q <br />* w <br />GABLE -ETD <br />HIP ROOF x w <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) AUCE: 7-lU <br />ZONE 1 = 18.52 PSF (28.52)) <br />ZONE 2 = 32.73 PSF (42.73) <br />ZONE 3 = 56.14 PSF (66.14) <br />"A"= 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />WIND EXPOSURE: "C" <br />RISK CATAGORY: 11 <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT+- 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16" <br />O.S.B. OR 12"CDX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. 5/8 COX EXT. PLYWOOD, WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND Sd. RING SHANK GUN NAILS <br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE <br />8d GUN NAILS @ 4" O.C. EDGEWISE 2x4 <br />BLOCKING ALL PANEL JOINTS WI IN 4' OF GABLE <br />END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. DIA. <br />SHANK <br />TENSILE STR. <br />SHANK <br />Bd <br />RING SHANK, <br />2 1/2'• <br />0.120" <br />170.000 <br />WrNd- <br />(16--20 RINGS <br />SCREW SHANK <br />PER INCH) <br />Sd <br />SCREW SHANK <br />2 1/2" <br />0.120" <br />PNEUMATIC <br />SCREW -NAILS <br />1. NAIL SIZE PER ASTM F1664 TOP CORD BLOCKING AT 4' <br />2. INTERNATIONAL STAPE, NAIL S TOOL O.C. MAX. IN FIRST 2 FRAMING <br />ASSOCIATION (ISANTA) ESR-1539 SPACES AT EACH END. <br />RAFTER OR TRUSS <br />ROOF SHEATHING <br />EXTERIOR SHEATHING <br />USE 112" COX OR 7116" O.S.B. PLY WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES <br />AND 8d RING SHANK GUN NAILS 4" O.C. TOP 8 <br />BOTTOM PANEL AND 8d RING SHANK GUN <br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS <br />OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUR SPECS.) SEE DETAIL. <br />8d RING SHANK GUN NAILS Q 4" O.C. <br />.- TOP 8 BOTTOM EDGES .- <br />J <br />z9 <br />� w <br />zY <br />2 <br />U � <br />O c <br />0) <br />J <br />QY <br />N <br />O . <br />K . <br />_J <br />W <br />0w <br />Z <br />a0 <br />� O <br />O 'v <br />Z <br />S <br />a <br />Z 2 N <br />a GJ W <br />O <br />W <br />W V <br />U H . <br />CO M O <br />m W o <br />a <br />I,1111'1111,111,1111,I <br />■�m��EMMMML �.��mmmm-11■1 I <br />jll� <br />=I <br />ROOF SHEATHING LAYOUT <br />AND ENOWALL BRACING <br />FOR GABLE END FRAMING <br />C8d RING SHANK GUN NAILS <br />0 6" O.C. IN FIELD <br />HEA I N R S I O.. . <br />TO BE STRUCTURAL GRADE <br />C8d RING SHANK GUN NAILS @ 12" O.C. IN <br />FIELD or 8d x 2 12" SCREW SHANK <br />PNEUMATIC SCREW -NAILS @ 12" 0.6.jN <br />FIELD J\ <br />TYP. 3/4" T8G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTMCM MAXIMUM AGGREGATE SIZESH4LL BE 3W <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />WOOD: <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />PROVIDE 6%AIR ENTFAI ED CONCRETE EXPOSED TO EARTH ORWEATHER <br />NON -BEARING WOOD WALLS TOP PLATES 8 STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS, APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, Bth EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED L/'. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-14. BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF <br />FOR STRUCTURAL CONCRETE, ACI 530.13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF <br />PROVIDE 8-MW L CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABSONIM GROD AHERE INDICATED ON <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS <br />DRAWINGS. SEAM MAPPED B INCHES AND SEALED WITH ADHESIVE TAPE. <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONSTRUCTURAL USES <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORM -WORK: <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODfUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORMWORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE, NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347. <br />W/ DOT SHALL BE HOT DIPPED GALV, FOR STRUCTURAL USES. AVOID BUYING TREATED LUMBER THAT <br />'RECOMMENDED PRACTICE FOR CONCRETE FORMWORK. <br />CONTAINS MORE THAN W OF HEARTWOOD, <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2017, eel EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2X STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP 112. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE 94 DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH' <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />OURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />WELDED WIRE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI <br />WOOD TRUSSES: <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES, WIRE MESH FOR SLABS SHALL BE <br />SUPPORTED WITH 2' CHAIRS SPACED 3'-0' OC. EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />REQUIREMENTS AND SLA"N-GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS, <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />DESIGN LOADS: <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 par <br />20 psi TOP CHORD -norHconarrerd <br />10 psf BTM CHORD-rwrvconcurteM <br />DEADLOAD DEAD LOAD <br />15 pH TOP CHORD 20 psf TOP CHORD <br />(7 psf w/ ASPHALT SHINGLES) (10 psf w/ No GVPCRETE) <br />10 psf BTM CHORD 5 psf BTM CHORD <br />DEAD LOAD TO RESIST WIND UPLIFT: tOpsf <br />BALCONY LIVE LOAD 60 psi <br />STAIRS LIVE LOAD 40 Paf <br />WIND: DEAD LOAD SPEED=160 MPH 3-SECOND GUST <br />(ASCE 7-10 (FBC R2017) EXPOSURE C, RISK CATEGORY II) <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10psf, UNINHABITABLE ATTIC WITH LIMITED <br />STORAGE: 20psi, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30ps1, BALCONIES (EXTERIOR) <br />AND DECKS: 40PS1. GUARDS AND HANDRAIL$: 200psf, GUARD IN4'ILL COMPONENTS: SOpO, PASSENGER <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40pei, SLEEPING ROOMS: 30psf, STAIRS: <br />40Psf <br />SHOP DRAWING REVIEW: <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />WRITING BY THE ARCHITECT. <br />FOUNDATIOW SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 If, FOOTING <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 96% OF THE <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL <br />SOIL FOR TERMITE PROTECTION. <br />REINFORCING STEEL: <br />REBAR SHALL BE ASTM ABI5 GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM AS15 <br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEERS <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36" <br />#5 BAR - 30" #7 BAR - 42" <br />PROVIDE 38" X 36' CORNER BARS, BOND BEAM ONLY, UPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION. <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />STANDARDS FOR METAL-PLATECONNECTED-WOOD TRUSS CONSTRUCTION:, AND 'TPI/WTCA BCSI 1" <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />WOOD TRUSSES. <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982. <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />WALL. <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS, DOWEL <br />ROOF a FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY 8 ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LAYOUT, SPANS &ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />MASONRY: <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />'SPECIFICATION MASONRY STRUCTURES' (ACI 5301 ASCE S/TMS 402, BUILDING CODE REQUIREMENTS FOR <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fm - 2000 PSI. BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8" <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8" TO 10'. USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />SHALL BE 3/8' THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />CELLS TO BE FILLED. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO•TECHNICAL ENGINEER TO VERIFY <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL REBAR 6 X SAR NO. (48 BAR DIAMETERS)., U.N.O. <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />STRUCTURAL STEEL: <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />CONCRETE: <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A38, Fy = 36 kN FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A-500, GRADE 8, <br />Fy - 48 ksl. STRUCTURAL PIPE SHALL BE ASTM53, GRADE B, TYPE E OR S, Fy = 35 Iasi. TUBE AND PIPE <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />STRENGTH <br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH WSTOPoCM STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />SUBMITFOR EACH <br />PRETESEDMz3HALLNS, <br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />CONTRACTORHALL <br />EXTHEIST°N-PRI ADDITION <br />NOTBE <br />TIGHTENED IN ACCORDANCE WITH THE TURNOFF -THE -NUT METHOD. <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C440R MEASURING, MXING, TRANSPORTING, ETC. ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL. <br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOYED FROM WHEN WATER IS <br />ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SWILL NOT EXCEED 90 MINUTES. IF FOR ANY REASON THERE IS <br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SWILL BE THE <br />RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY NON <br />COMPLIANCE WITH THE ABOVE <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A 3' FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS): <br />B. FOR CONCRETE EXPOSED TO EARTH ANDfOR WEATHER <br />1-1/2"FOR I5 AND SMALLER <br />T FOR #9 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />314' FOR SLABS, WALLS AND JOISTS <br />147 FOR BEAM MID COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APPLIUTKIN <br />SIZE <br />TYPE <br />9PACKJG <br />REMARKS <br />APPELLATION <br />SIZE <br />TYPE <br />SPACING <br />REMARx9 <br />FURRNGTO <br />1MASOMiY1CONC. <br />USE HAROENEDCO! <br />S, dC <br />6FAAOE DOOR BUCK <br />N•WA. <br />TAPCON AM90HNY <br />a. <br />1Yt EMBED., 4' END <br />NM411?40NG. <br />TO MASgMY/OONC. <br />NOWASHER <br />FASTENER <br />ttrz"EDGE DIET. <br />SGD�AL. EXT. DOORS <br />x ,A <br />1SEENOTEw.-BACK <br />CAEEHARDENEDOX <br />NM411?LONG. <br />PING <br />STAGGERED <br />WwDDWl0001L I-—D <br />INTO MASONRwQONC. <br />GARAGE DOOR BUCK <br />T OMA60NRY/WNC. <br />Ow. W/ <br />WASHER <br />EXPANSION BOLT <br />24'OG <br />1'EMBEDGENOD5i., <br />SEDGE WST. <br />CASE HARDENED CALL <br />9'WC <br />WwDOWIDOOP/FABTENED <br />METAL sTw TO <br />CONTACT THIS ENGINEER FOR SPACING <br />1x Pi, BEE NOTES <br />NML 112•LONG. <br />_GERED <br />INTO MASONRVICONC, <br />MASONRY/CONO <br />REQUIREMENTS <br />-IN. DOOR <br />(2)3'1BOIA, <br />RAPCON' <br />1 P O10 <br />11lY'_EO, P END. <br />NONBEARINGW000 <br />VP• E%PANSION d"EMBED. I"D <br />2d° OIC <br />BUCK 2x PT, SEE NOTE B <br />NO WASHER <br />FASTNER <br />0W., 1 1 EDGE WST. <br />WALL TO LONG. SUB <br />W/ WASHER BOLT GET., 3° EDGE DIST. <br />­ VND1Y BUCK 3B'PAF iT POIC 4•END. DI6T.,11rz' <br />01W/WASHER <br />P NELCUL"SEE xY <br />OTE6 6TAOGEHEO EDGE GIST, <br />i�SAPTAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURERS SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAP SHALL BE HILT] X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NM LED AND <br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE, <br />li N. RONALD REAGAN <br />LONGWOOD, FL 327777 <br />PH: 407-774,607 <br />FAX: 407-7744078 <br />www.abdeslgngroup.com <br />AA #: 0003325 <br />W <br />0 <br />ro <br />pad� <br />C <br />Ewy <br />atmErV. ae LOT <br />ABBOTT PARK <br />LOT #22 <br />BLK #8 <br />PLtojzcT/ <br />04181.000-22081 <br />1408 <br />"DAKO A" <br />GARAGE G: <br />RIGHT <br />PAGR: <br />DETAILS <br />160 MPH E C <br />