<br />ROOF WIND DESIGN PRESSURES
<br />NET (GROSS) ASCE 10
<br />ZONE 1 =23.79 PSF (33.79)
<br />ZONE 2 = 39.48 PSF (49.48)
<br />ZONE 3 = 67.16 PSF (77.16)
<br />'A'-4'-0' END ZONE DISTANCE
<br />BASIC WIND SPEED: 160 MPH
<br />WIND EXPOSURE:'C'
<br />RISK CATAGORY: II
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT+- 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16-
<br />O.S.B. OR 1/2' CDX EXT. PLYWOOD, FOR
<br />CEMENTITIOUS TILE AND METAL ROOFING, USE
<br />MIN. WS CDX EXT. PLYWOOD, WITH 8d RING
<br />SHANK GUN NAILS AT 4' O.C. AT SUPPORTED
<br />PANEL EDGES AND 8d RING SHANK GUN NAILS
<br />AT 6' O.C. AT INTERMEDIATE SUPPORTS. SEE
<br />DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE
<br />8d GUN NAILS 0 4' O.C. EDGEWISE 2x4
<br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE
<br />END.
<br />ROOF/ WALL/ FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />NAIL SCHEDULE
<br />SIZE
<br />TYPE
<br />MIN. LENGTH
<br />MIN. DIA.
<br />SHANK
<br />TENSILE STR.
<br />SHANK
<br />8d
<br />RING SHANK,
<br />2 1/2'
<br />0.120'
<br />170,000
<br />RING
<br />18-2RINGS
<br />SCREW SHANK
<br />ER NCH)
<br />I
<br />8d
<br />SCREW SHANK
<br />2 1/2"
<br />0.120'
<br />PNEUMATIC
<br />SCREW -NAILS
<br />1. NAIL SIZE PER ASTM F1664
<br />2. INTERNATIONAL STAPE, NAIL & TOOL
<br />ASSOCIATION ([SANTA) ESR-1539
<br />EXTERIOR SHEAT I1140
<br />USE 1/2" CDX OR 7/16' O.S.B. PLY WITH Bd RING
<br />SHANK GUN NAILS AT 4' O.C. AT PANEL SIDES
<br />AND 8d RING SHANK GUN NAILS 4' O.C. TOP &
<br />BOTTOM PANEL AND 8d RING SHANK GUN
<br />NAILS AT 6' O.C. AT INTERMEDIATE SUPPORTS
<br />OR 7116' ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL.
<br />8d RING SHANK GUN NAILS ® 4" O.C.
<br />.. TOP & BOTTOM EDGES ..
<br />Z
<br />Z 0
<br />� W
<br />C ILL
<br />Z
<br />Z
<br />_ �
<br />V O
<br />2 ®
<br />q .
<br />Q
<br />Z
<br />j .
<br />S
<br />Y
<br />2 '
<br />N
<br />C7 .
<br />(D
<br />J
<br />Zw
<br />7
<br />L5 W
<br />Y
<br />Q
<br />=U
<br />Tn Q
<br />L7 a
<br />Z
<br />OD '
<br />J
<br />Q
<br />Y Z
<br />Q W
<br />2CC
<br />3 c0 w
<br />W
<br />�< o
<br />m W
<br />a
<br />TOP CORD BLOCKING AT W
<br />O.C. MAX. IN FIRST 2 FRAMING
<br />SPACES AT EACH END.
<br />RAFTER OR TRUSS
<br />Glll1F CLJFAT411Nr
<br />---_M' ,1
<br />BUILDING
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />C8d RING SHANK GUN NAILS
<br />0 W O.C. IN FIELD `
<br />C8d RING SHANK GUN NAILS 0 12- O.C. IN
<br />FIELD or 8d x 2 1/2' SCREW SHANK
<br />PNEUMATIC SCREW -NAILS 0 12' 0.S
<br />FIELD J\
<br />TYP, 3/4' T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33. MAXIMUM AGGREGATE SIZE SHALL BE 31C.
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />WOOD:
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />pROWDE6%A6t ENTRAINED CONCRETE EXPOSEDTO EARTH OR WEATHER
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBCR 2017. ft EDITION
<br />ALL EXPOSED EDGES OF CONCRETE ARE 70 BE CfWMFERE03/1'.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. Fb - 1100 PSI AND A MODULUS OF
<br />FOR STRUCTURAL CONCRETE, ACI 530-13/ASCE 6.13 AISI SPECIFICATION FOR THE DESIGN OF
<br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER AL.SLABS-ONC�ItOUND WHERE INDICATED ON
<br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011. ASCE 7-10 AND AISC SPECIFICATIONS
<br />DRAWINGS. SEAMS LAPPED 61NCHES AND SEALEDWITH ADHESIVE TAPE.
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED, WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />FORMWORK:
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />FORMWORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE, NAILS, SPIKE, BOLTS USED
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347,
<br />W/ DOT SHALL BE HOT DIPPED GALV, FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />`RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK.
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FBCR 2017, sth EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />OF THE WORK.
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2X STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS
<br />SYP #2.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES 70 INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />WELDED WIRE MESH:
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />WELDED WIRE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI
<br />WOOD TRUSSES:
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE
<br />SUPPORTED WITH 2' CHAIRS SPACED S-O' OC EACH WAY.
<br />'
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE "NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS' THE NFPA. TRUSS DESIGNS SHALL SIGNED AND
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />E O
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />REINFORCING STEEL:
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />REBAR SHALL BE ASTM A616 GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615
<br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED.
<br />GRADE 601N MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE
<br />DESIGN LOADS:
<br />W/THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />E
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES ACCORDANCE DESIGN NATIONAL
<br />TM,
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />UWITH
<br />STANDARDS FOR METAL-PLATE-CONNECTED-WOODTRUSSCONSTRUCTION:, AND TPIM/TCA SCSI 1"
<br />D AN
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 pet
<br />ANDREVVERTICAL BARS SHALL LAP 8 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />20 PEI TOP CHORD -non-cancumnt
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: 04 BAR - 26" #6 BAR - 36" W.
<br />WOOD TRUSSES.
<br />10 pst STM CHORD-non-Doncurml
<br />#5 BAR - 30" #7 BAR - 42'
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADOMONAL DEAD LOADS FOR THE ROOF
<br />PROVIDE 36' x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />DEAD LOAD DEAD LOAD
<br />FOR ADDITIONAL INFORMATION.
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982.
<br />16 pal TOP CHORD p TOP CHORD
<br />(7 psf w/ ASPHALT SHINGLES) (1 a w/ No GYPCRETE)
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />5 p l B
<br />t 0 BTM CHORD 5 pal BTM CHORD
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />ApSfD
<br />DEAD LOAD TO RESIST WIND UPLIFT; 10psi
<br />MINIMUM 101NCH NOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />BALCONY LIVE LOAD 60 pef
<br />WALL.
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />STAIRS LIVE LOAD 40 pef
<br />WIND: DEAD LOAD SPEED =1R2017) MPH S- SECOND GUST
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS DOWEL
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />EXPOSURE C. RISK CATEGORY Iq
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10IT UNINHABITABLE ATTIC WITH LIMITED
<br />UVE(ASCE BIT BLE(FBC ATTIC
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />STORAGE: HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: BALCONIES (EXTERIOR)
<br />STO
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />: 40p NTS:
<br />AND DECKS: 40peF, OUAgDS AND HANDRAILS: 200pef, GUARD IN -FILL COMPONENTS: 60pef, PASSENGER
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />VEHICLE GARAGES: 60psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS:
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />40pef
<br />MASONRY,
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />LICENSED PROFESSIONAL ENGINEER.
<br />SHOP DRAWING REVIEW:
<br />'SPECIFICATION MASONRY STRUCTURES' (ACI 630/ASCE S/TMS 402, BUILDING CODE REQUIREMENTS FOR
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE.
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT.
<br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE F. = 1500 PSI. BLOCK SHALL BE PLACED USING
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7.10 COMPONENT
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM SIT
<br />WRITING BY THE ARCHITECT.
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8' TO 10'. USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />FOUNDATION/ SITE PREPARATION'
<br />"M'
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING
<br />TYPE OR'S' MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE
<br />SHALL BE 318' THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM 0-1667. TREAT ALL
<br />CELLS TO BE FILLED.
<br />SOIL FOR TERMITE PROTECTION.
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />REINFORCING.
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEERS REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O.
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />STRUCTURAL STEEL:
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WFTH THE
<br />CONCRETE:
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36 F 36 ksl FOR ANGLES PLATES AND W SHAPES STRUCTURAL TUBING SHALL BE ASTM A500 CcAnc G
<br />2,600 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB.
<br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, NTH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MX PRIOR TO
<br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5' N- PRIOR TO THE ADDITION OF PLASTICIZER
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C94 OR MEASURING, MIXING, TRANSPORTING, ETC.
<br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE 18 BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS
<br />ADDED TO THE MX UNTIL IT IS OEPOSI1fD IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON THERE IS A
<br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED, IT SHALL BE THE
<br />RESPONSIBNTY OF THE TESTING LABORATORY TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY NON
<br />COMPLIANCE E WITH THE ABOVE.
<br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS:
<br />A 3' FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS):
<br />B. FOR CONCRETE EXPOSED TO EARTH ANDIOR WEATHER
<br />1.112" FOR 45 AND SMALLER
<br />2' FOR 06 AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />314. FOR SLABS, WALLS AND JOISTS
<br />i-iR' FOR BEAM AND COLLMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />Y=
<br />Fy =48 ksi. STRUCTURAL PIPE SHALL BE ASTM53, GRADE B, TYPE E OR S, Fy = 35 k8l, TUBE AND PIPE
<br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING, ALL
<br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL
<br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />APPLICATpN
<br />911E
<br />TYPE
<br />&PACWO
<br />REMAfMS
<br />APPLICATCN
<br />SIZE
<br />TYPE
<br />SPACWG
<br />REMARKS
<br />I PTFURPJNOTO
<br />CASEHAROENE-
<br />GA -DOOR BUCK
<br />I/A•DIA.
<br />TAPCONMASIXJRV
<br />1112'EMBED., A'END 019T.,
<br />MASONFTICONC.
<br />IUIL 11/Y LONG.
<br />S O�
<br />TO M/SONRYftbNC.
<br />NO WASHER
<br />FASTENER
<br />I,_
<br />R'EDGEDIST.
<br />SGD.AL.EXT.DO
<br />CASE HARDENED COIL
<br />e'O/C
<br />WINDOW/DOOq/fA9TENED
<br />OAMGEDODRWCK
<br />1R'DN. W/
<br />E%PANSION BOLT
<br />4•EMBED., 4•END DST.,
<br />1. SEE NOTES
<br />NALI-LONG.
<br />STAGGERED
<br />INTO MA90NRYA:ONC.
<br />TO MASONRYA%X2C.
<br />WASHER
<br />2A'QC
<br />0•EDGE DST.
<br />WINDON SUCK
<br />CA9EI-ENEDCOLL
<br />e'OIC
<br />WINDOWA%JOWFABTENED
<br />-AL srPAPro
<br />CONTACT THIS ENGINEER FOR SPACING
<br />I Z PT, SEE NOTE4
<br />NAIL 11?LCNG.
<br />STAGGERED
<br />IN To M0.9gJRYA;ONC.
<br />MASONRY/cow,
<br />REQUIREMENTS
<br />EM. SWING ODOR
<br />(2)3�18'DN,
<br />APCON'
<br />I12' EMBED, B' END
<br />NG40EARING W000
<br />I/2'° E%PANSION A'EMBED. A'Er0
<br />SUCK 21 PT, SEE NOTE C
<br />NO WASHER
<br />ASTNER
<br />18'OC
<br />019T.,11-DGE DST.
<br />CONC. SLAB
<br />W/WASNEP BOLT DUST., 3'EDGE DST.
<br />2x PTWINDOWBUCK O.I3a°PAT R2IPo' 0'CA: A• END. DST., I I2'
<br />PTTOSTEELOM. SEE W/WASHER STAGGERED EDGE DIST.
<br />NOTES
<br />1 STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND/OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAP SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NAILED AND
<br />2X MEMBERS ARE SECURED W/ TAPCONS OR PAP TO THE SUBSTRATE.
<br />1441 N. RONALD REAGAN BLVD
<br />LONGWOOD, FL 32750
<br />PH: 407-774-6078
<br />FAX: 407-774.4078
<br />www.abdosigngroup.com
<br />AA #: 0003325 _ J
<br />y4�
<br />C
<br />>lVBDIV. & LOT:
<br />ABBOTT PARK
<br />LOT #19
<br />BLK #15
<br />PROJECT#
<br />04181.000-19151
<br />MODEL:
<br />4EAB
<br />"1672-ARIA"
<br />GARAGE BWING:
<br />LEFT
<br />PAGE:
<br />DETAILS
<br />160 MPH EXP. C