GABLE -END ��
<br />HIPR
<br />,N—
<br />ROOF WIND DESIGN PRESSURES
<br />NET (GROSS) ASCE 7-16
<br />ZONE 1 = 52.70 PSF (62,70) ZONE 3
<br />= 60.50 PSF (70.60)
<br />ZONE 2e = 60.50 PSF (70.50) ZONE 3e
<br />= 69.80 PSF (79.80)
<br />ZONE 2n = 69.80 PSF (79.80) ZONE 3r
<br />= 8310, PSF (93.80)
<br />ZONE 2r = 69.80 PSF (79.80)
<br />"A"= 4'-0" END ZONE DISTANCE
<br />BASIC WAND SPEED: 160 MPH
<br />EXPOSURE CATEGORY: "C"
<br />RISK CATAGORY: II
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT;'P 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/37STRUCTURAL SHEATHING
<br />EXP 1 (40/20), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN.
<br />19/37STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD
<br />AND EDGE SPACING) SEE DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN
<br />NAILS04"O.C. EDGEWISE 2.4 BLOCKING ALL PANEL JOINTS W/IN 4'OF
<br />GABLE END.
<br />ROOF/ WALL/ FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />SIZE
<br />HEAD
<br />LENGTH
<br />DIA.
<br />TENSILE STIR.
<br />SHANK
<br />ASTM
<br />lod
<br />RING SHANK,
<br />2 12'
<br />0131
<br />F1667
<br />170,000
<br />RING
<br />(16-20 RINGS
<br />RSRS-03
<br />8d
<br />RING SHANK
<br />2 318"
<br />0.113
<br />F1667
<br />SCREW SHANK
<br />PER INCH)
<br />RSRS-01
<br />Bd
<br />RING SHANK,
<br />PNEUMATIC
<br />2 3/9'
<br />0,113
<br />F1667
<br />SCREW -NAILS
<br />RSRS-01
<br />EXTERIOR SHEATHING
<br />USE 1/2" CDX OR 7/16" O.S.B. PLY WITH Ed RING SHANK GUN NAILS AT 4"
<br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" OC. TOP &
<br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT T O.C. AT
<br />INTERMEDIATE SUPPORTS OR 7116" ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL.
<br />ZONE 1: 10d NAILS @ 4" O.C. ON EDGE AND 6" O.C. IN FIELD
<br />ZONE 2e, 2n, 2, 10d NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />ZONE 3,3e, 3r 10d NAILS C 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED
<br />AND ADHERES TO ASCE 7-16
<br />WRING SHANK GUN NAAS04'OC.
<br />TOP 4 BOTTOM EDGES
<br />0
<br />B
<br />I
<br />TYP. EXT. SHEATHING
<br />RAFTER UK IHUS6
<br />ROOF SHEATHING
<br />z
<br />3
<br />m
<br />BUILDING LENGTH I,
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />NOTE: GABLES -DROP GABLE END & (1) ADD'L DROPPED
<br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING
<br />16O.C. IF NO DROPPED GABLE END, ATTACH 214 #2 SYP
<br />BLOCKING 0 16" O.C. FIRST 4 BAYS VW (2)12d NAILS EA
<br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/
<br />BLOCKING PER NAILING SCHEDULE
<br />1Od RING SHANK GUN NAILS
<br />SEE "ROOF SHEATHING ATTACHMENT'
<br />TABLE FOR FIELD SPACING
<br />#8 2" DECK SCREWS 0 T-T O.C. MAX
<br />EDGES & 12" O.C. MAX IN FIELD. UNTHREADED
<br />SHANK TO EXTEND BEYOND THICKNESS OF
<br />SUB -FLOOR SHEATHING `
<br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALLEXPOSED MEMBERS
<br />GENERAL NOTES,
<br />ALL AGGREGATE USED IN CONCRETE SHML CONFORM TO ASTM C331C33M. MAXIMUM AGGREGATE SIZE SHALL BE YAP.
<br />STRUCTURAL DRAWINGS SHALL BE USED I N CONJUNCTION WTH JOB SPECIFICATIONS AND
<br />WOOD"
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED 70 EARTH ORWFATFHt
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ARCHITECTURAL DRAWNGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC422020, 71h EDITION
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />POVIDEDRAWINGS. IL CO
<br />PROVIDE 6-MIX CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER All SABSONGROUNDWHHiEINDICATE00N
<br />NE VAPORB RRIER ME
<br />CRIPPLERS ,SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb= 1100 PSI ANDA MODULUS OF
<br />'=
<br />FOR STRUCTURAL CONCRETE, TMS 402/602-16 AISI SPECIFICATION FOR THE DESIGN OF
<br />COLD0.FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONSPRESSURE
<br />LAPPED B INCHES AND ED PE
<br />ELASTICITY 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />TREATED. PRESSURE TREATED BOTTOM PLATE REDUI RED. WOOD FOR NON-STRUCTURAL USES
<br />FORMWORK
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT. DI SODIUM
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT S WILL BE TREATED FOR ANY
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />FORM -NARK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH AG 347 LATEST
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBERTFIAT
<br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM-MRK.
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRALMNGS. FOLLOW WRITTEN DIMENSIONS ONLY, ANY DISCREPANCIES SHALL BE BROUGHT
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FBCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS,
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />OF THE WORK,
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDING
<br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2X STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYP#2'
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />W WIRE MESH'
<br />AT BEARING LOCATIONS W THOUT WOODEN TOP PLATES.
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />WELDED WIRE MESH, SHALL BE ASTM Al OSQA1064M, GRADE 65 AND BE PLACED INACCORDANCE WTH THE
<br />WOOD TRUSSES:
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />AG TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WRE MESH FOR SLABS SHALL
<br />BE SUPPORTED WTH 2" CHAIRS SPACED T-O" OC, EACH WAY.
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE "NATIONAL DESIGN SPECIFICATIONS FOR
<br />REQUIREMENT'S AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />STRESS GRADE LUMBER AND ITS FASTENINGS'THE NFPA. TRUSS DESIGNS SHALL SIGNED AND
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />REINFORCING; STEEL:
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />REBAR SHALL BE ASTM A615A615M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM -15
<br />GRADE 60 IN MASONRY DEFORMED BARS FREE FROM OIL SCALE AND RUSTPLACED
<br />AND IN ACCORDANCE
<br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A, AND SHALL BE HOT -UPPED GALVANIZED.
<br />DESIGN LOADS:
<br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WTH TPI-14, "DESIGN NATIONAL
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />L
<br />STANDARDS FOR METAL-P TRUSS METAL LATEST EDITION'
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf
<br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEERS
<br />BR:, ING
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />MENDA IONS FOR INSTACONSLLATION
<br />20 psf TOP CHORD -no nculnnt
<br />REVIEW
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36"
<br />WOOD TRUSSES.
<br />10 psf BTM CHORD-non-concurrent
<br />#5 BAR - 30" #7 BAR - 42"
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />PROVIDE 36' x 36" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />DEAD LOAD DEAD LOAD
<br />FOR ADDITIONAL INFORMATION.
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WTHANSI/ASCE 788: 1990.
<br />18 psf TOP CHORD 20 psf TOP CHORD
<br />(7 psf w/ ASPHALT SHINGLES) (10 psf w/ N. GYPCRETE)
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />10 PSI`BTM CHORD 5 psf BTM CHORD
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALLAT THE TOP AND BOTTOM WITH
<br />DEAD LOAD TO RESIST W ND UPLIFT: 10psf
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAW NGS FOR ALTERNATE CONNECTION DETAILS AT
<br />BALCONY LIVE LOAD 60 psf
<br />WALL.
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />STAIRS LIVE LOAD 40 psf
<br />VIAND: DEAD LOAD SPEED=10) MPH GUST
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS GUIDE FOR BEARING
<br />SUSECONDC,RI
<br />(ASCE 7-18 (FBC R2020) EXPOSURE C, RISK CATEGORY II)
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LIVE LOADS: UNA NHABIABLE ATTIC WITHOUT STORAGE: UNINHABITABLE ATTIC WTH LIMITED
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />WITH
<br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30ps1, BALCONIES (EXTERIOR)
<br />� NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />AND DECKS: 40ps1, GUARDS AND HANIDRAILS' 200psf, GUARD INIFILL COMPONENTS: 50psf, PASSENGER
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS'.
<br />PROVIDE ENGINEERED SHOP DRAW NGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />40psf
<br />MASONRY:
<br />PLAN SHOVING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WTH ALL REQUIREMENTS OF THE
<br />LICENSED PROFESSIONAL ENGINEER.
<br />SHOP DRAWING REVIEW:
<br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />SHOP DRAWINGS WlL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />THE MASONRY STANDARDS JOINT COMMITTEE.
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />COMPLIANCE WTH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH' ELEVATIONS DIMENSIONS ETC.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT.
<br />MANUFACTURED IN CONFORMANCE WTH ASTM C-90, GRADE iM = 2000 PSI, BLOCK SHALL BE PLACED USING
<br />OF THE DELEGATED TRUSS ENGINEER. VIAND UPLIFT VALUES RAVE BEEN BASED ON ASCE 7-16 COMPONENT
<br />AND CLADDING VIAND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />DRAW NGS SUBMITTED W THOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAW NGS IN THE FORM
<br />THERW
<br />PLIANT NIG BOND UNLESS OTHERW SE NOTED. 1AV11P MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />PLACING CONCRETE FOR COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WTH
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAW NGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN, THE GROUT MIX SHALL HAVE A MAXIMUM 318"
<br />WRITING BY THE ARCHITECT.
<br />COURSE AGGREGATE, AND SHALL BE PLACED W A SLUMP OF 6" TO 10". USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />FOUNDATION/ SITE PREPARATION'
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING
<br />TYPE A" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE
<br />PROPORTIONEDAND MIXEDASOUTLINEDUNDERASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WTH ASTM D-1557. TREATALL
<br />SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />CELLS TO BE FILLED.
<br />SOIL FOR TERMITE PROTECTION.
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />THE OWNER SENILE RETAIN THE SERVICES OF AN INDEPENDENT CEO -TECHNICAL ENGINEER TO VERIFY
<br />REINFORCING.
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEETTHE
<br />GEO-TECHNICAL ENGINEERS REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTEDATTRE
<br />CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEENMETSHALL
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />CONCRETE:
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB-0GRADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5` STRUCTURAL TERRACE SLAB
<br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HSTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PROR TO
<br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5' 4- PRIOR TO THE ADDITION OF PLASTICIZER
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94IC94M OR MEASURING, MIXING, TRANSPORTING,
<br />ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN
<br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 9D MINUTES. IF FOR ANY REASON
<br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MNUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL
<br />BE THE RESPONSBLITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY
<br />NON COMPLIANCE WTH THE ABOVE
<br />REQUIRED CONCRETE COVERAGE OVER REBARSHALL BE AS FOLLOWS:
<br />A 3"FORCONCRETE CAST AGAINST AND PERMANENTLYDTO,SEDTOEWTH(FOUNDATIONSY
<br />B. FOR CONCRETE EXPOSED TOURTHANDORWEATHER
<br />1-112- FOR #5 AND SMALLER
<br />T FOR #6 AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />3/4" FOR SLABS WALLS AND JOISTS
<br />1-1R' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O
<br />STRUCTURALSTEEL:
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WTH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36/A36M, Fy = 36 ksi FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM
<br />A5D0/A500M, GRADE B, Fy = 46 kai. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S, Fy =
<br />SEW. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WTH DOUBLE -NUT LEVELING. ALL
<br />OTHER BOLTS SHALL BE ASTM F3125/F3125M BOLTS WTH WASHERS UNDER THE TURNED ELEMENT. BOLTS
<br />SHALL BE TIGHTENED IN ACCORDANCE WTH THE TURN-0FF-THE-NUT METHOD.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK FASTENERS
<br />FASTENER
<br />APPI—TON
<br />.1.
<br />TYPE
<br />sRADNG
<br />REMARKS
<br />APPLICATION
<br />S.
<br />REMARKS
<br />RRINGTO
<br />INC.
<br />CASE HARDENm COL
<br />f f?LONG.
<br />a"�
<br />GARAGE DOOR BII"X
<br />NRY/COlC
<br />a OA'
<br />f f/]"ENBEd'ENDgBi.,
<br />SGD, X.—DOORS
<br />-HA
<br />9"OF
<br />WINDOVA -I FASTENED
<br />GARABEDWRBUCK
<br />Ofc (Ne'OW
<br />F20
<br />x"EMII-DGE
<br />i, eEENOTEB
<br />NAL1 -LONG.
<br />STAGGERED
<br />INTO M49JNRY/GOING.
<br />O MASDNRv/�NC.
<br />EXPAN91 OY BJLT
<br />2C'OIC (V1'OW)
<br />DST.D�
<br />wNDD BIxM(
<br />CASE HWDENM-L
<br />wlNDowiDooR/FAeTENED
<br />METAL STRAPT0
<br />CONTACT THIS ENGINEER
<br />FOR SPACING
<br />vT, sEENOTEs
<br />NAL1 ur'LofNc.
<br />GERm
<br />INTOr4A8DNRY�
<br />MrsoNRr/coN.
<br />REQUIREMENTS
<br />Exr. SNING DOOR (2)VI—I TAP0- 1B„- rz"EMeEp. B'ENO.
<br />BUCK2r 11, EEE_E _ ER ASTNER 12"EDGE.ST.
<br />Tx PTWINDOWBUCK E2211. 9S.-< ENDDIST.
<br />P O8 STEEL
<br />EL COL., 01WI WA31 T EREO EDGE S
<br />1LES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURERS SPECS AND /OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. RAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />6. W NDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1. MEMBERS ARE NAILED AND
<br />2.MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE.
<br />1 N. RONALD REAGAN BLVD.
<br />LONGWOOD, FL 32750
<br />PH: 407-774-6078
<br />FAX: 407-774-4078
<br />www.abdesWigmup.POm
<br />AA #: 0003325 J
<br />V
<br />O
<br />a
<br />a
<br />StmDIv. Tee LOT:
<br />ABBOTT PARK
<br />LOT #35
<br />BLK. #7
<br />PROJMCT#
<br />04181.000-35071
<br />MODEL:
<br />4EBB
<br />"1828—CALL"
<br />GARAGE STUNG:
<br />RIGHT
<br />PAGE':
<br />DETAILS
<br />160 MPH EXP. C
<br />,I; MAL
<br />L AR NO 93723 i
<br />DATIM 9/21/21
<br />SCALE: 1/4"=1'—O"
<br />SHEET
<br />s N1