />THERMOSTAT <br />m <br />PASS-THRU AIR GRILL <br />ATTIC <br />AIR SUPPLY- � <br />AIR <br />EVAR <br />ALL VAC TO HAVE PROPER <br />PANS W/ DRAMS <br />SECURE STRAP TO CONG <br />W/ (2)-3/16'X2' TAPCONSIDAd1ETR 81MP80N WB ROLL STRAP <br />EXTERIOR WALL OR EQUAL <br />AIR RETURN <br />SUCTION AND LIQUID 4' CONCRETE SLAB SECURE STRAP TO UNIT W/ (2) <br />REFRGERANT LINER #SXI 1/4' SHT, MTL. SCREWS <br />CONDENSER UNIT <br />EXTERIOR WALL CONNECTION TO PAD <br />1 3/4' PVC CONDENSATE DRAIN LINE <br />NOTE: MAIN COND. DRAIN 3/4' DIA. <br />1PVC SLEEVE 70 LINES BELOW SLA7B OVER HEAD • 12' FROM STRUCTURE <br />REFRIGERANT LINES TO <br />RETURN CONDENSING WIT <br />TRAP DRAIN LINE AND TERMINATE <br />IN AN APROVED DRAIN, AS PER <br />FBCR 1TH EDITION (2020) <br />MECHANICAL BLDG. CODE <br />SECTION 30 .2.4 <br />HVAC DRAINS <br />MECHANICAL PLAN <br />6CALE, 1/4 • 1'-0' <br />JUNI <br />i44i N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-7748078 <br />FAX: 407.774-4078 <br />www.abdesigngroup.com <br />L AA N: 0003325 J <br />a <br />ax7mrv. <br />ABBOTT PARK <br />LOT# 36 <br />BLK. 7 <br />PROJECT <br />04181.00 -36071 <br />MOD= <br />3EAB <br />"1504-ALLEX" <br />GARAGE AWING: <br />LEFT <br />PAGE: <br />MECHANICAL <br />PLAN <br />160APH M. C <br />