Ab <br />IPP ROOF <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-16 <br />ZONE 1 = 53.00 PSF (63.00) <br />ZONE 3 = 60.90 PSF (70.90) <br />ZONE 2e = 60.90 PSF (70.90) <br />ZONE 3e = 70.40 PSF (80.40) <br />ZONE 2n - 70.40 PSF (80.40) <br />ZONE 3r = 83.80 PSF (93.80) <br />ZONE 2r - 70.40 PSF (80.40) <br />"A"= 4'-0" END ZONE DISTANCE <br />BASIC 1MND SPEED: 160 MPH <br />EXPOSURE CATEGORY: "C" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT: +1- 0.18 <br />FOR ASS PHALLTT SHINGLE ROOF, USE MIN 19132" STRUCTURAL SHEATHING <br />EXP 1 (40/20). FOR CEMENTITIOUS TILE AND METAL ROOFING USE MIN. <br />19/37' STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN <br />NAILS 0 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF <br />GABLE END. <br />ROOF/ WALU FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />SIZE <br />HEAD <br />TENSILE STIR. <br />SHANK <br />ASTM <br />lod <br />RING SHANK, <br />1667 <br />S HANK <br />170 000 <br />RING <br />116-20 RINGS <br />RSRS-03 <br />8d <br />RING SHANK, <br />P1667 <br />SCREW SHANK <br />q3/6'0� <br />PER INCH) <br />RSRS-01 <br />Bd <br />RING SHANK, <br />PNEUMATIC <br />F1867 <br />SCREW -NAILS <br />RSRS-01 <br />KAF I tK UK I KUSS <br />ROOF SHEATHING <br />EXTERIOR SHEATHING <br />USE 12" CDX OR 7/16' O.S.B. PLY WITH 8d RING SHANK GUN NAILS ATV' <br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP 8 <br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT G' O.C. AT <br />INTERMEDIATE SUPPORTS OR 7116' ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL <br />BUILDING LENGTH U <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />ZONE 1, tGd NAILS @ 4" O.C. ON EDGE AND 6' O.C. IN FIELD <br />ZONE 2e, 2n, 2r 10d NAILS 0 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />ZONE 3,3e, 3, 10d NAILS 0 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />PROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />So RING SHANK GUN NAI18 G 4"OC. <br />TOP S BOTTOM EDGES <br />� <br />yg <br />........... <br />Z <br />z 9 <br />= y <br />0 <br />�ti <br />Z w <br />LL <br />2 Z <br />w G <br />to V <br />3 <br />Z O <br />$ <br />to <br />TYP. EXT, SHEATHING ATTACHMENT <br />�D <br />�Y <br />8 <br />mmmmklhml <br />mmmmumill 11 <br />I <br />I <br />MM GABLES -DROP GABLE END & (1) ADD'L DROPPED <br />TRUSS 2.4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING 0 <br />16'0.C. IF NO DROPPED GABLE END, ATTACH 2X4 #2 SYP <br />BLOCKING 0 16' O.C. FIRST 4 BAYS W/ (2)12d NAILS EA. <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />- 1. RING SHANK GUN NAILS <br />SEE "ROOF SHEATHING ATTACHMENT' <br />TABLE FOR FIELD SPACING ; <br />CA8 7' DECK SCREWS ® 6'4" O.C. MAX 0 <br />EQGES 8 17' O.C. MM IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING <br />I YP. 314" T&G SUB -FLOOR UECKING GLUED TO ALL EXPOSED MEMBERS <br />(iENEML NOTES: <br />ALLAGGREGATE USED N CONCRETE SHALL CONFORMTO ASTM C3VCXW. MAXIMUM AGGREGATE SIZE SHALL BE 3/P. <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION MATH JOB SPECIFICATIONS AND <br />WO�" <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />pROVIQE 6%NR ENTRNNED CONCRETE EXPOSED TO EARTH OR YiFATHER <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 7th EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BECHAMFl7tE0314'. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-14' BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF <br />FOR STRUCTURAL CONCRETE, TMS 4021602-16 AISI SPECIFICATION FOR THE DESIGN OF <br />PROMDE 64AIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS -ON -GROUND WHERE INDICATED ON <br />11. CO BARRIERMEMBRANE <br />ELASTICITY = 1,400,000 PSI, ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS <br />DRAWINGS. LAPPED 61NCHET AND SEALED WITH <br />PRESSURE TREATED, PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />SHALL BE RATED TO RETENTION LEVELS OF 0,25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORNFW10ft <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORMWORK. <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS, FOLLOW WRITTEN DIMENSIONS ONLY, ANY DISCREPANCIES SHALL BE BROUGHT <br />p CLA)SK NS RM T `= PLAN$, <br />MINIMUM NAILING PER FBCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL. DEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP 12. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WEI I'1RA WIRE <br />AT BEARING LOCATIONS WTHOUT V/OODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS ORTIE-DOWNS. <br />WELDED WIRE MESH, SHALL BE ASTM A10641A1064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE <br />W= TRUISM <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />' <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR <br />TE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION Q <br />H <br />BE SUPPORTED WITH 2' CHAIRS SPACED 3'-0' OC EACH WAY. <br />SBADE LUMBER AND ITS FASTENINGS" THE NFPA. TRUSS DESIGNS SHALL SIGNED AND <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />SEALEDEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAW NOS, <br />00 NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL" <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.038" AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SHALL BE ASTM A61SA615M GRADE 40 IN CONCRETE DEFORMED BA REBAR SHALL BE ASTM A615 <br />�• <br />GRADE 80 IN MASONRY DEFORMED BARS FREE FROM OIL SCALE AND RUST AND PLACED IN ACCORDANCE <br />MEETING THE REQUIREMENTS OF ASTM A446lA446M, GRADE A. AND SHALL BE HOT -DIPPED GALVANIZED. <br />DESIGN L"QADB; <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPIA4, "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION, HORIZONTAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "BCSI LATEST EDITION" <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO, UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />20 pef TOP CHORD-nan-concurrent <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 6' BAR - 3 <br />WOOD TRUSSES. <br />10 psf BTM CHORD H1Gn-ConOument <br />#5 BAR . 30' #7 BAR - 42" <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36' X 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION, <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88: 1990. <br />18 pef TOP CHORD 20 psf TOP CHORD <br />(7 psf w/ ASPHALT SHINGLES) (40 psf w/ No GYPCRETE) <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />10 psf BTM CHORD 5 psf BTM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: 1 Opsf <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 psf <br />WALL. <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 psf <br />WIND: DEAD LOAD SPEED MPH 3-SECOND GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />(ASCE 020) EXPOSURE C, RISK CATEGORY IO <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />BIT BLE(FBC ATTIC <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: tOpsf, UNINHABITABLE ATTIC WITH LIMITED <br />LAYOUT, SPANS &ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, SALCONIES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40PO, GUARDS AND HANDRAILS: 200pef, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40pSf, SLEEPING ROOMS: 30psf, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40pcf <br />M <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />COMPLIANCE V•ATH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL BLOCK WALLS SHALL TWO -DELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE Tm = 2000 PSI. BLOCK SHALL BE PLACED USING <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWINGS SUBMITTED WTHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED, LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACICONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WTH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTMNG <br />AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS,UNLESS <br />DOCUMENTS LL GOVERN OVER THE SHOP ORAWNGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />WILL <br />IC-478 <br />SPEC NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3M' <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED WA SLUMP OF 8" TO 10'. USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUN MINIM SITE PREPARATION' <br />FOOTINGS WERE DESIGNED FORAN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE <br />SHALL BE 318" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL <br />CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />REINFORCING. <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />STRURa" STEEL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB <br />CONTRACTOR $HALL SUBMIT PROPOSED PAX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5"4- PRIOR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI W AND ASTM C94IC94M OR MEASURING, MIXING, TRANSPORTING, <br />ETC. CONCRETE TICKETS SHALL BE TIMESTAMPEO WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN <br />WATER IS ADDED TO THE MIX UNTIL IT 16 DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MNLTTES. IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MNUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLANCE MATH THE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A 3' FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS): <br />B. FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER: <br />1-1/2'FORA5ANDSMALLER <br />2'FOR 06 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />314' FOR SLABS, WALLS AND JOISTS <br />1-1Q' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />THE. MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36IA36M FY = 36 ku FOR ANGLES PLATES AND WSRAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A500/ASOOM GRADE B F = 46 ksi. STRUCTURAL PIPE SHALL BE ASTM A53/A53M GRADE B TYPE E OR S F = <br />Y Y <br />35 ksi. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM F3125IF3125M BOLTS W TH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK FASTENERS <br />FASTENER <br />A.L-ON <br />SIZE <br />TYPE <br />RA <br />REMARKS <br />APPLICATION <br />S. <br />TYPE <br />qN[i <br />RE_. <br />.2PTFURRING tO <br />RYIbJNC. <br />HA)xIENEDCgL <br />?LONG. <br />OARAGEDWRSUIX <br />TO MABONRYIWNO <br />tM'p0. <br />ND WA6HER <br />T NMA9DAY <br />STEM1ER <br />S" <br />tl?ENBEO., J"ENO DST.. <br />rr EDGE DST. <br />SGD,AL.EXT.DOOR9 <br />CASEINROENEDWIL <br />9'OX; <br />NODWIODON FASTENED <br />GARAGE-BLCx <br />3R'mAOR <br />DA <br />EXPMISIONBOLT <br />IT OIC TB'e'DA) <br />1•EMBED., 1-EN)DST, <br />R PTSEENOTE6 <br />NNL11-ONG. <br />STAGGERED <br />INTO NA90NRY/WNC <br />TO MASOMYINNC <br />xY WASHER <br />2d' OIC IVY DA) <br />3" EDGE OIST <br />wnNDDWBUCK <br />RDENED COIL <br />a°aG <br />-0-000RIFASTENED <br />METAL $TRAP To <br />CONTACT THIS ENGINEER FOR SPACING <br />I. PT, SEE NOTES <br />NNL 11IY LONG. <br />STAGGERED <br />INTOM NRYr Nc. <br />MASONRY I CONC <br />REQUIREMENTS <br />EXT SWING DOOR <br />LICKS PT, SEE NOTES <br />O)VI6"DA: <br />NO -ER <br />'TAPCON' <br />FASiNER <br />IS- <br />I", EMBED, 6"EIA. <br />GIST., 1 fn` EDGE DST. <br />NONSEARING WOOD <br />WALLTOCONC. SUB <br />1R` -ANSIMSEO. 4'END <br />WI WASHER B0.t 2E QC SAT., $"EDGE DST. <br />roa NQOW BUCIt 3S°PPFr 21T YO,C 1'fND qST., <br />PT DEL COL"SEE WI WASHER STAGGERED EDGE DST. <br />TEB <br />1>� <br />1. STAPLES SHALL NOT 8E USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL SEAS PER MANUFACTURER'S SPECS AND/OR NOA <br />3, ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILT[ X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6, WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1X MEMBERS ARE NAILED AND <br />2K MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />LONG WOOD, FL 32750 <br />PH: 407-774.6078 <br />FAX: 407-7744078 <br />www.abdosigngroup.com <br />AA N: 0003326 <br />IF. <br />M <br />h <br />E <br />9L73DIV de I407: <br />ABBOTT PARK <br />LOT #27 <br />BLK #7 <br />PROJECT <br />04181.00 -27071 <br />MODEIA <br />4EAB <br />"1672-ARIA" <br />GARAGE BW MG: <br />RIGHT <br />PAGE: <br />DETAILS <br />160 MPH EXP. C <br />