0 <br />GABLE -END <br />ROOF WIND DESIGN PRESSURES <br />NET(GROSS) ASCE 710 <br />ZONE 1 = 23.79 PSF (33.79) <br />ZONE 2 = 39.48 PSF (49,48) <br />ZONE 3 = 67.16 PSF (77.18 <br />"A'= 4'-0' END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />WIND EXPOSURE: "C' <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT +-0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16" <br />O.S.B. OR lf2" CDX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. 5/8 COX EXT. PLYWOOD, WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND 8d RING SHANK GUN NAILS <br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE <br />Bd GUN NAILS 4" O.C. EDGEWISE 2x4 <br />BLOCKING ALL (PANEL JOINTS W/ IN 4' OF GABLE <br />END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. CIA. <br />SHANK <br />TENSILE STR. <br />SHANK <br />8d <br />RING SHANK, <br />21/2" <br />0.120" <br />170,000 <br />LNG <br />(i6-2 RINGS <br />SCREW SHANK <br />I <br />PPER NCH) <br />Sd <br />SCREW SHANK <br />2 1f2" <br />0.120" <br />PNEUMATIC <br />SCREW -NAILS <br />1. NAIL SIZE PER ASTM F1664 <br />2. INTERNATIONAL STAPE, NAIL & TOOL <br />ASSOCIATION (ISANTA) ESR-1539 <br />ExrERK3R aNE1►7HINo <br />USE 1/2" CDX OR 7f18" O.S.B. PLY WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES <br />AND SKI RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN <br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS <br />OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />8d RING SHANK GUN NAILS @ 4" O.C. <br />TOP & BOTTOM EDGES <br />Z O <br />Z J <br />Z <br />V � <br />J <br />6 <br />z . <br />YZZ <br />CD . <br />E . <br />m <br />TOP CORD BLOCKING AT 4' <br />O.C. MAX. IN FIRST 2 FRAMING <br />SPACES A7 EACH END. <br />RAFTER OR TRUSS <br />RnnF RuPAcerulNr- -� <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FR 13 <br />8d RING SHANK GUN NAILS . <br />6" O.C. IN FIELD` <br />TO BE STRUCTURAL GRADE <br />C8d RING SHANK GUN NAILS @ 12" O.C. IN <br />FIELD or 8d x 2 1/2" SCREW SHANK <br />PNEUMATIC SCREW -NAILS Q 12" 0.B�N <br />FIELD J\ <br />TYP. 314" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, 681 EDITION <br />ACI 31B-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, ACI $30-13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011. ASCE 7.10 AND AISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS, FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />OF THE WORK. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33 MAXMIUMAGGfEGATE BUT SH AU. BE314". <br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHWffERED 314'. <br />PROVIDE 04AL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS04-GROUND WHERE INDICATED ON <br />DRAWINGS. BEAMS LAPPED 6 INCHES AND SEALED WITH ADHESIVE TAPE. <br />FORM -WORK: <br />FORM -WORK, SHORING, AND BRAGNG FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347, <br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />WOOD: <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF <br />ELASTICITY !ILLS, <br />PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONSTRUCTURAL USES <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCP OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCP FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />W/ DOT SHALL BE HOT DIPPED CAM FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />CONTAINS MORE THAN %* OF HEARTWOOD. <br />EXCLUSIONS FROM THESE PLANS: MINIMUM NAILING PER FSCR 2017, 8th EDITION. SEE NAILING SCHEDULE ON PUNS. <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2X STRUCTURAL LUMBER <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALAEPENDING <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. SYp 02. <br />WELDED WIRE MESH: <br />WELDED WIRE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE <br />SUPPORTED WITH T CHAIRS SPACED 3'-O' OC, EACH WAY. <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />WOOD TRUSSES: <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS 3 E N HALLS SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.038" AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SHALL BE ASTM A815 GRADE 40 IN CONCRETE DEFORMED BARS REBAR SHALL B ASTM A815 <br />GRADE 60 IN MASONRY DEFORMED BARS FREE FROM OIL SCALE AND RUST AND PLACED IN ACCORDANCE <br />MEETING THE REQUIREMENTS OF ASTM M46, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />DESIGN LOADS: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES NATIONAL <br />ACCORDANCE WITH TN:, <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />D A D TPIlN <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND 'TPIIWTCA BCSI t" <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />20 pef TOP CHORD-rao-conartenl <br />REVIEW. <br />TYP, MIN UPS SHALL BE A9 FOLLOWS: #4 BAR - 25' /JS BAR - 36' <br />WOOD TRUSSES. <br />10 psf BTM CHORD -nor cores nl <br />#5 BAR - 30" #7 BAR - 42" <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36- X 38" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR. SEE DETAILS <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982. <br />16 PBf TOP CHORD 20 pef TOP CHORD <br />(7 psf w/ ASPHALT SHINGLES) psI wl No GVPCRE7E) <br />(1 <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING 70 MANUFACTURER'S INSTRUCTIONS. <br />10 pest BTM CHORD 5 s/BTM CHORD <br />5 p <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: 10psf <br />MINIMUM 101NCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 pef <br />WALL. <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL, <br />STAIRS LIVE LOAD 40 psf <br />WINO: DEAD LOAD SPEED =1R2017) MPH SECOND GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />S <br />(NICE EXPOSURE C, RISK CATEGORY III <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />BIT BLEFBC ATTIC <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10ps/, UNINHABITABLE ATTIC WITH LIMITED <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />STORAGE: 2OPsf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />W NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200pef, GUARD IN -FILL COMPONENTS: 60psf, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE LE GARAGES: 50psf, OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />pBf <br />MASONRY: <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: <br />"SPECIFICATION MASONRY STRUCTURES' (ACI 530/ ASCE 5fTMS 402, BUILDING CODE REQUIREMENTS FOR <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM 0-90, GRADE Prn -1500 PSI. BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CONTTRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM 0-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />ALL SHEET METAL FRAMING CONNECTORS SHOWN ON THE PLANS SHALL BE "USP STRUCTURAL <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8 <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8' TO 10'. USE ONLY MECHANICAL VIBRATION <br />WITH THE SIZE AND NUMBER OF BOLTSMAILS AS RECOMMENDED BY THE MANUFACTURER IN THE <br />TO CONSOLIDATE GROUT. <br />LATEST CATALOG. <br />FOUNDATIM SITE PREPARATION: <br />'S' <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 pL FOOTING <br />TYPE "M' ORMORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SUB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 96%OF THE <br />SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL <br />SOIL FOR TERMITE PROTECTION. <br />CELLS TO BE FILLED. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,600 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SUB. <br />CONTRACTOR SHALL SUBMT PROPOSED MX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5'.l- PRIOR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C44OR MEASURING, MIXING, TRANSPORTING, ETC. <br />CONCRETE TICKETS SHALL BE TIME-STAMPED <br />WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER I3 <br />ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON THERE IS A <br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGEtTHAN 90 MINUTES, THE CONCRETE SRALL NOT BE PLACED. IT SHALL BE THE <br />HE RESPONSIBILITY OF TTESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON <br />COMPLIANCE WITH THE ABOVE <br />REOURED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A TFOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH(FOUNDATIONS): <br />B. FOR CONCRETE EXPOSED TO EARTH ANDIOR WEATHER <br />1-1WFOR MI6 AND SMALLER <br />7 FOR 4 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3/4" FOR SLABS, WALLS AND JOISTS <br />Mir FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />STRUCTURAL STEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36, Fy = 36 ksl FOR ANGLES, PLATES, AND WSHAPES, STRUCTURAL TUBING SHALL BE ASTM A-500, GRADE B. <br />Fy = 46 ksl. STRUCTURAL PIPE SHALL BE ASTW53, GRADE B, TYPE E OR S, Fy - 35 W. TUBE AND PIPE <br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM A326-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APPLI.-F'�- <br />TYPE <br />BPACIND <br />REIAARKS <br />APPLICATKNd <br />SITE <br />TYPE <br />SPACING <br />PE- <br />1-FUR TO <br />HIEDCgI <br />DIAAGEDOON BUCK <br />-. <br />TAPD0NMA40xiY <br />I - EMBED. 4-END DIET., <br />MA80191Yl CONC. <br />S LONG.TO <br />9, bL <br />MASIXAY/OONC. <br />M.WASHFA <br />FASTENER <br />8.� <br />1-EDGEBGD. <br />AL. EXi. OOPS <br />ENED 0011 <br />B"dG <br />WINDOW/DOCWFASTENEO <br />GARAGE DOOR BUCK <br />tTY DwE <br />148KW BOLT <br />24'Q'C <br />A- EMEED.,VENDDIET„ <br />iN Pf, BEE NOTES <br />LONG. <br />STAGGEREDMA80NRY2VHC. <br />TO MAEDNRYIOONC. <br />WASHER <br />7EDGE DBIT. <br />WBm woK <br />ENED toe <br />rest <br />wwoowiDoow FASTENED <br />METAL STRAP To <br />CONTACT THIS ENGINEER FOR SPACING <br />PT, SEE NOTES <br />LGNG. <br />STAGGERED <br />INTO MASONmrcau0. <br />MAsoNRYlcoNc. <br />REQUIREMENTS <br />SEE N01E8SHER <br />A. <br />"TAPWN <br />FASTNER <br />1PdG <br />11R' EMBED. FEtYl'A'EMBED <br />DIET.. I INS EDGE DIRT. <br />-To CONL.54B <br />A'EtOPT, <br />w, Z-B0. BOLT 240/C .7EDGED6T. <br />Nxo WINDOW BUCK 8.138'PAFA219' B'O'C 1' END. DIB1. I INS <br />IT <br />PT TO STEEL COL., SEE 1W IyAyRER STAGGERED EDGED- <br />NorEe <br />NOW <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURERS SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />e. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NAILED AND <br />2X MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407.7748078 <br />FAX 407-774407E <br />www.a Wlesign group.Qom <br />AA #: 0003325 <br />W <br />N <br />Y <br />r <br />Q <br />NJ <br />aysElo ;#7 <br />LOT <br />ABBOTTPARK <br />LOT BLK 10 <br />PROJECT* <br />04181.000-07102 <br />MODEL' <br />4EAB <br />"1672-ARIA" <br />GARAGE 8Wn9G: <br />RIGHT <br />PAGE: <br />DETAILS <br />60 MPH EXP. <br />DA IM 11/25/19 <br />DCALE: 1/4"=1'-0" <br />ll Hm MT <br />S-N 1 <br />