Laserfiche WebLink
ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-16 <br />ZONE 1 = 52.70 PSF (62.70) ZONE 3 = 60.50 PSF (70,50) <br />ZONE 2e : 60.50 PSF (70.50) ZONE 3e = 69.80 PSF (79.80) <br />ZONE 2n = 69.80 PSF (79.80) ZONE 3r = 83.80 PSF (93.80) <br />ZONE 2T = 69.80 PSF (79,80) <br />"A"= 4'HO" END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />EXPOSURE CATEGORY: "C" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT: -1- 0.18 <br />ROOF DMIPHIMOM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/32" STRUCTURAL SHEATHING <br />EXP 1 (401 FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN. <br />19/32, STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL <br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN <br />NAILS 4"O.C. EDGEWISE 2x48 OCKING ALL PANEL JOINTS W/IN L 4 OF <br />GABLE END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL REQUIREMENTS <br />SIZE <br />HEAD <br />LENGTH <br />DIA. <br />TENSILE STR. <br />SHANK <br />ASTM <br />10d <br />RING SHANK, <br />212" <br />0,131 <br />F1667 <br />SC SHANK <br />170,000 <br />RING <br />(16-20 RINGS <br />RSRS-03 <br />Btl <br />RING SHANK, <br />23/6' <br />0,113 <br />F1667 <br />SCREW SHANK <br />PERINCH) <br />RSRS-01 <br />8d <br />RING SHANK, <br />PNEUMATIC <br />2 3/6' <br />0.113 <br />F1667 <br />RSRS41 <br />SCREW -NAILS <br />EXTERIOR SHEATHING <br />USE 12" COX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4" <br />O.C. AT PANEL SIDES AND Sd RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND Sd RING SHANK GUN NAILS AT 6' O.C. AT <br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />BUILDING LENGTH <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />ZONE 1: 10d NALS 0 4" OON EDGE AND 6' O.C. IN FIELD <br />ZONE 2e, 2n, 21 1Od NAILS 0 4" O.0.C.. ON EDGE AND, <br />FIELD <br />ZONE 3,3e, 3r 10d NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />18 <br />NaM ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />So RING SHANK GUN NAILS Q 4' OC. <br />TOPS BOTTOM EDGES <br />Q <br />�N <br />Rio <br />B <br />RAFTER OR TRUSS <br />ROD, SHEATHING --, <br />■mmmmIt 11 <br />I <br />I <br />I <br />11 <br />NO..M GABLES -DROP GABLE END S. (1) ADD'L DROPPED <br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING <br />16'0.C. IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP <br />BLOCKING 0 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />- 1. RING SHANK GUN NAILS <br />SEE"ROOF SHEATHING ATTACHMENT" <br />TABLE FOR FIELD SPACING <br />C#8 2' DECK SCREWS @ 6'A" O.C. MAX <br />EQGES & 1Z' O.C. M#X IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCH TECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS, APPLICABLE BUILDING CODE STANDARDS: FSCHN 2020, 7th EDITION <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, TMS 4021602-18 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 746 AND RISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />OF THE WORK. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS, <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS, <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />DESIGN LOADS: <br />ROOF: LIVE LOAD FLOOR. LIVE LOAD 40 psf <br />20 psf TOP CHORD nonconcv-t <br />10 psf BTM CHORD --Gent <br />DEAD LOAD DEADLOAD <br />15 pN TOP CHORD 20 psf TOP CHORD <br />(7 paf w/ ASPHALT SHINGLES) (10 pef w/ No GYPCRETE) <br />10 psf BTM CHORD 5 psf BTM CHORD <br />DEAD LOAD TO RESIST WIND UPLIFT: IOpsf <br />BALCONY LIVE LOAD 60 psf <br />STAIRS LIVE LOAD 40 psf <br />WIND: DEAD LOAD SPEED =160 MPH 3-SECOND GUST <br />(ASCE 7-16 (FBC R2020) EXPOSURE C, RISK CATEGORY III, <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10psf, UNINHABITABLE ATTIC WITH LIMITED <br />STORAGE: 20paf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS. 30psf, BALCONIES (EXTERIOR) <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />VEHICLE GARAGES: 50pef, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30p d, STAIRS: <br />40psf <br />SHOP DRAWING REVIEW: <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />COMPLIANCE WTH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL SHOP DRAW NGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />DRAWINGS SUBMITTED WTHOUT REVIEW DULL BE RETURNED UNCHECKED, SHOP DRAW NGS IN THE FORM <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAW NGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />WRITING BY THE ARCHITECT. <br />FOUNDATIOW SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL <br />SOIL FOR TERMITE PROTECTION. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS, LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTEDAT THE <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />COMMM' <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2 500 PSI REGULAR WEIGHT FOR FOOTINGS AND SLAB-OGRADE-ORADE <br />3 000 PS REGULAR WEIGHT FOR BEAMS COLUMNS AND 5" STRUCTURAL TERRACES LAB. <br />CONTRACTOR SHAH SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5".f-PRIOR TO THE ADDITION OF PLASTICIZER <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C3VC33M. MAXIMUM AGGREGATE SIZE SHALL BE 3W. <br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER WWNDARING WOOD WALLS TOP PLATES &STUDS CAN BE SPF. <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 31P. <br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABSAN-GROUND WHERE INDICATED ON <br />DRAWINGS. SEAMS LAPPED 6 INCHES AND SEALED WITH ADHESIVE TAPE <br />FORM-WOPoC: <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />EXCLUSIONS FROM THESE PLANS: <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO, 2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />SHALL BERATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />MINIMUM NAILING PER FBCR 2020, 7th EDITION, SEE NAILING SCHEDULE ON PLANS. <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDING SYP ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAYBE REQUIRED BUT ARE BY OTHERS. <br />WELDED WIRE MESH: <br />WELDED WIRE MESH, SHALL BE ASTM A1064/A1064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />BE SUPPORTED WITH 2" CHAIRS SPACED TAD' OC EACH WAY, <br />REBAR SHALL BE ASTM A61 SAMSM GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />GRADE 601N MASONRY DEFORMED BARS FREE FROM OIL, SCALE RUST A P E E L, AND US AND LACED IN ACCORDANCE <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />CONTRACTOR SHALL SUBMIT REBAR RAVINGS SHOP FOR REVIEW PRIOR T O D R O O FABRICATION. HORIZONTAL <br />AND VERTICAL BARS SHALL LAPBx BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJE <br />CT TO ENGINEER'S <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36" <br />#5 BAR - 30" #7 BAR - 47' <br />PROVIDE 3W x 36" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION. <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />WALL. <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />MASONRY: <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WTH ALL REQUIREMENTS OF THE <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />THE MASONRY STANDARDS JONT COMMITTEE. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fm = 2000 PSI. BLOCK SHALL BE PLACED USING <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WTH <br />ASTM C478 AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 <br />DAYS UNLESS <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8" <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF B" TO 10". USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />CELLS TO BE FILLED. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />STRUCTURAL STEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36/A36M, Fy = 36 ksi FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A500fA500M GRADE B F = 46 kai. STRUCTURAL PIPE SHALL BE ASTM 53/A53M GRADE TYPE E OR F = C S A DE B Y � � � Y <br />35 ksi. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WTH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM F3125/F3125M BOLTS WTH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WTH THE TURN-OFF-THEHNUT METHOD. <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM CSVCHM OR MEASURING, MIXING, TRANSPORTING, ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL.J-BOLTS ARE TO BE STEEL. <br />ETC. CONCRETE TICKETS SRALL BE TIME4TAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIMEALLOWED FROM WHEN <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MNUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WITH THE ABOVE <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A 3" FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS). <br />B. FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER <br />i-VY FOR 05 AND SMALLER <br />T FOR #6 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3/4' FOR SLABS, WALLS AND JOISTS <br />14/2' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />WOOD TRUSSES: <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE 'NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS" BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A446/A446M GRADE A AND SHALL BE HOT -DIPPED GALVANIZED. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />STANDARDS FOR METAL-PLATELONNECTED-WOOD TRUSS CONSTRUCTION:, AND "BCSI LATEST EDITION' <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />WOOD TRUSSES. <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS VVITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSUASCE 7 88: 1990. <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWWNGS FOR ALTERNATE CONNECTION DETAILS AT <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />PLAN SHOW NG COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />LICENSED PROFESSIONAL ENGINEER. <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />PROVIDED BY THE TRUSS ENGINEER. <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />OF THE DELEGATED TRUSS ENGINEER. W ND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />AND CLADDING W ND LOAD PRESSURES, THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK FASTENERS <br />FASTENER <br />APPLIGTION <br />S. <br />1 TYPE <br />SPACING <br />SITE <br />TYPE <br />SPAONG <br />REMARKS <br />PTFlIRRINGTO <br />CASEIWRGENEDCOL <br />GARAOEDOOHWG( <br />1N•D0. <br />TAPCON MASONiY <br />rz' EM... P END DST., <br />/CONC. <br />NNL I III LONG. <br />SQC <br />TO MASONriIWNC. <br />NG14 ES <br />FASTENER <br />SOC <br />rz'EDGE.. <br />ALT <br />CASE HARDENEDOUII <br />YOC <br />WINDOWIOOORI FASTENED <br />GMAOE DOOR &1Cl( <br />SN DA OR <br />8.OIC <br />1-1A) <br />EMaEO. 4•E-..T., <br />SEENOS <br />NNLI III LONG. <br />STAGGERED <br />TO MASONRYIWNC. <br />R'M AY WASHED <br />E%PPNSCN BOLT <br />O,C U"DA) <br />I-EDGE­ <br />.I- BUG( <br />. PT, SEENOTES <br />CASEHARDENEDCOIL <br />NNL111YLONG. <br />S"DID <br />STAGGERED <br />WINDOWICOOPoFASTENED <br />INTo MASONRYIWNO. <br />METAL STRAP TO <br />MasoNRvrconc. <br />CONTACT THIS ENGINEER FOR SPACING <br />REQUIREMENTS <br />EXT NG DOOR <br />S.A.PT,SEENDTES <br />(]Iy14DIa <br />NDWASHER <br />"TAPCON' <br />FAST- <br />IS OC <br />IIIEMSED, S-END <br />DST.,I III EDGE DST <br />NGNAEANNGWOOD <br />WALLTOCONC. SLAB <br />Irz"- EXPANSION 4'EMBED. 4'EIO <br />W/WASHER BOLT l4 OC .3•EWEgST. <br />2vT TWNOOWeUO( 0.138•PAFS]tR' B"OIC a•END. OST..112 <br />P OSNGTE. .SEE WASHER STAGGERED EDGEDSTWM <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND/ OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUN PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SMALL BE AS DUDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WTHA W000 DOOR FRAME. ix MEMBERS ARE NAILED AND <br />MEMBERS ARE SECURED WI TAPCONS OR PAF TO THE SUBSTRATE. <br />•1 N. RONALD REAGAN BT <br />LONGWOOD, FL 327E10 <br />PH: 407-7746078 <br />FAX: 407-7744078 <br />www.abdesigngroup.com <br />AA M. 0003325 <br />W <br />Y <br />tt <br />S <br />jjjlll���fffjj <br />a <br />p <br />BUDDrw. at LOT: <br />ABBOTT PARK <br />LOT 34 <br />BLK. 7 <br />PROJECT <br />04181.000 34071 <br />�[ODEXA <br />3EAB <br />"1504-ALLE)C' <br />GARAGE 81TMG: <br />LEFT <br />PAGE: <br />DETAILS <br />16 H E <br />1 8CALE: 1/4 1'-0"' 1 <br />S N1 <br />TYP. EXT. SHEATHING ATTACHMENT <br />