GABLE - ETD
<br />NIPROOF
<br />ROOF WIND DESIGN PRESSURES
<br />ZONE 1 =ASCE 23.79 PSF I. S)
<br />ZONE 2 = 39.48 PSF (49.48)
<br />ZONE 3 = 67.16 PSF (77.16)
<br />'A'= 4'-O' END ZONE DISTANCE
<br />BASIC WIND SPEED: 160 MPH
<br />WIND EXPOSURE:'C'
<br />RISK CATAGORY: II
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT, 0.18
<br />ROOF DMLPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 7116"
<br />O.S.B. OR 112" COX EXT. PLYWOOD, FOR
<br />CEMENTITIOUS TILE AND METAL ROOFING, USE
<br />MIN. 518 COX EXT. PLYWOOD, WITH Bd RING
<br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED
<br />PANEL EDGES AND 8d RING SHANK GUN NAILS
<br />AT 6' O.C. AT INTERMEDIATE SUPPORTS. SEE
<br />DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE
<br />8d GUN NAILS @ 4" O.C. EDGEWISE 2x4
<br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE
<br />ENO.
<br />ROOF/ WALL/ FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />I
<br />NAIL SCHEDULE
<br />SIZE
<br />TYPE
<br />MIN. LENGTH
<br />MIN. DIA.
<br />SHANK
<br />TENSILE STIR,
<br />SHANK
<br />Sd
<br />RING SHANK,
<br />21/2"
<br />0.120"
<br />170.000
<br />RING
<br />i6-20 RINGS
<br />SCREW SHANK
<br />ER INCH)
<br />Bd
<br />SCREW SHANK
<br />21/2"
<br />0.120"
<br />PNEUMATIC
<br />SCREW -NAILS
<br />1. NAIL SIZE PER ASTM F1664
<br />2. INTERNATIONAL STAPE, NAIL & TOOL
<br />ASSOCIATION (]SANTA) ESR-1539
<br />EXTERIOR SHEATHING
<br />USE 1/2" COX OR 7/16' O.S.B. PLY WITH 8d RING
<br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES
<br />AND 8d RING SHANK GUN NAILS 4" O.C. TOP 6
<br />BOTTOM PANEL AND 8d RING SHANK GUN
<br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS
<br />OR 7/16' ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL.
<br />8d RING SHANK GUN NAILS @ 4" O.C.
<br />TOP & BOTTOM EDGES
<br />. . . . . . . . . . .
<br />w"
<br />(9)
<br />J
<br />Z N
<br />z0
<br />a W
<br />Z
<br />S U
<br />i"
<br />of
<br />Em
<br />TOP CORD BLOCKING AT 4'
<br />O.C. MAX. IN FIRST 2 FRAMING
<br />SPACES AT EACH END.
<br />RAFTER TRUSS
<br />RrX1P SHEAPATHING
<br />ROOF SHEATHING LAYOUT
<br />aAND ENDWALL BRACING
<br />GABLE EAR FRAMING
<br />C8d RING SHANK GUN NAILS
<br />0 6" O.C. IN FIELD
<br />C8d RING SHANK GUN NAILS @ 12" O.C. IN
<br />FIELD or Sd x 210 SCREW SHANK
<br />PNEUMATIC SCREW -NAILS @ 12' 0.6,.jN
<br />FIELD J}
<br />GENERAL NOTES:
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBGR 2017, 6M EDITION
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />FOR STRUCTURAL CONCRETE, ACI 530.13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />SWILL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS, FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />OF THE WORK.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORMTO ASTM C33. MAXIMIMAGGREGATE 80 SHALL BE W.
<br />PROVIDE S%WR ENO6WffD CONCRETE EXPOSED TO EARTH OR HEATHER
<br />NOW�EDARING WOOD WALLS TOP PLATES 8 STUDS CAN BE 3PF.
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CKA FERED SW.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />PROVIDE 5-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SIASS-ON-GROUND WHERE INDICATED ON
<br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. FD =1100 PSI AND A MODULUS OF
<br />DRAWINGS. SEAMS LAPPED 51NCHES AND SEALED WITH ADHESIVE TAPE.
<br />ELASTICITY = 1.400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED, WOOD FOR NONSTRUCTURAL USES
<br />SHALL BERATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />FORM -WORK:
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347,
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK.
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FBCR 2017, 6th EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2% STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYP #2.
<br />WELDED WIRE MESH:
<br />WELDED WIRE MESH, SHALL BE ASTM AT85, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI
<br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE
<br />SUPPORTED WITH 2' CHAIRS SPACED T-0- DID, EACH WAY.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR REINFORCING STEEL:
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. REBAR SHALL BE ASTM A615 GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615
<br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE
<br />DESIGN LOADS' W/ THE TYPICAL SENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS,
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 WAND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD UPS ARE SUBJECT TO ENGINEERS
<br />REVIEW.
<br />20 psf TOP CHORD -Rocca -M
<br />10 psf BTM CHORD -I oiR Ia nt TYP. MIN LAPS SHALL BE AS FOLLOWS: W BAR - 25' ife BAR - 38'
<br />DEADLOAD
<br />15 W TOP CHORD
<br />(7 psfw/ ASPHALT SHINGLES)
<br />10 p9f BTM CHORD
<br />DEAD LOAD TO RESIST WIND UPLIFT: 1 Op9f
<br />DEAD LOAD
<br />20 p9f TOP CHORD
<br />(10 PIT w/ No GYPCRETE)
<br />5 Paf BTM CHORD
<br />BALCONY LIVE LOAD 60 p9f
<br />STAIRS LIVE LOAD 40 p9f
<br />R5 BAR - 30" Y7 BAR - 42"
<br />PROVIDE 36' x 36" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />FOR ADDITIONAL INFORMATION.
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />WOOD TRUSSES:
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS* BY THE NFPA. TRUSS DESIGNS SHALL B SIGNED E AND
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL
<br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT-0IPPED GALVANIZED.
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14,'DESIGN NATIONAL
<br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION%AND "TPVWTCA SCSI 1-
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />WOOD TRUSSES.
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982.
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />WALL. TRUSSESIGIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />WIND: DEAD LOAD SPEED -160 MPH 3-SECOND GUST
<br />(ASCE 7-10 (FBC R2017) EXPOSURE C, RISK CATEGORY II)
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE,
<br />ROOF 5 FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />DETERMINATIONS, FEASIBILITY S ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10pef, UNINHABITABLE ATTIC WITH LIMITED
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING, ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FD(ED STAIRS: 30p9f, BALCONIES (EXTERIOR)
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />AND DECKS: 40pef, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50p9f, PASSENGER
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />VOEHHIICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS:
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />MASONRY:
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />LICENSED PROFESSIONAL ENGINEER.
<br />SHOP DRAWING REVIEW.
<br />'SPECIFICATION MASONRY STRUCTURES' (ACI 530/ ASCE 5?MS 402, BUILDING CODE REQUIREMENTS FOR
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE.
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL 70 THE ARCHITECT.
<br />MANUFACTURED IN CONFORMANCE WITH ASTM CIO, GRADE im = 1500 P31. BLOCK SHALL BE PLACED USING
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT
<br />AND CLADDING WIND LOAD PRESSURES, THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />PLACING CONCRETE FOR IN -WALL COLUMNS GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />ASTM C-478, AND SMALL PROVIDE A MES
<br />3000 PSI AT 28 DAYS, UNLESS F MINIMUM COMPRESSIVE STRENGTH IO
<br />MOF ES S
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED INMIX
<br />SPECIFICALLY NOTED OTHERWISE FOUNDATION PLAN. THE GROUT SHALL HAVE A MAXIMUM
<br />WRITING BY THE ARCHITECT.
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF S'TO 10'. USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />FOUNDATION/ SITE PREPARATION'
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2.000 PEI, FOOTING
<br />TYPE 'M" OR "S' MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE
<br />MALL BE 3/8' THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND IWO
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY. DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL
<br />CELLS TO BE FILLED,
<br />SOIL FOR TERMITE PROTECTION.
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />REINFORCING,
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS, LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O,
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />STRUCTURAL STEEL:
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />CONCRETE:
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />CONCRETE SHALL ACHIEVE MINIMUM 26 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36, Fy a 36 ksl FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM A500, GRADE B,
<br />Fy = 46 W. STRUCTURAL PIPE SHALL BE ASTM53, GRADE B, TYPE E OR S, Fy = 35 ksl. TUBE AND PIPE
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS. WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE M%PRNM TO
<br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL
<br />CONCRETE PLACEMENT. CONCRETE SLUM SHALL NOT EXCEED S' N- PRIM TO THE ADDITION OF PLASTICIZER
<br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI301 AND ASTM C-04 OR MEASURING, MANG. TRANSPORTING, ETC.
<br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER E
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL,
<br />ADDED TO THE MX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MNUTES. IF FOR ANY REASON THERE IS A
<br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MNUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE
<br />RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON
<br />COMPLIANCE WITH THE ABOVE,
<br />REOURED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS:
<br />A 3' FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH(FWNDATIONS):
<br />B. FOR CONCRETE EXPOSED TO EARTH ANDVR WEATHER
<br />1.1 /2" FOR A6 AM3 SMIALIER
<br />2' FOR IS AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />3/4' FOR SLABS, WALLS AND JOISTS
<br />1-1Q" FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />.—ON
<br />SUE
<br />iVPE
<br />SPACING
<br />REIMPo(9
<br />AFPLICA1pN
<br />SQE
<br />HYPE
<br />9PACXC
<br />REMAR49
<br />14 PT FURRING TO
<br />CAEEHARDENED COIL
<br />"
<br />.—GE DOOR BACK
<br />11A'pIA.
<br />TMCON MA90N1Y
<br />11?ENEE0,4"END 019T.,
<br />MA9�IRY/CONC.
<br />NAIL 11?LONG.
<br />TO MA90NRYICONC
<br />NO WIENER
<br />FASTENER
<br />11?EDGE DIST.
<br />SGD, &. EXT.
<br />CASE HARDENED COIL
<br />YO•C
<br />WMDOWIOOpL FASTENED
<br />GAMGE OOM BUCK
<br />1?DIA.WI
<br />E%PAN9K)N BOLT
<br />RI'OIC
<br />f'EMBED.. 1' ENDDI9T.,
<br />l.PT,EEENOTE9
<br />NAIL 11?LONG.
<br />STAGGERED
<br />INTO MPSONRYILdIL.
<br />TO MA90NRVIWNC.
<br />WASHER
<br />3"EDGE OWT.
<br />wNoow aua
<br />cASE NARDElED cos
<br />rac
<br />WINoowimoru FASTENED
<br />AETALBTRAPTO
<br />CONTACT THIS ENGINEER FOR SPACING
<br />'-T.—NOTE.
<br />NAIL 11?LONG.
<br />—.EKG
<br />NTO MASONRVICONL.
<br />MlWF 1CONC.
<br />REQUIREMENTS
<br />EM.SWING WOR
<br />(1)11901A
<br />TAPCON'
<br />1}
<br />11?EABE0, 9'ElD,
<br />NONBFJUUNG WOOD
<br />IZ IXPA - PEAx1ED."END
<br />IA"�
<br />BUCK h PT,EEENOTEe
<br />NO—
<br />FMTFER
<br />OIST.,11?EDGEDIST,
<br />WALLTOCONG.9LAB
<br />W/WASHER BOLT DIET., }EDGE DIST,
<br />3 PTWwDOYI BULK 0.13} PAF a21? 9" OIC f END. DIET,. 11?
<br />PT T09TEEL WL., SEE y(/WASHER STAGGERED EDGE DWT.
<br />NOTES
<br />NOTO
<br />11. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. ix MEMBERS ARE NAILED AND
<br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE.
<br />. N. RONALD REAGAN 13LY
<br />LONGWOOD, FL 32750
<br />PH: 407-7746078
<br />FAX( 401-7744078
<br />AA 15:
<br />k
<br />M
<br />C
<br />�
<br />Q
<br />5
<br />SUDDIV. &c HAT:
<br />ABBOTT PARK
<br />LOT #13
<br />BLK #7
<br />PROJECT#
<br />04181.000-13071
<br />MODEIU
<br />4EAB
<br />° 1672- ARIA"
<br />GAGE awsxG:
<br />. RIGHT
<br />PAGE:
<br />DETAILS
<br />160 MPH EXP. C
<br />UN% 06/08/20 1
<br />SN1
<br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />
|