HP ROOF
<br />ROOF WIND DESIGN
<br />PRESSURES
<br />NET (GROSS) ASCE 7-16
<br />ZONE 1 = 58.50 PSF (68.50)
<br />ZONE 3 = 67.10 PSF (77.10)
<br />ZONE 2e = 67.10 PSF (77.10)
<br />ZONE 3e = 77.50 PSF (87.50)
<br />ZONE 2n = 77.50 PSF (87.50)
<br />ZONE 3r = 91.60 PSF (101,60)
<br />ZONE 2r = 77.50 PSF (87.50)
<br />"A"= 4'-0" END ZONE DISTANCE
<br />BASIC WIND SPEED: 160 MPH
<br />EXPOSURE CATEGORY: "C"
<br />RISK CATAGORY: II
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT: +1- 0.18
<br />ROOF DOPHRAOM
<br />FOR ASPHALT SHINGLE ROOF USE MIN 19/37' STRUCTURAL SHEATHING
<br />EXP 1 (40/20), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN.
<br />19/32' STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD
<br />AND EDGE SPACING) SEE DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN
<br />NAILS 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF
<br />GABLE END.
<br />ROOF/ WALL/ FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />SIZE
<br />HEAD
<br />LENGTH
<br />DIA
<br />TENSILE STR.
<br />SHANK
<br />ASTM
<br />10d
<br />RINGSHANK,
<br />212"
<br />0131
<br />F1667
<br />SCREW SHANK
<br />170.000
<br />RING
<br />(16-20 RINGS
<br />RSRS-03
<br />Bd
<br />RINGSHANK,
<br />2 3/6'
<br />0.113
<br />Fi667
<br />SCREW SHANK
<br />PER INCH)
<br />INCH)
<br />RSRS-01
<br />8d
<br />RING SHANK,
<br />PNEUMATIC
<br />23/9'
<br />0,113
<br />F1667
<br />SCREW -NAILS
<br />RSRS-01
<br />DQAF ORTRUSS
<br />EXTERIOR SHEATHING
<br />USE 1f2' COX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4"
<br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP 8
<br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 6' O.C. AT
<br />INTERMEDIATE SUPPORTS OR 7/16' ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL.
<br />I� BUILUINO LENG I
<br />ROOF SHEATHING LAYOUT SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />N= GABLES -DROP GABLE END 8 (1) ADD'L DROPPED
<br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING
<br />16'O.C. IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP
<br />BLOCKING a 16" O.C. FIRST 4 BAYS W/(2)12d NAILS EA.
<br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/
<br />BLOCKING PER NAILING SCHEDULE
<br />���ATT�BP�
<br />ZONE 1: tOd NAILS 0 4" O.C. ON EDGE AND 6" O.C. IN FIELD
<br />ZONE 2e, 2n, 2, 10d NAILS 0 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />ZONE 3,3e, 3r 10d NAILS 0 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />NM', ROOF SHEATHING THICKNESS WAS CALCULATED
<br />AND ADHERES TO ASCE 7.16
<br />04 RING SHANK GUN NAILS Q 4" Q C.
<br />TOP A BOTTOM EDGES
<br />4A
<br />a�
<br />ly
<br />z�
<br />�O
<br />$ 0 .
<br />TYP. EXT. SHEATHING ATTACHMENT
<br />za
<br />�o
<br />B
<br />-___ legal
<br />I
<br />I
<br />1. RING SHANK GUN NAILS
<br />SEE "ROOF SHEATHING ATTACHMENT'
<br />TABLE FOR FIELD SPACING
<br />C#6 2" DECK SCREWS 0 6'-0" O.C. MAX 0
<br />EDGES 8 12' O.C. MAX IN FIELD. UNTHREADED
<br />SHANK TO EXTEND BEYOND THICKNESS OF
<br />SUB -FLOOR SHEATHING
<br />TYP. 3/4" TSG SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GMERAL NOTE&
<br />ALL AGGREGATE USED IN CONCRETE SHAD. CONFORM TO ASTM C3=31M. MAXIMUM AGGREGATE SIZE SHALL BE W.
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER
<br />NON -BEARING WOOD WALLS TOP PLATES 8 STUDS CAN BE SPF.
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES. DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 7th EDITION
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3/1'.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />ACI 310-14, BUILDING CODE REQUIREMENTS
<br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF
<br />FOR STRUCTURAL CONCRETE, TMS 4021602-16 AISI SPECIFICATION FOR THE DESIGN OF
<br />PROVIDE BMIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS -ON -GROUND WHERE INDICATED ON
<br />R BARRIER MEMBRANE
<br />ELASTICITY - 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS
<br />DRAWINGS. SEAMS LAPPED 61NCHET AND SEALED TH ADHESIVE
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />FORM'WOWG
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />EXCUMOM FROM THINE PLANE:
<br />MINIMUM NAILING PER FBCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />OF THE WORK.
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING
<br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYP #2.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />WELM VRE MM:
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS,
<br />WELDED WIRE MESH, SHALL BE ASTM A10641A1064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE
<br />WOO TR S�
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FORSLABS SHALL
<br />BE SUPPORTED WITH 2'CHAIRS SPACED 3'-0' OC, EACH WAY.
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE "NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS" BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA, SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />REINFOWNG STEEL:
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />REBAR SHALL BE ASTM A61 M615M GRADE 40 IN CONCRETE DEFORMED BARS REBAR SHALL BE ASTM A615
<br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED.
<br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE
<br />INSIN LOAM:
<br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />WOOD TRUSS CONSTRUCTION:, AND METAL LATEST EDITION'
<br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 PST
<br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEERS
<br />ATIONS FOR
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />20 pef TOP CHORD+Ion-com-nt
<br />REVIEW
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - %"
<br />WOOD TRUSSES.
<br />10 of BTM CHORD --oncurrent
<br />P
<br />#5 BAR - 30" #7 BAR - 47'
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />PROVIDE 36' x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />DEAD LOAD DEAD LOAD
<br />FOR ADDITIONAL INFORMATION.
<br />INTERSECTIONS OF HIGHER OR LOUVER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88: 1990,
<br />16 pot TOP CHORD 20 PST TOP CHORD
<br />(7 PSI W/ ASPHALT SHINGLES) (10 psf WNp GYPCRETE)
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />10 Psf BTM CHORD 5 psf BTM CHORD
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />DEAD LOAD TO RESIST WIND UPLIFT: IOpSf
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />BALCONY LIVE LOAD 60 psf
<br />WALL.
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />STAIRS LIVE LOAD 40 psf
<br />WIND: DEAD LOAD SPEED MPH 3- SECOND GUST
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS, DOWEL
<br />ROOF 8 FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />(ASCE (FBC 020) C, RISK CATEGORY II)
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DETERMINATIONS, FEASIBILITY 8 ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />ATTIC STSUREORAGE:
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE:
<br />BIT WITHOUTUNINHABITABLE ATTIC WITH LIMITED
<br />LAYOUT, SPANS 8 ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />WITH
<br />STORAGE: 2Dpsf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR)
<br />NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THERE PLANS SHALL NOTIFIED TO THE
<br />AND DECKS: 40pef, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER
<br />WI
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />H
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS:
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />40ps(
<br />MASONRY.-
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />LICENSED PROFESSIONAL ENGINEER.
<br />SHOP DF AWING RMEW:
<br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />THE MASONRY STANDARDS JOINT COMMITTEE.
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT.
<br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE Tm = 2000 PSI. BLOCK SHALL BE PLACED USING
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />Of REPRODUCIBLE SEPIAS STRUCTURAL DRAWINGS (CON! -TRACT DOCUMENTS) ARE PROHIBITED
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER.
<br />IT ALL INSTANCES, THE CONTRACT
<br />ASTM C478, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />L
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318"
<br />WRITING BY THE ARCHITECT.
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />FOUW ATIOW SITE PREPARATION
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING
<br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />EXCAVATIONS AND SLAB SUB-GRADEYSHALL, COMPACTED A DENSITY OF AT LEAST THE
<br />SHALL BE THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />A
<br />ACCORDANCE 7. THE
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM 0.1557. TREAT ALL
<br />MAXIMUM D
<br />CELLS TO BE FILLED.
<br />BE
<br />SOIL FOR TERMITE PROTECTION.
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT CEO -TECHNICAL ENGINEER TO VERIFY
<br />REINFORCING.
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS, LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />LAP VERTICAL REBAR 6 X BAR NO. (48.BAR DIAMETERS)., U.N.O.
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />RAI"
<br />STFOXTUTHE
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY MATH THE
<br />SCONCFWMPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS'
<br />BTH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36/A36M, Fy = 36 W FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM
<br />A500/A500M GRADE B F - 46 Mi. STRUCTURAL PIPE SHALL BE ASTM A53/A53M GRADE B TYPE E ORS F =
<br />y Y
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />35ksi. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO
<br />OTHER BOLTS SHALL BOLTSWITHWASHERSUNDER THE TURNED ELEMENT. BOLTS
<br />CONCRETE PLACEMENT. CONCREIESLUMP SHALL NOT EXCEED 5'4- PRIORTO THEADDITIONOF PLASTICIZER
<br />IN ACCSTM RDANF3125EWIT3125M
<br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 310 AND ASTM C94IC94M OR MEASURING, MXING, TRANSPORTING.
<br />ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. JOLTS ARE TO BE STEEL.
<br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES, IF FOR ANY REASON
<br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL
<br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY
<br />NON COMPLIANCE WITH THE ABOVE,
<br />REGUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS:
<br />A 7 FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS):
<br />B. FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER
<br />1.1YC FOR 06 AND SMALLER
<br />2' MI FOR #6 D LARGER
<br />C. FOR CONCRETE NOT EMBED TO WEATHER
<br />3/4' FOR SLABS, WALLS AND JOISTS
<br />1-112' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK FASTENERS
<br />FASTENER
<br />APPLIfATION
<br />eliE
<br />TYPE
<br />SPA..
<br />REMARKS
<br />APPL-ON
<br />SIZE
<br />TYPE
<br />I SPAONG
<br />REMARKS
<br />1. PTRIRRINGTO
<br />CASE-- COIL
<br />GARAGE ODOR SLICK
<br />TAPCON MASONRY
<br />11IY'EMBED., I END
<br />ASONRYICIXJC.
<br />11IY IGNG.
<br />0 dC
<br />TO M4SONSY/WIC.
<br />FASTENER
<br />0„_
<br />11Y1"EDGEDIST.
<br />9GD�.E%T.DOORS
<br />CASE INRDENED COL
<br />g'OIC
<br />WNDOWIDOORIFASTENED
<br />GARAGE DDOR SUCK
<br />3re"dA. OR
<br />EXPPN910N e0LT
<br />te'-(3� )
<br />a^ EMBED. 4" END DIST.,
<br />1 a ,SEE NDTE6
<br />t1fP LONG.
<br />STAGGERED
<br />INTO MABONRv/WIC.
<br />TO M490NRYICONC.
<br />-
<br />14'O/C (111'DIP)
<br />3"EODE GIST.
<br />WINDOW-
<br />CASE HARDENED WIL
<br />rac
<br />WNDOWIDOORI FASTENED
<br />ET S_TG
<br />CONTACT THIS ENGINEER FOR SPACING
<br />ix PT SEENOTE.
<br />N 11mwNG.
<br />STAGGERED
<br />INTD 50-10D.
<br />MASONRYIWND
<br />REQUIREMENTS
<br />EAT. SWINIG DDOR
<br />(1).-A
<br />°TAfCON'
<br />1A 0�
<br />I-E.., S°ENO
<br />NlON43E4RINGWWD
<br />tYI° E%PANSION 4"EMBED. AMEND
<br />2<dC
<br />SUCK 2e PT, SEE NOTES
<br />NO WASHER
<br />IASTN.
<br />qST., I IITE.-IT.
<br />WALL TO CONC.eWe
<br />WI WASHER DIST., 3" 03-ST
<br />2x PTWINDOW BUCI( 0.130°PAf x21I0' e"OIC 4"ENO. DIST.,111Y
<br />AT TO STEEL COL.. SEE WI WASl1ER STAGGERED EDGEgST.
<br />E0
<br />1. STAP SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILTI X.ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NCA OR THE SPACING DETAILED ABOVE
<br />B. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. lx MEMBERS ARE NAILED AND
<br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE.
<br />1441 N. RONALD REAGAN BLVD.
<br />LONGWOOD, FL32750
<br />PH: 407-774-6078
<br />FAX: 407-7744078
<br />www.abdosigngroup.com
<br />AA #: 0003325
<br />h
<br />1r11
<br />11
<br />H
<br />�'
<br />Q
<br />QQ
<br />Q
<br />�B
<br />dl
<br />1�jQQll
<br />eum & LOT
<br />ABBOTT PARK
<br />LOT #14
<br />BLK #9
<br />PROJWT*
<br />04181.000-14091
<br />MODEL
<br />E401
<br />"2828-ENSLEY"
<br />GARAGE 8WMG:
<br />RIGHT
<br />PAGE:
<br />DETAILS
<br />160 MPH EXP. C
<br />jI�) 2
<br />:Sl:n : 1pf =.L -U
<br />SHEET
<br />S N1