<br />GABLE ENO
<br />ROOF WIND DESIGN PRESSURES
<br />NET (GROSS) ASCE 7-16
<br />ZONE 1 = 52.70 PSF (82.70)
<br />ZONE 3 = 60.50 PSF (70.50)
<br />ZONE 2e = 60.50 PSF (70.50)
<br />ZONE 3e = 69.80 PSF (79.80)
<br />ZONE 2n = 69.80 PSF (79.80)
<br />ZONE 3r = 83.80 PSF (93.80)
<br />ZONE 2r = 69.80 PSF (79.80)
<br />"A"= 4'-0" END ZONE DISTANCE
<br />BASIC WIND SPEED: 160 MPH
<br />EXPOSURE CATEGORY: "C"
<br />RISK CATAGORY: II
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT: +/- 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/37STRUCTURAL SHEATHING
<br />EXP 1 (40420), FOR G CEMENT( IOUS TILE AND METAL ROOF( USE MIN.
<br />02 T N
<br />i9/37' STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD
<br />AND EDGE SPACING) SEE DETAIL
<br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN
<br />NAILS 0 4" O.C. EDGEWISE 2.4 BLOCKING ALL PANEL JOINTS W/ IN V OF
<br />GABLE END.
<br />ROOF/ WALU FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />SIZE
<br />HEAD
<br />LENGTH
<br />DIA,
<br />TENSILE STIR.
<br />SHANK
<br />ASTM
<br />Tod
<br />RING SHANK,
<br />21/2'
<br />0131
<br />F1667
<br />SCREW HANK
<br />170000
<br />RING
<br />( tE20 RINGS
<br />RSRS-03
<br />8tl
<br />RING SHANK,
<br />2 3!9'
<br />0.113
<br />F1667
<br />SCREW SHANK
<br />PER INCH )
<br />RSRS-01
<br />81
<br />RING SHANK,
<br />PNEUMATIC
<br />2WS'
<br />0,113
<br />F1667
<br />SCREW -NAILS
<br />RSRS-01
<br />EXTERIOR SHEATHING
<br />USE 12" COX OR 7/16' O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4"
<br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP &
<br />BOTTOM PANEL AND SO RING SHANK GUN NAILS AT 6" O.C. AT
<br />INTERMEDIATE SUPPORTS OR 7116" ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL.
<br />ROOF SHEATHING ATTACHEMENT SPACING
<br />ZONE 1: 1 Od NAILS 0 4" O.C. ON EDGE AND 6" O.C. IN FIELD
<br />ZONE 2e, 2n, 2r 10d NAILS @ 4" O.C. ON EDGE AND 4" O.C. INFIELD
<br />ZONE 3,3e, 3r: 10d NAILS C4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />NO • ROOF SHEATHING THICKNESS WAS CALCULATED
<br />AND ADHERES TO ASCE 7-16
<br />8d RING SHANK GUN NAILS 04" O.CIr .
<br />TOP & BOTTOM EDGES
<br />0
<br />B
<br />RAFTER OR TRUSS
<br />ROOF SHEATHING
<br />■1♦mimm
<br />mmm
<br />=mW
<br />mmI, 11
<br />I
<br />I "
<br />11
<br />111,111.111.111.111.1`- I
<br />U BUILDING LENGTH
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />NOTE: GABLES -DROP GABLE END & (1) ADO'L DROPPED
<br />TRUSS 2,14 #2 SYP OUTLOOKER RAFTER W/ BLOCKING M
<br />16'O.C, IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP
<br />BLOCKING 0 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA.
<br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/
<br />BLOCKING PER NAILING SCHEDULE
<br />Tod RING SHANK GUN NAILS
<br />SEE "ROOF SHEATHING ATTACHMENT"
<br />TABLE FOR FIELD SPACING ,
<br />#8 7' DECK SCREWS 0 6"-8" O.C. MAX
<br />EQGES & 12' O.C. MAX IN FIELD. UNTHREADED
<br />SHANK TO EXTEND BEYOND THICKNESS OF
<br />SUB -FLOOR SHEATHING
<br />I YK 3/4" 1 &U SUB+LUUH ULUKINU GLULU I U ALL LXHUSLU MLMbt:H5
<br />GENERAL NOTES:
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33C33W MAXIMUM AGGREGATE SIZE SHALL BE 3/4',
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />WOOD:
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />PROVIDE6%AIR ENTRAINED CONCRETE EXPOSEDTO EARTH OR WEATHER
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 314'
<br />ON STRUCTURAL DRAWINGS, APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 7th EDITION
<br />.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />PROVIDE 64AIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS -ON -GROUND WHERE INDICATED ON
<br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF
<br />FOR STRUCTURAL CONCRETE, TMS 4021602-16 AISI SPECIFICATION FOR THE DESIGN OF
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS
<br />DRAWINGS. SEAMS LAPPED 61NCHES AND SEALED WITH ADHESIVE TAPE.
<br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />PRESSURE TREATED, PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />FORMWORK:
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF OA2 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST
<br />WI DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK.
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FBCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />OF THE WORK
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL. DEPEND NG PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAYBE REQUIRED BUT ARE BY OTHERS
<br />SYP #2.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />DESIGN LOADS:
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf
<br />20 psf TOP CHORD-non-Sonculrent
<br />10 psf BTM CHORD -non -concurrent
<br />DEAD LOAD DEADLOAD
<br />WELDED WIRE MESH:
<br />WELDED WIRE MESH, SHALL BE ASTM A1084/A1064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE
<br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL
<br />BE SUPPORTED WITH 2' CHAIRS SPACED Y-0.00, EACH WAY.
<br />REINFORCING STEEL:
<br />REBAR SHALL BE ASTM A615A815M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615
<br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE
<br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />AND VERTICAL BARS SHALL LAP 8 x BAR NO, UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S
<br />REVIEW.
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36'
<br />#5 BAR - 30' #7 BAR - 42'
<br />PROVIDE 36' x 36" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />FOR ADDITIONAL INFORMATION.
<br />15 pSf TOP CHORD 20 psf TOP CHORD ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />(7 psf w/ ASPHALT SHINGLES) 5 p psf w/ No GVPCRETE) THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />10 psf BTM CHORD 5 psf BTM CHORD
<br />DEAD LOAD TO RESIST WIND UPLIFT: 10psf MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />BALCONY LIVE LOAD 60 psf WALL. TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />STAIRS LIVE LOAD 40 psf
<br />WIND: DEAD LOAD SPEED =160 MPH 3-SECOND GUST
<br />(ASCE 7-16 (FBC R2020) EXPOSURE C, RISK CATEGORY 10
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10psf, UNINHABITABLE ATTIC WITH LIMITED
<br />STORAGE: 2Dpef, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR)
<br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER
<br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS:
<br />40psf
<br />SHOP DRAWING REVIEW:
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />OF THE CONTRACT DOCUMENTS ONLY, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />WRITING BY THE ARCHITECT.
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />MASONRY:
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY
<br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY
<br />THE MASONRY STANDARDS JOINT COMMITTEE.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fin = 2000 PSI. BLOCK SHALL BE PLACED USING
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />ASTM C-078 AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS UNLESS
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318"
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />FOUNDATION/ SITE PREPARATION: TYPE W" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM 0-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE SHALL BE 318" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL CELLS TO BE FILLED.
<br />SOIL FOR TERMITE PROTECTION.
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />CONCRETE:
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOV46:
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB.
<br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO
<br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED T d- PRIOR TO THE ADDITION OF PLASTICIZER.
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94MW OR MEASURING, MXING TRANSPORTING,
<br />ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN
<br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON
<br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL
<br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY
<br />NON COMPUANCE WITH THE ABOVE
<br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS:
<br />A. 3' FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS):
<br />B. FOR CONCRETE EXPOSED TO EARTH ANDIOR WEATHER:
<br />1-1
<br />/2' FOR X6 AND SMALLER
<br />2' FOR 06 AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />3/4' FOR SLABS, WALLS AND JOISTS
<br />1-1/2'FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />REINFORCING.
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O.
<br />STRUCTURAL STEEL:
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36/A36M FY = 36 W FOR ANGLES PLATES AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM
<br />A50
<br />0
<br />IA500M GRADE B F =48 W. STRUCTURAL PIPE SHALL BE ASTM A53/A53M GRADE BTYPE E OR S FEY
<br />=
<br />Y
<br />35 ksi. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />OTHER BOLTS SHALL BE ASTM F3125IF3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS
<br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. JSOLTS ARE TO BE STEEL.
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />WOOD TRUSSES:
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE 'NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS" BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.03e' AND BE MANUFACTURED FROM STEEL
<br />MEETING THE REQUIREMENTS OF ASTM A446/A446M GRADE A AND SHALL BE HOT -DIPPED GALVANZED.
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL
<br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "BCSI LATEST EDITION"
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METALfLATE-CONNECTED
<br />WOOD TRUSSES.
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88 1990
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FORBEARING
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />LICENSED PROFESSIONAL ENGINEER.
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />APPLICATION
<br />SIZE
<br />TYPE
<br />SPACING
<br />REMARKS
<br />APPLICATION
<br />S.
<br />TYPE
<br />SEALING
<br />RE-
<br />1z2PTFURRING iO
<br />MASONRY I CON4
<br />CASE-RCENEDCOIL
<br />B DC
<br />GPRAGE--A
<br />ONRY/OONC.
<br />1I4'DA
<br />NO WASHER
<br />TAPWNMASONRY
<br />FASTENER
<br />9"OTC
<br />(?EMBED.. I END q9T.,
<br />2'EWEDST.
<br />SODALEE DOORS
<br />CPNAL
<br />9'O/C
<br />WINWWIWORIYCONDED
<br />DAM AGE DOOR BUCK
<br />ve^ OIA OR
<br />18"C!CS -GA)
<br />4"EMBED., 4- END DST.,
<br />1. Pt SEE NOTES
<br />111ENEDGOIL
<br />NAIL, 1/Y'LOWG.
<br />9TAWEREo
<br />INTO MA90NRYA'X1NC.
<br />TOMASONRY/OJNC.
<br />,—
<br />wI WASHER
<br />E%PANSIgJ BOLT
<br />24"OTC 0—A)
<br />3"EDGE DST.
<br />vANDmv BUCK
<br />CASE KAR NED-L
<br />B'x
<br />wNDDW DO—I'ASTENED
<br />MEA STRAP TG
<br />CONTACT THIS ENGINEER FOR SPACING
<br />,r Pf, SEE NOTES
<br />Hal „rr LONG.
<br />STAGGERED
<br />INTO MAsoNRYIWNc.
<br />MAsoNRVlco"G
<br />REQUIREMENTS
<br />EXT SING DOOR
<br />BUCK b PT, SEE NOTES
<br />(O M,e'gq
<br />NO WASHER
<br />"TAPCON
<br />FASTNER
<br />1b' QC
<br />11/2"EMBED, B"ENO.
<br />019T., 1 1l2' EDGE q9T.
<br />NON-SEARINGWWO
<br />WgLL TO CONC.6LPB
<br />1R" EXPANSION 24„ 4"EMBED. 4"ENO
<br />ABHER GIST.. 9" EWE q9T.
<br />L PT WINWW BUCK 61W°PW421Po' 9"QC
<br />PTTOSTEELOO SEE 9TAWEAEp EEDGE DSTTEI .1rs
<br />NOTES
<br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND/ OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WTH A WOOD DOOR FRAME. 1. MEMBERS ARE NAILED AND
<br />Z. MEMBERS ARE SECURED W7 TAPCONS OR PAF TO THE SUBSTRATE.
<br />1441 N. RONALD REAGAN BLVD.
<br />LONGWOOD, FL32750
<br />PH: 407-7746078
<br />FAX: 407-774-4078
<br />www.abdesigngroup.com
<br />AA #: 0003325 J
<br />i
<br />aul3mv. & LIT
<br />ABBOTT PARK
<br />LOT #11
<br />BLK. #9
<br />PROJECT#
<br />04181.000-11091
<br />MODELa
<br />4EBB
<br />"1828-CALI"
<br />GARAGE OWING:
<br />LEFT
<br />PAGE:
<br />DETAILS
<br />%160 MPH RV. C
<br />1I
<br />mm
<br />DATE 8/14/21
<br />aCAL.E: 1/4"=1'-0"
<br />S*EC T
<br />SN1
<br />
|