mb
<br />•
<br />q
<br />a A
<br />GABLE END
<br />HIP RDOF i`A'
<br />ROOF WIND DESIGN PRESSURES
<br />NET ( -10
<br />ZONE 1 = 23.79 PSF (33.79)
<br />ZONE 2 = 39.48 PSF (49.48)
<br />ZONE 3 = 67.16 PSF (77.16)
<br />'A'= 4'-O' END ZONE DISTANCE
<br />BASIC WIND SPEED: 160 MPH
<br />WIND EXPOSURE:'C'
<br />RISK CATAGORY: II
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT +- 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 7116-
<br />O.S.B. OR 1/2' CDX EXT. PLYWOOD, FOR
<br />CEMENTITIOUS TILE AND METAL ROOFING, USE
<br />MIN. 518 CDX EXT. PLYWOOD, WITH 8d RING
<br />SHANK GUN NAILS AT 4' O.C. AT SUPPORTED
<br />PANEL EDGES AND 8d RING SHANK GUN NAILS
<br />AT e' O.C, AT INTERMEDIATE SUPPORTS. SEE
<br />DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE
<br />8d GUN NAILS 0 4' O.C. EDGEWISE 2x4
<br />BLOCKING ALL PANEL JOINTS W/ IN W OF GABLE
<br />END,
<br />ROOF/ WALU FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />NAIL SCHEDULE
<br />SIZE
<br />TYPE
<br />MIN, LENGTH
<br />MIN. DIA.
<br />SHANK
<br />TENSILE STR.
<br />SHANK
<br />ad
<br />RING SHANK,
<br />2 1/2'
<br />0.120'
<br />170,000
<br />1 ff—
<br />SCREW SHANK
<br />(116-2 RUNGS
<br />8d
<br />SCREW SHANK
<br />2 1/2'
<br />0.120'
<br />PNEUMATIC
<br />SCREW -NAILS
<br />1. NAIL SIZE PER ASTMF1664
<br />2. INTERNATIONAL STAPE, NAIL & TOOL
<br />ASSOCIATION (ISANTA) ESR-1539
<br />EXTERIOR SHEATHING
<br />USE 1/2' CDX OR 7/16' O.S.B. PLY WITH Bd RING
<br />SHANK GUN NAILS AT 4' O.C. AT PANEL SIDES
<br />AND ad RING SHANK GUN NAILS 4' O.C. TOP &
<br />BOTTOM PANEL AND 8d RING SHANK GUN
<br />NAILS AT 6- O.C. AT INTERMEDIATE SUPPORTS
<br />OR 7116' ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL,
<br />8d RING SHANK GUN NAILS® 4" O.C.
<br />.- TOP & BOTTOM EDGES
<br />J
<br />Q
<br />2 Q
<br />7 w
<br />Z7 Z
<br />Q 2
<br />U
<br />m O
<br />z`O
<br />di
<br />V -
<br />J
<br />zN
<br />za
<br />0 W
<br />Y a
<br />Q
<br />=U
<br />in O
<br />Z_a
<br />Q
<br />J J
<br />Q
<br />Z Y Z
<br />z z< LU
<br />a
<br />cD �U w
<br />a wL)a®
<br />It
<br />`a o
<br />z ' -
<br />W
<br />$ a
<br />TOP CORD BLOCKING AT 4'
<br />O.C. MAX. IN FIRST 2 FRAMING
<br />SPACES AT EACH END.
<br />RAFTER OR TRUSS—�
<br />ROOF SHEATHINGS
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />C8d RING SHANK GUN NAILS
<br />B 6' O.C. IN FIELD `
<br />8d RING SHANK GUN NAILS G 12' O.C. IN
<br />FIELD or Bd x 2 1/2' SCREW SHANK
<br />PNEUMATIC SCREW -NAILS 0 12' 0.7
<br />FIELD
<br />TYP. 3/4' T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBGR 2017, ffM EDITION
<br />ACI 318-14. BUILDING CODE REQUIREMENTS
<br />FOR STRUCTURAL CONCRETE, ACI 630-13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />OF THE WORK.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />DESIGN LOADS:
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf
<br />20 psf TOP CHORD nan-concurrent
<br />10 pet BTM CHORD -non-coocui—I
<br />DEADLOAD DEADLOAD
<br />15 pat TOP CHORD 20 psf TOP CHORD
<br />(7 psfW ASPHALT SHINGLES) (10 psf w/ No GYPCRETE)
<br />10 psf BTM CHORD 6 PSI BTM CHORD
<br />DEAD LOAD TO RESIST WIND UPLIFT: 1Opsf
<br />BALCONY LIVE LOAD 60 psf
<br />STAIRS LIVE LOAD 40 psf
<br />WIND: DEAD LOAD SPEED-180 MPH 3-SECOND GUST
<br />(ASCE 7-10 (FSC R2017) EXPOSURE C, RISK CATEGORY II)
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: tOpsf, UNINHABITABLE ATTIC WITH LIMBED
<br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR)
<br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER
<br />VEHICLE GARAGES: SDpsf, ROOMS OTHER THAN SLEEPING ROOM: 40*, SLEEPING ROOMS: 30psL STAIRS:
<br />40pef
<br />SHOP DRAWING REVIEW:
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />OF THE CONTRACT DOCUMENTS ONLY, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />WRITING BY THE ARCHITECT.
<br />FOUNDATIM SITE PREPARATION:
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 PSI, FOOTING
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM DAS57. TREAT ALL
<br />SOIL FOR TERMITE PROTECTION.
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33 MAXIMUM AGGREGATE SIZE WALL BE 3W..
<br />PROWDE 6%AIR ENTIED CONCRETE EXPOSED TO EARTH OR WEATHER WOOD.
<br />RN
<br />NON-BEARING WOOD WALLS TOP PLATES &STUDS CAN BE SPF.
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3W.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />PROVIDE 6-ML CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABSDN-GROUND 04M INDICATED ON
<br />CRIPPLERS,SILLS,ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. Fb. 1100 PSI AND A MODULUS OF
<br />ELASTICITY. 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />DRAWINGS SEAMS LAPPED 6INCHES AND SEALED WITH ADHESIVE TAPE.
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />FORM -WORK:
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />FORMWORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347,
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK.
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FBCR 2017, 6th EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYP #2.
<br />WELDED WIRE MESH:
<br />WELDED WIRE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI
<br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES, WIRE MESH FOR SLABS SHALL BE
<br />SUPPORTED WITH 2' CHAIRS SPACED T-0' OC, EACH WAY.
<br />REINFORCING STEEL:
<br />REBAR SHALL BE ASTM ASIS GRADE 40 IN CONCRETE DEFORMED BARS REBAR SHALL BE ASTM A615
<br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE
<br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />AND VERTICAL BARS SHALL LAP 8 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT 70 ENGINEER'S
<br />REVIEW.
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 26' #6 BAR - 36'
<br />#6 BAR - 30' #7 BAR - 42'
<br />PROVIDE 36' x 3C CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR. SEE DETAILS
<br />FOR ADDITIONAL INFORMATION.
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />WALL.
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />MASONRY:
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />'SPECIFICATION MASONRY STRUCTURES' (ACI 530/ ASCE SITMS 402, BUILDING CODE REQUIREMENTS FOR
<br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS
<br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />MANUFACTURED IN CONFORMANCE WITH ASTM "0, GRADE I'm . 1600 PSI. BLOCK SHALL BE PLACED USING
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />ASTM C 476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8'
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF S"TO 10'. USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />TYPE'M' OR'S' MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT, MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />SHALL BE 3/8' THICK UNLESS OTHERWISE NOTED, REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />CELLS TO BE FILLED.
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />REINFORCING.
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O.
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT, WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />STRUCTURAL STEEL:
<br />BE MADE BYTHE GE0.TECH. ENGINEER.
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />CONCRETE:
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS A3 FOLLOWS:
<br />9TH EDITION, BY THE AMERICAN INSTRUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36, Fy .36 k8i FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A-500, GRADE B,
<br />Fy . 46 Mi. STRUCTURAL PIPE SHALL BE ASTM53, GRADE B, TYPE E OR S. Fy = 35 kd. TUBE AND PIPE
<br />2,600 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO
<br />OTHER BOLTS BE S WITH THE TURNED ELEMENT. BOLTS SHALL
<br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5'N- PRIOR TO THE ADDITION OF PLASTICIZER
<br />INACCORDLL
<br />BE TIGHTENED IN ACCORDANCE WITH THE TURNAFF•THE-NUT METHOD.
<br />NCE WITH THE
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C-94 OR MEASURING, MXING, TRANSPORTING, ETC. ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL,
<br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOA'ED FROM WHEN WATER IS
<br />ADDED TO THE MX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MNUTES. IF FOR ANY REASON THERE IS A
<br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE
<br />RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY NON
<br />COKWUANCE VATH THE ABOVE
<br />REQUIRED CONCRETE COVERAGE OVER REaAR SHALL BE AS FOLLOWS:
<br />A TFDR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS):
<br />B. FOR CONCRETE EXPOSED TO EARTH ANDIOR WEATHER
<br />1-1lT FOR 05 AND SMALLER
<br />2" FOR 08 AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />3/4" FOR SLABS, WALLS AND JOISTS
<br />17Vt FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />WOOD TRUSSES:
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE "NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS" BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.03 6" AND BE MANUFACTURED FROM STEEL
<br />MEETING THE REQUIREMENTS OF ASTM A448, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED.
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14,'DESIGN NATIONAL -
<br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND TPIAVTCA BCSI V
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />WOOD TRUSSES.
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A68.1-1982.
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />DETERMINATIONS, FEASIBILITY 8 ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LAYOUT, SPANS & ALLTRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO7HE
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />LICENSED PROFESSIONAL ENGINEER.
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT
<br />AND CLADDING WIND LOAD PRESSURES, THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />—.AT-
<br />9RE
<br />TYPE
<br />SPACING
<br />RE -NAG
<br />APPLICATION
<br />TYPE
<br />BPACNG
<br />RENMRK9
<br />#PTFURE-T.
<br />'MA9CNRY/COAC.
<br />CASE IMRDENEDCOA
<br />NAILI tIY LONG.
<br />S'OR;
<br />GARAGEDOOR&ICK
<br />To MA90NRTA ,
<br />IN•OIA.
<br />NO WARNER
<br />TAPCON MASONRY
<br />FASTENER
<br />SD,C
<br />BED-ENODST.,
<br />—EDGE DST,
<br />S
<br />CASE ELEDG
<br />IOTENED
<br />I
<br />DI9i.
<br />1.K,S SEE
<br />NAILInONG.
<br />STAGO RED
<br />I—NA9���
<br />To MxCK
<br />WAS—
<br />EKPAN910NSOLT
<br />TEGE DIS
<br />WINDOWBUCK
<br />GAME—ENEDCOIL
<br />c•oro
<br />WlNoow4xwwFASTENED
<br />METALST—T.
<br />CONTACT THIS ENGINEER FOR SPACING
<br />1. Pi, SEE NOTES
<br />NAIL I/2'LONG,
<br />9TAGGEREO
<br />INTOMASON—ONO.
<br />MABONBY/CONC
<br />REQUIREMENTS
<br />E%r. SWWGDOOR
<br />121 YtB'DM.
<br />'TAPCON'
<br />OD
<br />rz'EMBED, SEND.
<br />—SEARINGWOOD
<br />Il2'° E%PANSDN .'EMBED. 4-END
<br />DUCK 2. PT. SEE NOTE S
<br />NOWASHER
<br />FASTNER
<br />IS
<br />fIM'EDGE DST.
<br />WALL TO Do. SLAB
<br />W/WASHER BOLT � 019T., S' EDGE DST.
<br />2r PT WINDOW BUCK 38°PAF r21rS' B'OC A' ENO, DIST., I tYY
<br />PT TO STEEL COL.,SEE S'IWi WASHER STAGGERED EDGE DIST.
<br />NOTES
<br />NoTES
<br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND/ OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />e. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NAILED AND
<br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE.
<br />1441 N. RONALD REAGAN BLVD.
<br />LONGWOOD,FL32750
<br />PH: 407-774-6078
<br />FAX: 407-7744078
<br />www.abdesigngroup.com
<br />AA #: 0003326
<br />y
<br />Y
<br />JI
<br />8
<br />r
<br />a
<br />F4
<br />4
<br />a
<br />a
<br />mm
<br />eUDDIV. & LOT
<br />ABBOTT PARK
<br />LOT #18
<br />BLK #15
<br />P1iOJECT#/
<br />04181.000-18151
<br />MODEL:
<br />4EBB
<br />"1828-CALM"
<br />GARAGE BWMWG:
<br />LEFT
<br />PAGE:
<br />DETAILS
<br />160 MPH EXR C
<br />04
<br />aw� 09/01/20
<br />SCALE: 1/4"=1'-0"
<br />sl.Ms N1
<br />00