NIP Roof.k
<br />ROOF WIND DESIGN PRESSURES
<br />NET (GROSS) ASCE 7-16
<br />ZONE 1 = 58.00 PSF (68.00)
<br />ZONE 3 = 66.50 PSF (76.50)
<br />ZONE 2e = 66.50 PSF (76.50)
<br />ZONE 3e = 76.60 PSF (86.60)
<br />ZONE 2n = 76.60 PSF (86.60)
<br />ZONE 3r = 91.70 PSF (101.70)
<br />ZONE 2r = 76.60 PSF (86.60)
<br />"A"= 4'-0" END ZONE DISTANCE
<br />BASIC WIND SPEED: 16Q MPH
<br />EXPOSURE CATEGORY: "C"
<br />RISK CATAGORY: II
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT: +1- 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/32" STRUCTURAL SHEATHING
<br />EXP 1 (4020), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN.
<br />19/32" STRUCTURAL SHEATHING EXP 1 (402O).(SEE TABLE FOR FIELD
<br />AND EDGE SPACING) SEE DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN
<br />NAILS@4"O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/IN 4'OF
<br />GABLE END.
<br />ROOF/ WALU FLOOR
<br />.qHFATHIN(,
<br />FASTENER SCHEDULE
<br />SIZE
<br />HEAD
<br />LENGTH
<br />DIA.
<br />TENSILE STR,
<br />SHANK
<br />ASTM
<br />10d
<br />RING SHANK,
<br />21/2'
<br />0131
<br />F1667
<br />SCREW SHANK
<br />170,000
<br />RING
<br />(16-20 RINGS
<br />RSRS-03
<br />8d
<br />RING SHANK,
<br />23/8"
<br />0.113
<br />F1667
<br />SCREW SHANK
<br />PER INCH)
<br />RSRS-01
<br />8d
<br />RING SHANK,
<br />PNEUMATIC
<br />23/8"
<br />0.113
<br />F1667
<br />SCREW -NAILS
<br />RSRS-01
<br />EXTERIOR SHEATHING
<br />USE 12" CDX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4"
<br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP &
<br />BOTTOM PANEL AND Btl RING SHANK GUN NAILS AT 6' O.C. AT
<br />INTERMEDIATE SUPPORTS OR 7116" ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUR SPECS.) SEE DETAIL.
<br />ROOFS EATRiiG ATTACHEMW BPACM
<br />ZONE 1: 10d NAILS @ 4" O.C. ON EDGE AND 6" O.C. IN FIELD
<br />ZONE 2e, 2n, 2r: 10d NAILS @ 4" O.C. ON EDGE AND 4" O.C. INFIELD
<br />ZONE 3,3e, 3r 10d NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />KVM
<br />ROOF SHEATHING THICKNESS WAS CALCULATED
<br />AND
<br />ADHERES TO ASCE 7-16
<br />W RING SHANKGUNN SQ4"O.C.
<br />OP 4 BOTTOM EDGES
<br />...........w
<br />�
<br />y
<br />Z
<br />z
<br />x D
<br />z w
<br />< LL
<br />I z
<br />y0
<br />a
<br />z O
<br />W
<br />`
<br />6
<br />TYP FXT CIJFATHING A-14MENT
<br />RAFTER OR TRUSS
<br />ROOF SHEATHNr;
<br />■����11 11
<br />I
<br />I
<br />Y BUILUINI 1--IH
<br />ROOF SHEATHING LAYOUT Jf'
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />NOTE GABLES -DROP GABLE END & (1) ADUL DROPPED
<br />TRUSS 2.4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING @
<br />16'O.C. IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP
<br />BLOCKING @ 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA -
<br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/
<br />BLOCKING PER NAILING SCHEDULE
<br />1W RING SHANK GUN NAILS
<br />SEE"ROOF SHEATHING ATTACHMENT'
<br />TABLE FOR FIELD SPACING
<br />C#8 2" DECK SCREWS @ 6'S" O.C. MAX @
<br />QG EES & 12' O.C. MAX IN FIELD. UNTHREADED
<br />SHANK TO EXTEND BEYOND THICKNESS OF
<br />SUB -FLOOR SHEATHING
<br />I TP. N4" I &G SUB-I-LUUH UEUKING GLU EU 10 ALL EXPUSEU MEMBERS
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS. AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPUCABLE BUILDING CODE STANDARDS: FBCR 2020, 7th EDITION
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />FOR STRUCTURAL CONCRETE, TMS 4021602-16 AISI SPECIFICATION FOR THE DESIGN OF
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />OF THE WORK.
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33IC33M. MAXIMUM AGGREGATE SIZE SHALL BE 3/4".
<br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED Y4".
<br />PROVIDES-MIl CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS -ON GROUND WHERE INDICATED ON
<br />DRAWINGS. SEAMS LAPPED 61NCHES AND SEALED WITH ADHESIVE TAPE.
<br />FORMWORK:
<br />FORM-VV0 RK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS. COLUMNS, WALLS,
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST
<br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM-VVDRK.
<br />EXCLUSIONS FROM THESE PLANS:
<br />WOOD:
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES. BRACING, LEDGERS, BLOCKING,
<br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. Fb = 1100 PSI ANDA MODULUS OF
<br />ELASTICITY = 1,400.000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONSTRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />MINIMUM NAILING PER FBCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. SYP #2.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS �� ME AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, WELDED WIRE MESH, SHALL BE ASTM A1064/A1064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL TRUSSES'
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE "NATIONAL DESIGN SPEC
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION BE SUPPORTED WITH 2' CHAIRS SPACED 3'-0' OC, EACH WAY. WI I SPECIFICATIONS FOR
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. STRESS -GRADE LUMBER AND ITS FASTENINGS'BY THE NFPA. TRUSS DESIGNS SHALL O SIGNED AND
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR REINFORCING STEEL CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. REBAR SHALL BE ASTM M15AO15M GRADE 401N CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 MEETING THE REQUIREMENTS OF ASTM A446/A44614, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED.
<br />GRADE 601N MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUSTAND PLACED IN ACCORDANCE
<br />DESIGIN LOADS: W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "BCSI LATEST EDITION"
<br />AND VERTICAL BARS SHALL LAP 6. BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf REVIEW. WOOD TRUSSES.
<br />20 psf TOP CHORD-n-ooncumnt TYP. MIN LAPS SHALL BE AS FOLLOWS' #4 BAR - 25" #6 BAR - 36"
<br />10 psf BTM CHORD -on RoRt 05 BAR - 30" #7 BAR - 42"
<br />RUN REINFORCING BARS CONT NUOUSLY LAPP F
<br />PROVIDE 36'x 36-CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />TRUSS MANUFACTURER VIA LL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />DEAD LOAD
<br />DEAD LOAD
<br />FOR ADDITIONAL INFORMATION.
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANS#ASCE 788: 1990.
<br />15 pH TOP CHORD
<br />20 psf TOP CHORD
<br />(7 psl wl ASPHALT SHINGLES)
<br />(7
<br />(10 psf wl No GYPCRETE)
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO NIANUFACTURER'SANSTRUCTIONS.
<br />10 psf BTM CHORD
<br />5 psf BTM CHORD
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />DEAD LOAD TO RESIST WIND UPLIFT: 10psf
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />BALCONY LIVE LOAD SO Psf
<br />WALL
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL
<br />STAIRS LIVE LOAD 4o psf
<br />NAND: DEAD LOAD SPEED =160 MPH 3- SECOND GUST
<br />(ASCE 7-16 (FBC R2020) EXPOSURE C. RISK CATEGORY II)
<br />I ED AT SPLICES AND AROUND CORNERS. DOWEL
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />ROOF & LOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FORBEARING
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE, TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10psf, UNINHABITABLE ATTIC WITH LIMITED
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR)
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM40psf, SLEEPING ROOMS' 30psf STAIRS'
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />40psf
<br />MASONRW:
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />LICENSED PROFESSIONAL ENGINEER.
<br />SHOP DRAWING REVIEW:
<br />'SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY
<br />7HE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />THE MASONRY STANDARDS JOINT COMMITTEE.
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY LENGTH ELEVATIONS DIMENSIONS ETC.
<br />' �
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />MANUFACTURED IN CONFORMANCE WITH ASTM CEO. GRADE fRI = 2000 PSI. BLOCK SHALL BE PLACED USING
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT.
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF T E BEAMS BEFORE
<br />I
<br />AND CLADDING WAND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS)ARE PROHIBITED
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />WRITING BY THE ARCHITECT.
<br />FOUNDATION/ SITE PREPARATION:
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF ZMD psf, FOOTING
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST %%OF THE
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL
<br />SOIL FOR TERMITE PROTECTION.
<br />THE OWNER SHALL RETAIN THE SERVICES OFAN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED ATTHE
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />CONNCRESHAL ETTEALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB
<br />CONTRACTOR SHALL SUBMAIT PROPOSED MX DESIGNS, WITH HSTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO
<br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5" 4-PRIOR TO THE ADDITION OF PLASTICIZER
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94IC94M OR MEASURING, MIXING, TRANSPORTING,
<br />ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED THE MAXIMLM TIME ALLOWED FROM WHEN
<br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MNUTES IF FDR ANY REASON
<br />THERE IS A DELAY IN SUCH THATA BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL
<br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY
<br />NON COMPLIANCE WITH THE ABOVE
<br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS
<br />A 3"FOR CONCRETE CAST AtAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS)
<br />B. FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER.
<br />1-12- FOR #5 AND WA ER
<br />Y FOR #6 AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />314" FOR SLABS, WALLS AND JOISTS
<br />1-1/2" FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />ASTM C476 AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF GOOD PSI AT 28 DAYS UNLESS
<br />SPECINFICALLY CITED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8"
<br />COURSE AGGREGATE, AND SHALL BE PLACED WI A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTUNED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />CELLS TO BE FILLED.
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />REINFORCING.
<br />LAP VERTICAL REBAR 6 X BAR NO. (AS BAR DIAMETERS)., U.N.O.
<br />STRUCTURAL STEEL'
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />9TH EDITION BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36IA36M Y
<br />F =36 ksi FOR ANGLES PLATES AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM
<br />ASOOIASOOM GRADE B F = O6 ksi. STRUCTURAL PIPE SMALL BE ASTM A53IA53M GRADE BTYPE E OR S F =
<br />Y Y
<br />35 ksi. TUBE AND PIPE COLUMNS SHALL BE CONCRETE-RU-ED IN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />OTHER BOLTS SHALL BE ASTM F3125/F3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS
<br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK FASTENERS
<br />FASTENER
<br />sexoAc
<br />s we
<br />.
<br />EwAN4on nolT
<br />olc (ye owl
<br />CONTACT THIS ENGINEER FOR SPACING
<br />.No
<br />STAGGORED
<br />_MA NRY oC
<br />-It No
<br />REQUIREMENTS
<br />NoWn M
<br />is ac
<br />xa PAc .
<br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURERS SPECS AND / OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1. MEMBERS ARE NAILED AND
<br />2A MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE.
<br />1 N. RONALD REAGAN BI
<br />LONGWOOD, FL32750
<br />PH: 407-774 6078
<br />FAX: 407-7744078
<br />W Ww.abdesigngroup.com
<br />AA #: 0003325
<br />W
<br />�
<br />�
<br />�
<br />ziiz
<br />a
<br />F
<br />�f
<br />4ii
<br />F
<br />SUHDIV. & LoT:
<br />A BBOTT
<br />PARK
<br />LOT #16
<br />BLK #9
<br />[I-ROJECT#
<br />04161.000-16091
<br />MODEIe
<br />4EHB
<br />"2605-HAYDEN"
<br />GARAGE SWING:
<br />RIGHT
<br />PAGE:
<br />DETAILS
<br />6 H
<br />SCALE: 1/4-'=1--0-
<br />SHEET
<br />SN1