Laserfiche WebLink
A xF HIPROOFF <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-16 <br />ZONE 1 • 52.70 PSF (62.70) <br />ZONE 3 = 60.50 PSF (70.50) <br />ZONE 2e • 60.50 PSF (70.50) <br />ZONE 3e = 69.80 PSF (79.80) <br />ZONE 2"= 69.80 PSF (79.80) <br />ZONE 3r = 83.80 PSF (93.80) <br />ZONE 2' • 69.80 PSF (79.80) <br />"A"• 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />EXPOSURE CATEGORY: "C" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT: +I- 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/32" STRUCTURAL SHEATHING <br />EXP 1 (4020), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN. <br />19137' STRUCTURAL SHEATHING EXP 1 (40/20).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL <br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN <br />NAILS Q Al" O.C. EDGEWISE 2K4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF <br />GABLE END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />SIZE <br />HEAD <br />LENGTH <br />DIA, <br />TENSILE STR. <br />SHANK <br />ASTM <br />10d <br />RING SHANK, <br />2lr7 <br />0.131 <br />F17 <br />SCREW SHANK <br />170,000 <br />RING <br />(16-20 RINGS <br />RS66RS-03 <br />Bd <br />RING SHANK, <br />2 318' <br />0.113 <br />F1667 <br />SCREW SHANK <br />PER INCH) <br />RSRS-01 <br />8d <br />RING SHANK, <br />PNEUMATIC <br />23/8" <br />0.113 <br />F1667 <br />SCREW -NAILS <br />I <br />I <br />I <br />RSRS-01 <br />I <br />EXTERIOR SHEATHING <br />USE 1/2" COX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4" <br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND Bd RING SHANK GUN NAILS AT 6" O.C. AT <br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANI SPECS.) SEE DETAIL <br />ROOF SHEATHING ATTACHEMENT SPACING <br />ZONE 1: 1Od NAILS 0 4" O.C. ON EDGE AND 6" O.C. IN FIELD <br />ZONE 2e, 21, 21 JOd NAILS 04" O.C. ON EDGE AND 4" O.C. IN FIELD <br />ZONE 3,3e, 3r: 10d NAILS ® 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />8d RING SHANK GUN NNLS G 4D.C. <br />P8 BOTTOM EWES <br />o' <br />ho <br />8e <br />So <br />rcrr I erc urc 1 rcuaa _ <br />ROOF SHEATHING <br />■EMME <br />����11 11 <br />EME <br />ulillll <br />11 <br />U BUILDING LENGTH <br />r ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />NOTE: GABLES -DROP GABLE END & (1) ADUL DROPPED <br />TRUSS 2.4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING 0 <br />16'0.C. IF NO DROPPED GABLE END, ATTACH Z14 #2 SYP <br />BLOCKING Q 16' O.C. FIRST 4 BAYS W/ (2)12d NAILS EA. <br />END, ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />- 1. RING SHANK GUN NAILS <br />SEE"ROOF SHEATHING ATTACHMENT" <br />TABLE FOR FIELD SPACING <br />C#8 2" DECK SCREWS ® 6" A" O.C. MAX 0 <br />EDGES & 12' O.C. MM IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING ` <br />LI TYP 3/4' T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />TYP. EXT. SHEATHING ATTACHMENT <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33C33M. MAXIMMJ AGGREGATE SIZE SHALL BE 311 <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />WOOD: <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULTNON-BEARING <br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER <br />WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 7th EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 314" . <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />PROVIDE 64All CONTINUOUS POLYETHYLENE VAPOR BANNER MEMBRANE UNDER ALL SLABS-0N GROUND WHERE INDICATED ON <br />6. <br />VAPLED <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb= 1100 PSI ANDA MODULUS OF <br />FOR STRUCTURAL CONCRETE, TMS 402/602-16 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND ABC SPECIFICATIONS <br />PROVIDE <br />SEAMS UPPED B INCHES ANDSE NTH ADHESIVE VETAPE. <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORM -WORK: <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAW NGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WTH 2K STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY 70 DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH: <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />WELDED WIRE MESH, SHALL BE ASTM A1064/A1064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />WOOD TRUSSES: <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />BE SUPPORTED WITH 2°CHAIRS SPACED 3'-0' OC, EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE *NATIONAL DESIGN SPECIFICATIONS FOR <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' THE NFPA. TRUSS DESIGNS SHALL SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR ASUBCONTRACTORREINFORCING <br />CO C R AND VERIFY ALL DIMENSIONS PRIOR <br />STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF AND MANUFACTURED FROM STEEL <br />CRALL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SHALL BE ASTM GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />E A, A A <br />MEETING THE REQUIREMENTS OF ASTM A446/A448M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED, <br />DEFORMED <br />GRADE BO IN MASONRY DEFORMED BARS FREEFROM OIL SCALE, AND RUST A PLACED <br />LE, S AND CEDIN ACCORDANCE <br />DESIGN LOADS: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "SCSI LATEST EDITION" <br />ROOF: LIVE LOAD FLOOR' LIVE LOAD 40 psf <br />AND VERTICAL BARS SHALL LAP 6 K BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL-PLATE-CONNECTED <br />20 psf TOP CHORD -non-concurrent <br />REVIEW. <br />TYP. MIN LAPS $HALL BE AS FOLLOWS: 04 BAR - 25" #6 BAR - 36' <br />WOOD TRUSSES. <br />10 psf BTM CHORD-no-oncurrent <br />05 BAR - 30" #7 BAR - 42" <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36' K 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88: 1990. <br />15 WTOP CHORD 20 psf TOP CHORD <br />(7 psf w/ ASPHALT SHINGLES) (10 Psfw/ No GYPCRETE) <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />10 PSI BTM CHORD 5 psf BTM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: 10psf <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 pef <br />WALL. <br />TRUSSES/GfRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 psf <br />WIND: DEAD LOAD SPEED MPH 3- SECOND GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />(ASCE (FBC 020) EXPOSURE C, RISK CATEGORY II) <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />ATTIC <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10IT UNINHABITABLE ATTIC WITH LIMITED <br />BIT <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />STORAGE: 20pst, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40pst, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER, <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS'. 30psf, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40psf <br />MASONRY: <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />OF THE CONTRACT DOCUMENTS ONLY IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED By <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />Mft ASONRY <br />PROVIDED BY THE TRUSS ENGINEER. <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-9G GRADE 2000 PSI, BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS A <br />STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IWWALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />IT <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. ALL INSTANCES, THE CONTRACT <br />ASTM C-478 AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 300 PSI AT B DAYS, 5 <br />0 P 2 D V UM S <br />L <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8" <br />3 <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATION/ SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SU&GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE <br />SHALL BE 318" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM 0-1557, TREAT ALL <br />SOIL FOR TERMITE PROTECTION. <br />CELLS TO BE FILLED. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS ANO/OR VERTICAL <br />REINFORCING. <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL STRUCTURAL STEEL: <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR VVEIGHT FOR FOOTINGS, AND SLAB-0N-GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MX PRIORTO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5' -f-PRIOR TO THE ADDITION OF PLASTICIZER. <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94C94M OR MEASURING, HYING, TRANSPORTING, <br />ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WITH THE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A Y FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS): <br />B. FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER <br />1-111' FOR #6 AND SMALLER <br />T FOR #6 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3/4' FOR SLABS, WALLS AND JOISTS <br />1.1R" FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36/A36M FY = 3e ksi FOR ANGLES PLATES AND WSTUBING HAPES. STRUCTURAL TU IN SHAL <br />L BE ASTM <br />A500/A500M GRADE B F = 46 hsiSTRUCTURAL PIPE SHALL BE ASTM A53/A53M GRADE B TYPE EORS F - <br />35 ksi. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP, <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WTH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM F3125/F3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APPLIU <br />I. <br />TYPE <br />SPACING <br />A3vL1UTroN <br />912E <br />I - <br />I ACING <br />REMMKS <br />-TOUSE <br />MASONRY/CONC. <br />HARDEN 00L <br />IIY LONG. <br />6OIL <br />A GEOOORBUCK <br />TTo MASONRYANC. <br />1M'DIA <br />NO WASHER <br />T APCON MASJNRV <br />FASTENER <br />6O� <br />-EMBEO.,TENO IT, <br />2"EWE T. <br />S EXTD00R5 <br />CASEHARDENEOCOIL <br />S"OIC <br />WINTOWIWORIFAeTW <br />BUCK <br />QMAGETO <br />ems- OR <br />OIA <br />E%PANSION BOLT <br />I6"O/C(3 <br />EMBEO.,K"EN0019i., <br />1-T, <br />x EE NOTE 6 <br />NNL t 11Y' LONG. <br />BTAOOERED <br />TO MASONRT/C�NC. <br />NRY <br />TO MgeONRVANC. <br />w/WASHER <br />• NC (1rY OAI <br />A) <br />3' EDGE GIST. <br />W1NDow SUOK <br />CASE HAROENEGODL <br />s•o/c <br />WNODWIDOOR/FASTENED <br />METAL 9TRAPTO <br />CONTACT THIS ENGINEER FOR SPACING <br />x PT, SEE NOTE6 <br />NNLI VY LONG. <br />STA <br />INTOMA60NRVICONC. <br />MASONRY /CONC <br />REQUIREMENTS <br />T. $YA6Ai OOOH <br />BUCK h PT.SEENOTE6 <br />(31 En6'pA <br />I NO WASHER <br />TAPCON <br />FASTNER <br />IB'OC <br />I VY EMBED, BEND. <br />DST I /l'EDGE qST. <br />NON.BFARINGYg00 <br />E%PM1810N <br />BOLT Zi O� <br />PTIWINOOW &ICK O.t38°PAF x219" S"QC <"ENO. OIBT. IVY <br />TOSNEELCOL., SEE Wl geHER STAGGERED EWEOI6T. <br />OTEfi <br />111SSTTAAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />8. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WTH A WOOD DOOR FRAME. iK MEMBERS ARE NAILED AND <br />2. MEMBERS ARE SECURED W TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL32750 <br />PH: 407-774-6078 <br />FAX: 407-774.4078 <br />www.abdesigngroup.com <br />AA #: 0003326 J <br />b <br />04 <br />��FpL <br />Lp�S <br />4 <br />SVHDiv. de LOT: <br />ABBOTT PARK <br />LOT #13 <br />BLK. #9 <br />PROJECT# <br />04181.000-13091 <br />MODEL/ <br />4EBB <br />"1828-CALI" <br />OARAOE 9MINO: <br />LEFT <br />PACE: <br />DETAILS <br />160 PH M C <br />my l <br />DATE: 6/16/21 <br />SCALE: 1/4"=1r-0r' <br />SFIEET <br />SN1 <br />