<br />ROOF WIND DESIGN PRESSURES
<br />NET (GROSS) ASCE 7-16
<br />ZONE 1 = 52.70 PSF (62.70)
<br />ZONE 3 = 60.50 PSF (70.50)
<br />ZONE 2e = 60.50 PSF (70.50)
<br />ZONE 3e = 69.80 PSF (79.80)
<br />ZONE 2n = 69.80 PSF (79.80)
<br />ZONE 3r = 83.80 PSF (93.80)
<br />ZONE 2r = 69.80 PSF (79.80)
<br />"A"= 4'-0" END ZONE DISTANCE
<br />BASIC WIND SPEED: 160 MPH
<br />EXPOSURE CATEGORY: "C"
<br />RISK CATAGORY: 0
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT:-/-0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/32" STRUCTURAL SHEATHING
<br />EXP 1 (40120). FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN.
<br />19/32" STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD
<br />AND EDGE SPACING) SEE DETAIL
<br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SWANK GUN
<br />NAILS 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W IN 4' OF
<br />GABLE END.
<br />ROOF/ WALL/ FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />SIZE
<br />HEAD
<br />LENGTH
<br />CIA
<br />TENSILE STR.
<br />SHANK
<br />ASTM
<br />10d
<br />RING SHANK
<br />2 12"
<br />0.131
<br />F1867
<br />SCREW K
<br />170,000
<br />NG
<br />((1116--20 RINGS
<br />RSRS-03
<br />Ed
<br />RING SHANK
<br />2 3/8"
<br />OA 13
<br />F1667
<br />SCREW SHANK
<br />PER INCH)
<br />RSRS-01
<br />8d
<br />RING SWANK
<br />PNEUMATIC
<br />231T
<br />OA13
<br />SCREW -NAILS
<br />RSRS-01
<br />RSRS
<br />EXTERIOR SHEATHING
<br />USE 112" COX OR 7/16" O.S.B. PLY WITH Ed RING SHANK GUN NAILS AT4"
<br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS V O.C. TOP &
<br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 5' O.C. AT
<br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL
<br />ZONE 1: 10d NAILS @ 4" O.C. ON EDGE AND 6' O.C. IN FIELD
<br />ZONE 2e, 2n, 2r: 10d NAILS Q 4" O.C. ON EDGE AND I O.C. IN FIELD
<br />ZONE 3,3e, 3r: tOd NAILS 4' O.C. ON EDGE AND 4" O.C. IN FIELD
<br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED
<br />AND ADHERES TO ASCE 7-16
<br />WRING SHANK GUN NAILS BMOC.
<br />T-4D 0M EDGES
<br />i�
<br />y0
<br />TYP. EXT. SHEATHING ATTACHMENT
<br />KAt IRK VK IKUJ'J
<br />ROOF SHEATHING
<br />0 0
<br />� 3
<br />m
<br />BUILDING LENGTH L
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />NOT ' GABLES -DROP GABLE END & (1)ADUL DROPPED
<br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W BLOCKING
<br />18"O.C. IF NO DROPPED GABLE END, ATTACH 214 #2 SYP
<br />BLOCKING @ 16" O.C. FIRST 4 BAYS W (2)12d NAILS EA
<br />END. ATTACH ROOF SHEATHING TO RAFTERS 21
<br />BLOCKING PER NAILING SCHEDULE
<br />lGd RING SHANK GUN NAILS
<br />SEE "ROOF SHEATHIINGATTACHMENT"
<br />TABLE FOR FIELD SPACING \
<br />C#8 2" DECK SCREWS O 6'-B" D.C. MAX
<br />EDGES & 12" O.C. MAX IN FIELD. UNTHREADED
<br />SHANK TO EXTEND BEYOND THICKNESS OF
<br />SUB -FLOOR SHEATHING
<br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />ARC7-AifCTIlS2Ai SYRAW4NGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAW NGS. APPUCABLE BUILDING CODE STANDARDS: FBCR 2020, 7th EDITION
<br />AG 31844, BUILDING CODE REQUIREMENTS
<br />FOR STRUCTURAL CONCRETE, TMS 402(602-16 AISI SPECIFICATION FOR THE DESIGN OF
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />EXCEPT MERE A DIFFERENT DETAIL IS SHOWN.
<br />ALL AGGREGATE USED IN CONCRETE SHALL OOWORM TO ASTM C131C33M. MAXIMUM AGGREGATE SIZE SHNL BE 31T.
<br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR MATHER
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3W
<br />PROVIDE 64AL CONTINUOUS POLYETHYLENE VAPOR BMRIER MEMBRANE UDBRALL SIPBSON43RDIM WHEW INDICATED ON
<br />DRAWINGS. SEAMS LAPPED 6INCHES AND SEALED WITHADFIEBffTAPE
<br />FORM -WORK
<br />FORWAORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WTHAG 347 LATEST
<br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM4AORK.
<br />WOOD:
<br />NON -BEARING WOOD HALLS TOP PLATES & STUDS CAN BE SPF.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER Po = 1100 PSI AND A MODULUS OF
<br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0,42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SKALL BE BROUGHT
<br />EXI USIONS' FROM THESE PLANS:
<br />MINIMUM NAILING PER FBCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />WATERPROOFING, FLASHING, SOUND ISOLATION FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />OF THE WORK.
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTUMRALDEPENDIND
<br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH Zx STRUCTURAL LUMBER
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUL)ING
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUTARE BY OTHERS.
<br />SYP M12.
<br />IS COMPLETE. IT IS THE CONTRACTORS RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />WISIDED WIRE MESH'
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRAG NAG, GUYS OR TIE-DOWRLS.
<br />WELDED WRE MESH, SHALL BE ASTM A10641A1064M, GRADE 85 AND BE PLACED IN ACCORDANCE WTH THE
<br />TH S'
<br />AG TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WRE MESH FOR SLABS SHALL
<br />BE SUPPORTED W TH 2' CFW RS SPACED 3'-0° OC, EACH WAY.
<br />TOE DESIGNEDANDFABRICATEDINACCORDANCE WTHFOR
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />NSISH SHALL ANID
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS'BY THE NFPA. TRUSS DEBITED SHALL BE SI NEDA
<br />PA. TRUSS DESINALGNS
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRICTION LOADS.
<br />O DRAV%A
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWNGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />REINFORCING STEH:
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />REBAR SHALL BE ASTM A615A615M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615
<br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED.
<br />GRACE 80 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE
<br />DESIGN LOADS:
<br />W/THE PICA. ENDING AGRAM AND PLACING DETAILS OF THE AG STANDARDS AND SPECIFICATIONS.
<br />TYPICAL B DI
<br />DESIGN FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH ,"DESIGN NATIONAL
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />STANDARDS FOR METAL-PLATECONNECTED-VWOOD TRUSS CONSTRUCTION:,N:, AND 'SCSI LATEST EDITION'
<br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD UPS ARE SUBJECT TO ENGINEER'S
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METALFLATECONdECTED
<br />ROOF: LIVE LOAD FLOOR LIVE LOAD 40 PST
<br />REVIEW
<br />WOOD TRUSSES.
<br />20 psf TOP CHORD nanconwrren[
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36'
<br />10 psf BTM CHORD alDncanwrTent
<br />#5 BAR - 30" #7 BAR - 47'
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />DEAD LOAD DEAD LOAD
<br />PROVIDE 36°x 36"CORNER BARS, BOND BEAM ONLY, LAPPEDAND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />FOR ADDITIONAL INFORMATION.
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WTH ANSIASCE 7 88: 1990
<br />15 pd TOP CHORD
<br />20 psf TOP CHORD
<br />.
<br />(7 pd 4 ASPHALT SHNGLES)
<br />(10 PST 4No GYPCRETE)
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />10 psf BTM CHORD
<br />5 pst BTM CHORD
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />DEAD LOAD TO RESIST W NO UPLIFT: 1 OpEf
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAW NGS FOR ALTERNATE CONNECTION DETAILS AT
<br />BALCONY LIVE LOAD 60 PST
<br />WALL.
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />STAIRS LIVE LOAD 40 PST
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS DOWEL
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR SEARING
<br />WNO DEAD LOAD SPEED-160 MPH 3-SECONOGUST
<br />(ASCE 7-16 (FBC R2020) EXPOSURE C, RISK CATEGORY 11)
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10psf, UNINHABITABLE ATTIC WTH LIMITED
<br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR)
<br />AND DECKS: 40pet, GUARDS AND HANDRAILS: 200pst, GUARD INFILL COMPONENTS: 50psf, PASSENGER
<br />VEHCLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS:
<br />40pst
<br />SHOP DRAWING REVIEW:
<br />SHOP DRAWNGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WTH THE DESIGNING INTENT
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />COMPLIANCE WTH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHTECT
<br />DRAWINGS SUBMITTED WITHOUT REVIEW DULL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPUGES WHEREVER POSSIBLE.
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />MASONRY -
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY
<br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBUSHED BY
<br />THE MASONRY STANDARDS JOINT COMMITTEE.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />MANUFACTURED IN CONFORMANCE WTH ASTM C410, GRADE fm = 2000 PSI. BLOCK SHALL BE PLACED USING
<br />RUNNING BOND UNLESS OTHERW SE NOTED, LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WTH
<br />WTHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />ASTM C476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 26 DAYS, UNLESS
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SKILL HAVE A MAXIMUM 3/8"
<br />WRITING BY THE ARCHITECT.
<br />COURSE AGGREGATE, AND SHALL BE PLACED W A SLUMP OF 8' TO 10". USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />FOUNDATIOW SITE PREPARATION:
<br />TYPE W' OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF ZOOO Psf, FOOTING
<br />PROPORTIONED AND MIXED AS OUTU NEE) UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE
<br />SHALL BE 3/8' THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WTH ASTM D-1557. TREAT ALL
<br />CELLS TO BE FILLED.
<br />SOIL FOR TERMITE PROTECTION.
<br />FILL CMU CELLS SOLID WTH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS ANCHOR VERTICAL
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />REINFORCING.
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTEDAT THE
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT WRITTEN CERTIFICATION THAT THE
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O.
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />STRUCTVRAL STEE:
<br />BE MADE BY THE GEO-TECH ENGINEER.
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WTH THE
<br />CONCRETE"
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />A36/A36M, Fy = 36 kv FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM
<br />A500/A500M, GRADE S. Py = 46 W. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S, Fy =
<br />21500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB-0NORADE
<br />35Imi. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SFDP.
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE-NUF LEVELING. ALL
<br />CONTRACTOR %KLSUBMIT PROPOSED MX DESIGNS, NTH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIORTO
<br />OTHER BOLTS SHALL BE ASTM F3125IF3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS
<br />CONCRETE PLACEMENT. CONCRETE BLIMP SHALL NOT IXCEE)5"d- PRIOR TO THE ADDITION OF PLASTICIZER
<br />SHALL BE TIGHTENED IN ACCORDANCE WTH THE TURNOFF-THENUT METHOD.
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI MS AND ASTM C94/C94M OR MEASURING, MANG, TRANSPORTING,
<br />ETC. CONCRETE TICKETS SHALL BE TIMESTAMPM WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN
<br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES IF FORANY REASON
<br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MNUTES THE CONCRETE SHALL NOT BE PLACED. IT SILL
<br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE GAINERS REPRESENTATIVE AND THE CONTRACTOR OF ANY
<br />NON COMPLIANCE WTH THE ABOVE
<br />RED RED CONCRETE COVERAGE OVER RMARSALL BEASFOLLOAB:
<br />A 3FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH IFOUDATION4
<br />S FOR CONCRETE EXPOSED TO EARTH A DPORWEATHER
<br />1-117FGR 05 ANDSMNLBR
<br />2° FOR #6 AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />31C FOR SLABS WALLS AND JOISTS
<br />1-12' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL.
<br />DETERMINATIONS, FEASIBIUTY & ARCHTECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />PROVIDE ENGINEERED SHOP DRAWNGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWNGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />LICENSED PROFESSIONAL ENGINEER
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDEDTO FACILITATE THE
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THS PLAN SHALL SUPERCEDE THOSE
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ONASCE 7-16 COMPONENT
<br />AND CLADDING W ND LOAD PRESSURES. S URES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />ALL TRUSS TO TRUSS CONNECTIONS
<br />FASTENERSCHEDULE
<br />WINDOW AND
<br />DOOR BUCK FASTENERS
<br />FASTENER
<br />APhICATgV
<br />SIZE
<br />SPACING
<br />REMARKS
<br />AWUCgTON
<br />512E
<br />SPACING
<br />REMARKS
<br />I,Q PTR1p2NG TO
<br />MA9WRY/CCNG
<br />CASE HAROB4EDCgL
<br />L
<br />eOF
<br />ARAGE WOR dMJ(
<br />FASTENER
<br />8 PC
<br />ABED. /2'®4•ENOOU
<br />C ST.
<br />.DPN..EM ODORS
<br />CASE HArmFN®COk
<br />8'O,C
<br />WINpDN60DORlF ENEO
<br />DO 9K1t
<br />3,B"PANT
<br />E%PANStONBJtT
<br />t2-(YS"DUy
<br />4- EMBED.. 4'HL
<br />NDTEB
<br />—ONG.
<br />SERED
<br />TAGG
<br />T
<br />�
<br />4'O� H 0✓4
<br />3'EDGE GISr.
<br />CASE PARDBL''-
<br />wwoR/FASrEN®
<br />M AL STRraro
<br />CONTACT THIS ENGINEER FOR SPACING
<br />P"T,SEEN6
<br />NNLIWrL—ONG
<br />EaEo
<br />° o R" °"
<br />REQUIREMENTS
<br />sPT. DGaR 111 •TAFoxr +In^EMBE0.6•ElD.
<br />BUCK 2a PT SEENOTE6 FASTNBt DST.11r2'EL'GECIST.
<br />�xo—DID " p.t 38'P 2— 8'GC 1-END. DUST., I N7
<br />STEEL — SEE
<br />OTEB 9iAGGBREDEDGE DISr.
<br />NTEB
<br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND/OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />& W NDOW AND OR BUCKS SHALL BE AS WIDE OR W DER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1. MEMBERS ARE NAILEDAND
<br />2x MEMBERS ARE SECURED W/TAPCONS OR PAF TO THE SUBSTRATE.
<br />1 N. RONALD REAGAN BLVD.
<br />LONGWOOD, FL32750
<br />PH: 407-7746078
<br />FAX: 407-774-4078
<br />w A W.abdeskM*up.com
<br />AA #: 0003325 -A
<br />p
<br />�
<br />C
<br />d
<br />WE
<br />v
<br />oulmly ae LOTs
<br />ABBOTT PARK
<br />LOT #19
<br />BLK #8
<br />PHASE #2A
<br />PllOJECT#
<br />04181.000-19082
<br />MODEL'
<br />4EBB
<br />"1828—CALI11
<br />GAGE SWMWG:
<br />RIGHT
<br />PAGE:
<br />DETAILS
<br />160 MPH EXP. C
<br />D TM 12/07/21
<br />sCALE: 1/4"=1'-0"
<br />sHm=
<br />SN1