Laserfiche WebLink
q <br />xL' A HI <br />- <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-16 <br />ZONE 1 = 52.70 PELF (62.70) <br />ZONE 3 = 60.50 PSF (70.50) <br />ZONE 2e = 60.50 PSF (70.50) <br />ZONE 3e = 69.80 PSF (79.80) <br />ZONE 2n = Sim PSF (79.80) <br />ZONE 3r = 83.80 PSF (93.80) <br />ZONE 2r = 69.80 PSF (79.80) <br />"A"- 4'-O" ENO ZONE DISTANCE <br />BASIC VIAND SPEED: 160 MPH <br />EXPOSURE CATEGORY: "C" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT: +/- 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/3Z' STRUCTURAL SHEATHING <br />EXP 1 (40120). FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN. <br />19132" STRUCTURAL SHEATHING EXP 1 (40/20).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN <br />NAILS Ld 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF <br />GABLE END, <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />SIZE <br />HEAD <br />LENGTH <br />DIA. <br />TENSILE STIR. <br />SHANK <br />ASTM <br />10d <br />RING SHANK, <br />21/2' <br />0.131 <br />F1667 <br />SORE ANK <br />170,000 <br />RING <br />(16-20 RINGS <br />RSRS-03 <br />8d <br />RING SHANK <br />2318" <br />0.113 <br />71667 <br />SCREW SHANK <br />PER INCH) <br />RSRS -01 <br />RSRS <br />8d <br />RING SHANK, <br />PNEUMATIC <br />23/S' <br />0,113 <br />F1667 <br />SCREW -NAILS <br />RSRS-01 <br />EXTERIOR SHEATHING <br />USE 1/Z' COX OR 7/16" O.S.B. PLY WITH 6d RING SHANK GUN NAILS AT 4" <br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 6" O.C. AT <br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />ZONE 1: 10d NAILS 0 4" O.C. ON EDGE AND G' O.C. IN FIELD <br />ZONE 2e, 2n, 2T. 10d NAILS G 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />ZONE 3,3e, 3r: 10d NAILS @ 4" O.C. ON EDGE AND C O.C. IN FIELD <br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />8d RING SHANK GUN NAILS N 4" O.C. <br />TOP & BOTTOM EDGES ®) <br />a <br />zw <br />Z LL�0 <br />�w <br />=U <br />m O <br />ZO <br />D: <br />8 <br />1 <br />ROOF 7tN HEAVK I USS <br />ROOF STHING <br />U BUILDING LENGTH, <br />r <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />NOTE: GABLES -DROP GABLE END & (1) ADO-L DROPPED <br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING 0 <br />1S"O.C. IF NO DROPPED GABLE END, ATTACH 20 #2 SYP <br />BLOCKING 0 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />tOd RING SHANK GUN NAILS <br />SEE "ROOF SHEATHING ATTACHMENT' <br />TABLE FOR FIELD SPACING <br />�#B 2" DECK SCREWS ® 6"4" O.C. MAX 0 <br />EDGES & 12" O.C. MAX IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 7th EDITION <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, TMS 402/W2-16 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2010, ASCE 7-16 AND AISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33C33M. <br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3W. <br />PROVIDE 64A CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS -ON -GROUND WHERE INDICATED ON <br />DRAWINGS. SEAMS LAPPED 61NCHES AND SEALED WITH ADHESIVE TAPE. <br />FORM -WORK: <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />EDITION,°RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />WOOD: <br />NOWSEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF, <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />PRESSURE TREATED, PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDING <br />PROVIDE SOLID 84OCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WDOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH' <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />WELDED WIRE MESH, SHALL BE ASTM AIOS4/AIO64M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE <br />WOOD TRUSSES: <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />BE SUPPORTED WITH 2' CHAIRS SPACED T-O-OC, EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS" BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SHALL BE ASTM A81SA615M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />MEETING THE REQUIREMENTS OF ASTM A44S/A446M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />DESIGN LOADS: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION%AND "SCSI LATEST EDITION" <br />ROOF' LIVE LOAD FLOOR: LIVE LOAD 40 psf <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />-nonc <br />20 pet TOP CHORDo-Tem <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" A6 BAR - 36" <br />WOOD TRUSSES. <br />10 pd BTM CHORD+wrHooncurrent <br />#5 BAR - 3T #7 BAR - 42" <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 38' x 36" CORNER BARS BOND BEAM ONLY LAPPED AND TIED TO EACH BEAM REBAR SEE DETAILS <br />LOCATIONS WITH GUSSETS, CRICKETS O VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS Of HIGHER OR LOWER OOF9IN ACCORDANCE WITH ANSI/ASCE 7 BB: 1990. <br />R <br />p TOP CHORD PIT CHORD <br />f ASPHALT BRINDLES) w/ GYPCRETE) <br />(7 pd <br />(7 (1 <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />10 S 5 p f ST C <br />BTM CHORD 5 pBf BTM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />AD <br />DEAD LOAD TO RESIST WIND UPLIFT: 10pBf <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 p9f <br />WALL. <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 Psf <br />WIND: DEAD LOAD SPEED=160 3 SECOND GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />(ASCE (FBC XP <br />EXPOSURE C, RISK CATEGORY 10 <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE, TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />ATTIC <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE; 10p9f, UNINHABITABLE ATTIC WITH LIMITED <br />BIT <br />LAYOUT, SPANS & ALL TRU53/HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />STORAGE: 20p9f, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200p9f, GUARD IN -FILL COMPONENTS: 50p9f, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50p9f, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30p9f, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40PBf <br />MASONRY: <br />PLAN SHOW NG COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402. BUILDING CODE REQUIREMENTS FOR MASONRY <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />SHOP DRAWINGS WALL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER, <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE Pm = 2000 PSI. BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />AND CLADDING VAND LOAD PRESSURES, THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3l8" <br />WRITING BY THE ARCHITECT, <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF S' TO 101. USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATION/ SITE PREPARATION' <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 FOOTING <br />• <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB COMPACTED A DRY DENSITY OF AT LEAST THE <br />SMALL BE THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />YSHALL, D <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL <br />MAXIMUM A 7. THE <br />BE <br />CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GE0.TECHNICAL ENGINEER TO VERIFY <br />REINFORCING. <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />STRUCTURAL STEEL: <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />CONCRETE: <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM A36/A36M FY = 38 k4i FOR ANGLES PLATES AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A500/A500M GRADE B. F = 48 STRUCTURAL PIPE SHALL BE ASTM A53IA53M GRADE B TYPE E OR S F = <br />Y Y <br />2,500 P31 REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />35 kel. TUBE AND PIPE COLUMNS SMALL BE CONCRETE -FILLED IN THE &HOP. <br />S <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SUB. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />OTHER BOLTS SHALL BE ASTM F3125IF3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED F4- PRIOR TO THE ADDITION OF PLASTICIZER <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94C94M OR MEASURING, MIXING, TRANSPORTING, <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL.J-BOLTS ARE TO BE STEEL. <br />ETC. CONCRETE TICKETS SHALL BE TIMESTAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSMON SHALL NOT EXCEED 90 MINUTES, IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />BE THE RESPONSIBIUTY OF THE TESTING LABORATORY TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE DDNTRACTOROF ANY <br />NON COMPUANCE WTH THE ABOVE <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A 3'FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH(FOUNDATIONS): <br />S. FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER <br />1-1/2* FOR 45AND SMALLER <br />Y FOR NO AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3/4' FOR SLABS, WALLS AND JOISTS <br />1-1Q' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />FASTENER SCHEDULE <br />WINDOW AND <br />DO R BUCK <br />FASTENERS <br />FASTENER <br />APPLI- <br />SDE <br />TYPE <br />9PACIw <br />REMARKS <br />APPLIUTON <br />912E <br />TYPE <br />.-No <br />RE . <br />v2PTFURRIw TO <br />1M0.�NRY/GONG. <br />CA.-L <br />G.-RNNL11?LONG. <br />B„ <br />OAMDEDOORSNdt <br />TOM IAYM C. <br />I _ <br />No- <br />TAPtIJNMOHCNRY <br />9OK; <br />11?EMBED.,4`END qST., <br />I I-- <br />SGDALEXTDC­CABS <br />HARDENED CqL <br />9`qC <br />YANDOWIDOORI FASTENED <br />OARAOEDOORSIKN <br />YS DIA OR <br />1R'dA <br />E%PANSION BOLT <br />18'gC(3B'DIN <br />4"EMBED., 4"ENO IT., <br />ix PT, SEE NOTES <br />NMLI LIT LCw. <br />STAGGERED <br />INTO MPSONRY,LONC, <br />roMA80NRY,WNC. <br />w WA6 ER <br />24"qC (1?dA) <br />3"EDDE d9T. <br />vnwowwx:K <br />cA9E HMDENEDWIL <br />9-oc <br />vnNoovd000wFASTEHm <br />MENU STRArro <br />CONTACT THIS ENGINEER FOR SPACING <br />1v PT,SEENOTE1 <br />NML11?Low. <br />STAGGERED <br />INTOMA9gMYA:ONC. <br />_YIWNC. <br />REQUIREMENTS <br />MA <br />EKT. SN1w DOOR <br />(2)11B91A. <br />RAPCON° <br />19'0� <br />11/2'EMBED, B"END <br />NON-BFARIw W'OW <br />1/T° E%PAN91- 4"EMBED. 4"E <br />24 qC <br />SUCK 2x T, SEE wrEB <br />OWASHER <br />FA9TNER <br />dST.,11?'-I EDT. <br />WALL TO CONC.9LPB <br />.1 WASHER BOLT DIET., 3"FDOEgST. <br />X PT MAwOW BIN>< 3B•PAFv21R" 6"OG 4'-deT.,11? <br />P OSTEEL COL., SIFE 01YN WASHER 8TAGGERED EDGE pST <br />NOTES <br />1N STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. Vv1NDDW AND DOOR BUCKS SHALL BE AS WIDE OR WADER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1. MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W TAPCGNS OR PAP TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL32750 <br />PH: 407-774-6078 <br />FAX 407-7744078 <br />www.abdosigngroup.com <br />L AA #: 0003325 <br />F <br />C <br />-RD <br />O <br />ausDm at TAT <br />ABBOTT PARK <br />LOT #5 <br />BLK. #9 <br />PROJECT* <br />04181.000-05091 <br />MODZU <br />4EBB <br />"1828-CALI12 <br />GARAGZ 87WNG: <br />LEFT <br />PAGM: <br />DETAILS <br />160 MPH E " C <br />( M7 <br />Dmpm <br />ATZ: 5/05/21 <br />aCALS: 1/4"=1r-0" <br />aHL'RT <br />S N1 <br />