w <br />a <br />10 <br />GABLE -END <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-10 <br />ZONE 1 = 23.79 PSF (33.79) <br />ZONE 2 = 39'48 PSF (49.48, <br />ZONE 3 = 67.16 PSF (77.16) <br />"A"= W_0' END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />WIND EXPOSURE: 'C" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT, 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16" <br />O.S.B. OR 112"COX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. 518 COX EXT. PLYWOOD, WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND 8d RING SHANK GUN NAILS <br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL, <br />ROOF SHEATHING TO GABLE END FRAME USE <br />8d GUN NAILS @ 4" O.C. EDGEWISE 2x4 <br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE <br />END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. DIA. <br />SHANK <br />TENSILE STR. <br />SHANK <br />Bd <br />RING SHANK, <br />2 112" <br />0.120" <br />170,ODO <br />(18-20 RINGS <br />SCREW SHANK <br />PER INCH) <br />8d <br />SCREW SHANK <br />21/2" <br />0.120" <br />PNEUMATIC <br />SCREW -NAILS <br />1. NAIL SIZE PER ASTM F1664 <br />2. INTERNATIONAL STAPE, NAIL & TOOL <br />ASSOCIATION (ISANTA) ESR-1539 <br />EXTERIOR BHEA7F#NO <br />USE 1/2" COX OR 7116" O.S.B. PLY WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES <br />AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND Bd RING SHANK GUN <br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS <br />OR 7116" 7JP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />8d RING SHANK GUN NAILS @ 4" O.C. <br />.. TOP & BOTTOM EDGES .. <br />Z9 <br />0 w , <br />z <br />, <br />� <br />Y <br />z . <br />T <br />z LU <br />z0 <br />Uw <br />Y (off <br />SO <br />O `v <br />J <br />2 N <br />N. <br />(7 <br />U w <br />m� o <br />W <br />a <br />TOP CORD BLOCKING AT N <br />O.C. MAX. IN FIRST 2 FRAMING <br />SPACES AT EACH END. <br />RAFTER OR TRUSS <br />O!tlYF CNCITLIIN!_ <br />.--_—I <br />._--M,I <br />ROOF. SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />Sd RING SHANK GUN NAILS <br />(B 6" O.C. IN FIELD ` <br />C8d RING SHANK GUN NAILS 0 12" O.C. IN <br />FIELD or 8d x 2 112" SCREW SHANK <br />PNEUMATIC SCREW -NAILS @ 12" 0.&.jN <br />FIELD J\ <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />ROOF. SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />Sd RING SHANK GUN NAILS <br />(B 6" O.C. IN FIELD ` <br />C8d RING SHANK GUN NAILS 0 12" O.C. IN <br />FIELD or 8d x 2 112" SCREW SHANK <br />PNEUMATIC SCREW -NAILS @ 12" 0.&.jN <br />FIELD J\ <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTMC33 MAXIMUM AGGREGATE SIZE SHAH BE 31T <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />WOOD, <br />ARCHITECTURAL. MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />PROVIDE B%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER <br />NON -BEARING WOOD WALLS TOP PLATES S STUDS CAN BE SPR <br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FEI 2017, S61 EDITION <br />ALLEXPOSEDEDGES OF CONCRETE ARE TO BE CHAMFERED 314'. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />CRIPPLERSSILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER Fb = 1100 PSI AND A MODULUS OF <br />FOR STRUCTURAL CONCRETE, ACI 53D-13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF <br />PROWDE 84ML CONfIN0009 POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SW35-0NCROIRID WHERE INDICATED ON <br />POLYETHYLENE <br />NE VAPORLED <br />ELASTICITY*- 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS <br />DRAWINGS BEAMS LAPPED SPOLYE <br />AND M ADHESIVE TAPE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONSTRUCTURAL USES <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORMWORK <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE, NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347, <br />W/ DOT SHALL BE HOT DIPPED GAILY. FOR STRUCTURAL USES, AVOID SWING TREATED LUMBER THAT <br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS <br />MINIMUM NAILING PER FSCR 2017, 6tn EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALOEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS, <br />SYp 02. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REQUIREMENTS AND SLA60N-GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />DO NOT SCALE DRAWINGS, THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL PRIOR <br />DIMENSIONS <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />DESIGN LOADS: <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf <br />20 p3f TOP CHORD -rroD-DOncurrent <br />10 pet BTM CHORD -rIc,I arrent <br />DEAD LOAD DEAD LOAD <br />15 pH TOP CHORD 20 psf TOP CHORD <br />(7 psf w/ ASPHALT SHINGLES) (10 Psf w/No GYPCRETE) <br />10 psf BTM CHORD 5 psf BTM CHORD <br />WELDED WIRE MESH: <br />WELDED WIRE MESH, SHALL BE ASTM Al 85, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE <br />SUPPORTED WITH 2' CHAIRS SPACED T-O' OC, EACH WAY. <br />REINFORCING STEEL: <br />REBAR SHALL BE ASTM AS15 GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A616 <br />GRADE 80 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36" <br />#5 BAR - 3W #7 BAR - 42" <br />PROVIDE 36' x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION. <br />WOOD TRUSSES: <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A. AND SHALL BE HOT -DIPPED GALVANIZED. <br />DESIGN, FABRICATE. AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, -DESIGN NATIONAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND TPIAVTCA BCSI 1" <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING INSTALLATION BRACING METAL -PLATE -CONNECTED <br />WOOD TRUSSES. <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WITH GUSSETS. CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982, <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: IOpaf <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 PIT <br />WALL. <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL, <br />STAIRS LIVE LOAD 40 psf <br />WIND: DEAD LOAD MPH S- SECOND GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />(NICE 7-10 FBCSPER2017) EXPOSURE C, RISK CATEGORY 10 <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLELIVE FOR FINAL <br />BLE ATTIC UNINHABITABLE ATTIC WITH <br />LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />WITH (0 <br />STAIRS: BALCONIES (EXTERIOR) <br />STORAGE: BALCLIMIONIES <br />STORAGE: HABITABLE ATTICS AND ATTICS SERVED WITH FILL <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />! 40p COMPONENTS: <br />AND DECKS: dOpsf GUARDS AND HANDRAILS: 200paf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />C <br />WITHOUT THE APPROVAL OF THE ENGINEER, <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE Of TRUSSES. THE TRUSS FABRICATOR SHALL <br />VOEpHI LE GARAGES: 50paf, ROOMS OTHER THAN SLEEPING ROOM: 40ps1, SLEEPING ROOMS: 30PS1, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />sf <br />MASONRY: <br />PLAN SHOWING COMPONENT LAYOUT, SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: <br />'SPECIFICATION MASONRY STRUCTURES' (ACI 6301 ASCE 5/TMS 402, BUILDING CODE REQUIREMENTS FOR <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM GOD, GRADE fm - 1500 PSI. BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM C476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />ALL SHEET METAL FRAMING CONNECTORS SHOWN ON THE PLANS SHALL BE "USP STRUCTURAL <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN, THE GROUT MIX SHALL HAVE A MAXIMUM 3/8' <br />CONNECTORS" BY LISP, OR EQUAL UNLESS NOTED OTHERWISE ON PLANS, INSTALL CONNECTIONS <br />WRITING BY THE ARCHITECT, <br />COURSE AGGREGATE, AND SHALL BE PLACED W/A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION <br />WITH THE SIZE AND NUMBER OF BOLTSINAILS AS RECOMMENDED BY THE MANUFACTURER IN THE <br />TO CONSOLIDATE GROUT, <br />LATEST CATALOG. <br />FOUNDATION/ SITE PREPARATION: <br />"M" "S" <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE Of 2,000 psl, FOOTING <br />TYPE OR MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SWILL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE <br />SHALL BE 3/8' THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL <br />CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />REINFORCING. <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL REBAR 6 X BAR NO. (48 SAR DIAMETERS)., U.N.O. <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />STRUCTURAL STEEL: <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MY DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIORTO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED S d-PRIOR TO THE ADDITION OF PLASTICIZER <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36, Fy - 36 kal FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM AS00, GRADE B, <br />Fy = 46 ksl. STRUCTURAL PIPE SHALL BE ASTMS3, GRADE 8, TYPE E OR S, Fy = 35 ksL TUBE AND PIPE <br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />CONCRETE SHALL COMPLYWITHALL THE REQUIREMENTS OF ACI 301 AND ASTMC-040R MEASURING, MIXING, TRANSPORTING, ETC. ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL.J-BOLTS ARE TO BE STEEL. <br />CONCRETE TICKETS SHALL BE TIMEZTAM3ED WHEN CONCRETE IS BATCHED, THE MAXIMUM TIME ALLOWED FRDM WHEN WATER IS <br />ADDEDTO THE MX UNTIL R IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MNLRES. IF FOR ANY REASON THERE 18 A <br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN w MINUTES, THE CONCRETE SHALL NOT BE PLACED, R SHALL BE THE <br />RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON <br />COMPLIANCE WITH THE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER RESAR SHALL BE AS FOLLOWS: <br />A 3' FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS): <br />B. FOR CONCRETE EXPOSED TO EARTH ANDAOR WEATHER <br />1-1/2'FOR N 5 AND SMALLER <br />T FOR ai AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3/4' FOR SLABS, WALLS AND JOISTS <br />1-iQ' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />FASTENER SCHEDULE <br />WINDOW AN <br />O DOOR BUCK <br />FASTENERS <br />FASTENER <br />_1oAT_ <br />SITE <br />TYPE <br />SPACING <br />REIMRxS <br />APPLIGTpN <br />SQE <br />TYPE <br />9PACWG <br />REMARKS <br />I—FURRMOTO <br />GSEHARDENEDC00. <br />DARAGEDOORBUOK <br />fN'DIA <br />TAPCON MAa I <br />I-EM .1-END I. <br />MASONRY/LONG. <br />NAIL 11/Y LONG. <br />�� <br />TO MASONRYIOONC. <br />ND WASHER <br />FA —ER <br />S•QG <br />114•EOGE D.T. <br />SOD, AL.E DOORS <br />1KP,SEENITEB <br />GSE HAROENE0000. <br />NMLIIIT LONG. <br />YOIC <br />STAGGERED <br />WNDOWITAOR/FASTENED <br />INTO M190NRY, <br />ORANGE DOOR BACK <br />TO MA90NRYICONC. <br />III DU.WI <br />WASHER <br />E%PANSpN BOLT <br />]A'OIC <br />PEMBED-PEA GIST., <br />TED. DIET. <br />WwOOWSUOK <br />CASE HARDENED WIL <br />FDIC <br />WINDOWNGORPASTENED <br />METAL STRAP TO <br />CONTACT THIS ENGINEER FOR SPACING <br />I. PT, SEE ACTEB <br />NAIL III LONG, <br />STAGGERED <br />INTO MA80NRYiCONC. <br />MA90NRYI—G.. <br />REQUIREMENTS <br />EM.SWNG DOOR <br />p)3I18.OLA. <br />TAPCON <br />I I1EMBE0,6'EN1, <br />NONSF.AWNGWWD <br />IL EXPANSION 1-EMSED. PENS <br />SUE( L PT,EEENOTEa <br />NO —ER <br />FASTNER <br />t8'gC <br />OAST., I III EDGE OUT. <br />WALL TO CONC,SUB <br />WI WASHER BOIi L•OIC OUT.,3• EDGE GIST. <br />LO WINO COL. K 38'PAFA3IAF POC FEND DUT., 11? <br />PT TO STEEL COL. O 'WI WASHER STAGGERED EOOEDUT. <br />NOTES <br />1, STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />/. PAF SHALL BE HILT[ X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE MCA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD <br />LONGWOOD,FL32750 <br />PH: 407-7746078 <br />FAX: 407-7744078 <br />www.abdosigngfoupcom <br />AA N: 0003325 do <br />all <br />O <br />C <br />SUDDIV. k LOT <br />ABBOTT PARK <br />LOT #4 <br />BLK #10 <br />PROJECT#G <br />04181.000-04103 <br />MODEIA <br />3ELB <br />"1239-LAYTON" <br />GARAGE 8WING: <br />LEFT <br />PAGE: <br />DETAILS <br />160 MPH EXP. C <br />PRINT DATIc 11/25/19 <br />EC A,LE: 1/4"=1'—O" <br />a SN1 <br />