aAaE-TENS <br />I I <br />s <br />ROOF WIND DESIGN <br />PRESSURES <br />NET (GROSS) ASCE7-16 <br />ZONE 1 = 52.70 PSF (62.70) <br />ZONE 3 = 60.50 PSF (70.50) <br />ZONE 2e = 60.50 PSF (70.50) <br />ZONE 3e = 69.80 PSF (79.80) <br />ZONE 2n = 69.80 PSF (79.80) <br />ZONE 3r = 83.80 PSF (93.80) <br />ZONE 2r = SEIM PSF (79.80) <br />"A"= 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />EXPOSURE CATEGORY:"C" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT: -1- 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/J2" STRUCTURAL SHEATHING <br />EXP 1 (40120), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN. <br />19,37' STRUCTURAL SHEATHING EXP 1 (40/20).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE IOd RING SHANK GUN <br />NAILS 0 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF <br />GABLE END. <br />ROOF/ WALU FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />SIZE <br />HEAD <br />LENGTH <br />DIAL <br />TENSILE STR. <br />SHANK <br />ASTM <br />10d <br />RING SHANK, <br />2 1/2' <br />0.131 <br />F1667 <br />S E SHANK <br />170,000 <br />RING <br />(16-20 RINGS <br />RSRS-03 <br />8d <br />RING SHANK, <br />23/6' <br />0,113 <br />F7667 <br />SCREW SHANK <br />PER INCH) <br />RSRS-01 <br />Ed <br />RING SHANK <br />PNEUMATIC <br />23/9' <br />0.113 <br />F1667 <br />SCREW -NAILS <br />RSRS-01 <br />EXTERIOR SHEATHING <br />USE 1/7' COX OR 7116" O.S.B. PLY W ITH SO RING SHANK GUN NAILS AT 4" <br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 6" O.C. AT <br />INTERMEDIATE SUPPORTS OR 7/16' ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL <br />ZONE 1: 1GO NAILS 0 4" O.C. ON EDGE AND 6" O.C. IN FIELD <br />ZONE 2e, 2n, 2r 1Od NAILS 0 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />ZONE 3,3e, 3r IOd NAILS 0 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />8d RING SHANK GUN NAILS 0 4" O.C. <br />.- TOP & BOTTOM EDGES .- a <br />li - <br />ROOF SHEATHING , <br />I <br />I <br />.Mir.rl W.U. <br />U BUILDING LENGTH <br />r <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />NOTE: GABLES -DROP GABLE END & (1) ADD'L DROPPED <br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING 0 <br />'SO <br />S O.C. IF NO DROPPED GABLE END, ATTACH 2.4 #2 SYP <br />BLOCKING 0 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA. <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />rn <br />zW <br />Z c7 <br />O w <br />tOd RING SHANK GUN NAILS <br />z D <br />SEE "ROOF SHEATHING ATTACHMENT' <br />= ti <br />�O <br />TABLE FOR FIELD SPACING , <br />Z 'a <br />0' <br />8 <br />33°w <br />L <br />w <br />#8 7' DECK SCREWS 06-8. O.C. MAXO <br />EDGES & 17' O.C. MAX IN FIELD. UNTHREADED <br />Y <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />p00 <br />SUB -FLOOR SHEATHING <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />TYP. EXT. SHEATHING ATTACHMENT <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS, APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 7th EDITION <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, TMS 4021602-16 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2018, ASCE 7-16 AND RISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />OF THE WORK. <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C331033M. MAXIMUM AGGREGATE SIZE SHALL BE NW. <br />BY OT ERS <br />WWD. <br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH ORMATHER <br />NON -BEARING WOOD WALLS TOP PLATES 8 STUDS CAN BE SPF. <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CKAMFERED3I4'. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />PROVIDE 64AL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABSOMMUND MERE INDICATED ON <br />CRIPPLERS, SILLS,ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. Fb= 1100 PSI AND A MODULUS OF <br />DRAWINGS. SEAMS LAPPED B INCHES AND SEALED WITH ADHESIVE TAPE. <br />ELASTICITY = 1,400,D00 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />DISODIUM <br />TION LWOOD <br />ROBORATEL BEDTETTRAHE NDRAL TREAT <br />FORMWORK: <br />CO (DOT). FOR STRUCTURAL USE THAT SHALL BE ED FOR ANY <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />WI DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITIOWRECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FSCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL. DEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE SYP 02, <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />H , <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH: <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />WELDED WIRE MESH, SHALL BE ASTM A106UA1084M, GRADE 85 AND BE PLACED IN ACCORDANCE WITH THE <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />WOOL) TRUSSES: <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />BE SUPPORTED WITH 2' CHAIRS SPACED T-O' OC, EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE 'NATIONAL DESIGN SPECIFICATIONS FOR <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. HE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SHALL BE ASTM A815A815M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />GRADE 601N MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />DESIGN LOADS: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "BOB] LATEST EDITION' <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psl <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />20 pW TOP CHORD -npn-cpncurrent <br />REVIEW. <br />TYP. MIN LAPS SHALL BE A5 FOLLOWS: #4 BAR - 25" p8 BAR - 38" <br />WOOD TRUSSES. <br />10 psi BTM CHORD-nonooncurrent <br />#5 BAR 30' #7 BAR - 42" <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36' x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSUASCE 7 88: 1990, <br />15 pef TOP CHORD 20 psf TOP CHORD <br />(7 paf W ASPHALT SHINGLES) (10 PST W/ ND GYPCRETE) <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />10 psf BTM CHORD 5 pSf BTM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: 1 Opsf <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 PST <br />WALL' <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 P f <br />WIND: DEAD LOAD SPEED MPH 3- SECOND GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />(NICE (FBC 020) EXPOSURE C, RISK CATEGORY IN <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE, <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />ATTIC <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10IT UNINHABITABLE ATTIC WITH LIMITED <br />BIT <br />LAYOUT, SPANS & ALL TRUSSI HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />STORAGE: 20pef, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50pef, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES, THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50pef, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40W <br />MASONRY: <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL BLOCK WALLS SHALL BETWO-CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fm = 2000 PSI. BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS, GROUT USED TO FILL Y <br />MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM C-478 AND SHALL PROVIDE A MINIMUM COMPRESSIVE TR GT <br />M STRENGTH H OF 3000 P51 AT 28 DAYS, UNLESS <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8' <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED WI A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATION/ SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 PSI, FOOTING <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL <br />SWILL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />SOIL FOR TERMITE PROTECTION, <br />CELLS TO BE FILLED, <br />FILL CMU CELLS SOUD WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />REINFORCING, <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL REBAR B X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />STRUCTURAL STEEL: <br />BE MADE BY THE OEO-TECH. ENGINEER. <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />CONCRETE: <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS' <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A38/A36M F - 36 kM FOR ANGLES PLATES AND - HA E . STRUCTURAL 1 <br />Y A W S P S C RAL TUBING SHALL BE ASTM <br />A500/A500M GRADER F =48NS STRUCTURAL HA ASTM - <br />� Y E S LL BE S 53/A53M, GRADE B, TYPE E OR S, Fy - <br />2,500 P31 REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />35 ka. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB <br />CONTRACTOR SHALL SUBMT PROPOSED M%DE8IGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5'4- PRIOR TO Tiff ADDITION OF PLASTICIZER <br />OTHER BOLTS SHALL BE ASTM F3125/F3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C9UC94M OR MEASURING. MANG. TRANSPORTING, <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL.J-BOLTS ARE TO BE STEEL. <br />ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROMMEN <br />WATER IS ADDED TO THE MX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MNUTES. IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED, IT SHALL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WITH THE ABOVE <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A. YFOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH IFOUNDATIONS): <br />B. FOR CONCRETE EXPOSED TO EARTH ANDAIR WEATHER <br />1.12MALL 'FORA6ANOSER <br />7' FOR 06 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3/4-FOR SLABS, WALLS AND JOISTS <br />1-12' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />FASTENER SCHEDULE <br />WIND W AND <br />DOOR BUCK <br />F STENERS <br />FASTEN R <br />APPLIGTON <br />SIZE <br />T'PE <br />BPPPNG <br />REMARKS <br />APPLI ON <br />SIZE <br />TYPE SPACING <br />REMARKS <br />Iva Pi Fl)RPolIG TO <br />MASONRY/GONG. <br />CASE HARDENED OPL <br />NNLit?LONG. <br />e•OC <br />GNNGE DOOR BICA( <br />TO MASONRYK%1E3C <br />1'— <br />NO WASHER <br />TM'CONMABOI$Y <br />FASTENER 8'Ox: <br />�/I'EMBED., <-Ela PST., <br />f12"EDGE PST. <br />ATEXT. <br />9GD L. DOO.R9 <br />CAGE HARDENED AIL <br />9"OG <br />WINDOWIDOOR/FASTENED <br />OMAGE DOOR SUP( <br />6 gA.OR <br />1H"OIC (i8'PA) <br />V-11ED., A"ENOP9T, <br />1x PT SEE NOTES <br />-11tYY'LONG. <br />STAGGER. <br />INTO MASCNRYFONC. <br />TO MASONRV/PINC. <br />dA <br />xtl WASHER <br />FIIPANSIO.I BOLT Id•OIC (IIY DIIa <br />3"EDOE DST <br />vMnoov.•awx <br />vsE NAADENEDCPL <br />a'oc <br />W�NDowmoororASTENEo <br />METAL STRAIT rG <br />CONTACT THIS ENGINEER FOR SPACING <br />1v PT. SEE NOTES <br />NP1L1 tn'LONG. <br />STAGGERED <br />INTOMA80NRY/CONC. <br />MASONRY ICONC. <br />REQUIREMENTS <br />EXi. SYHNGOOOR <br />RI IDIBOV. <br />"TPPCPY <br />1T.II E0,6"EI•U. <br />NON-EEARIN3wWD <br />/r• EXPANe1CN <'EMBED. 1•ENO <br />BIICKh Pi, BEE HOTTER <br />NO WpBHER <br />fABIiEP <br />18'OC <br />pST.,it?EDGE PST. <br />WALL TO COlL.9lAE <br />W/WASHER BOti 3A"� PST., $'EDGE PBi. <br />b Pf VlINOOWBUp( ,. .PA 3IIS" POC PEN.. PST.,I <br />PTTOSTEELCOL., SEE <br />IS, W/ ER 9TAf3GERED EOOE PST. <br />KIM <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND /OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4, PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />S. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR HE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS HE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. Ix MEMBERS ARE NAILED AND <br />2. MEMBERS ARE SECURED W TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL32750 <br />PH: 407-774-6078 <br />FAX: 407-7744078 <br />www.abdosigngroup.com <br />AA M: 0003325. J <br />It <br />aIa <br />6 <br />fA <br />umirv. a.LOT.BBOTT PARK <br />LOT#4 <br />BLK. #9 <br />0 1810 �-0409 <br />iiOD>aLC <br />4EBB <br />"1828—CALI" <br />GAIIII"M MWVMs <br />LEFT <br />PAGO <br />DETAILS <br />%160 MPH E . C <br />1 <br />DAB 5/05/21 <br />sCAXM 1/4"=1'- <br />sN1 0" <br />s>� <br />