Laserfiche WebLink
• <br />x 'A <br />GA6Lf-EFD <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCrf-Tr <br />ZONE 1 = 23.79 PSF (33.79) <br />ZONE 2 = 39.48 PSF (49.48) <br />ZONE 3 = 67.16 PSF (T7.16) <br />'A'= 4'-0' END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />WIND EXPOSURE:'C' <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT ♦- 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16' <br />O.S.B. OR 1/2' CDX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. 5/8 CDX EXT. PLYWOOD, WITH 8d RING <br />SHANK GUN NAILS AT 4' O.C. AT SUPPORTED <br />PANEL EDGES AND 8d RING SHANK GUN NAILS <br />AT W O.C. AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE <br />Bd GUN NAILS 0 4' O.C. EDGEWISE 2c4 <br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE <br />END. <br />ROOF/ WALU FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. DIA. <br />SHANK <br />TENSILE STR. <br />SHANK <br />Bd <br />RING SHANK, <br />2 1/2' <br />0.120' <br />170,000 <br />1 NG <br />(PER 0 RUNGS <br />SCREW SHANK <br />Sd <br />SCREW SHANK <br />2 112" <br />0.120' <br />PNEUMATIC <br />SCREW -NAILS <br />1. NAIL SIZE PER ASTM F1664 <br />2. INTERNATIONAL STAPE, NAIL & TOOL <br />ASSOCIATION (ISANTA) ESR-1539 <br />EXTERIOR SHEATHING <br />USE 1/2' COX OR 7/16' O.S.B. PLY WITH Sd RING <br />SHANK GUN NAILS AT 4' O.C. AT PANEL SIDES <br />AND 8d RING SHANK GUN NAILS 4' O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN <br />NAILS AT W O.C. AT INTERMEDIATE SUPPORTS <br />OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />8d RING SHANK GUN NAILS 0 4" O.C. <br />.. TOP & BOTTOM EDGES .- <br />J <br />I <br />Z <br />Z <br />7 W <br />- LD aL <br />O <br />® <br />Z . <br />j . <br />Y <br />Q <br />z <br />a <br />19 <br />Q I <br />ZW <br />z CD <br />0LU <br />Y � <br />a <br />=U <br />Tp 0 <br />Z a <br />Z <br />Ir <br />m <br />J <br />Y <br />Z <br />Q W W <br />2 <br />38 o <br />JU U M <br />L) F U <br />row ro <br />a <br />TOP CORD BLOCKING AT 4' <br />O.C. MAX. IN FIRST 2 FRAMING <br />SPACES AT EACH END. <br />RAFTER OR TRUSS <br />Gf1f1F RHFATHINl: <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />- Bd RING SHANK GUN NAILS <br />S 6' O.C. IN FIELD <br />8d RING SHANK GUN NAILS 0 12- O.C. IN <br />FIELD or 8d x 2 112' SCREW SHANK <br />PNEUMATIC SCREW -NAILS W 12. O.E.N <br />FIELD J\ <br />TYP. 3/4' T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTMC33. MAXIMUM AGGREGATE SIZE SWILL BE 3W. <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />WOOD: <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />PROVIDE 8%AIR ENTRAINED CONCRETE EXPOSED TO EARTHORWEATHER <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF <br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />TO CHAMFERED 3/C <br />ON STRUCTURAL DRAWINGS, APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, 6th EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE BE . <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. FIG . 1100 PSI AND A MODULUS OF <br />FOR STRUCTURAL CONCRETE, ACI ASCE AISI SPECIFICATION FOR THE DESIGN OF <br />PROVIDE 64AL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLAB.SONC-ROUND WHERE INDICATED ON <br />ELASTICITY . 1,40Q0. PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL <br />013 <br />L MEMBERS <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS <br />DRAWINGS. SEAMS LAPPED 61NCHES AND SEALED WITH ADHESIVE TAPE. <br />IBE <br />LA A <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORM -WORK: <br />SHALL BE RATED TO RETENTION LEVELS OF 0,25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347, <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2017, 6th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS <br />SYP a2. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />T WORK PERFORMED AN SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />O O KD E <br />DESIGN LOADS: <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 paf <br />20 pBf TOP CHORD-nonconcu-1 <br />10 paf BTM CHORD -ran-wrlcurrnrlt <br />DEADLOAD DEAD LOAD <br />15 pef TOP CHORD 20 paf TOP CHORD <br />(7 GO W/ ASPHALT SHINGLES) (10 psf W/ No GYPCRETE) <br />10 GO BTM CHORD 5 paf BTM CHORD <br />DEAD LOAD TO RESIST WIND UPLIFT: 1 Opaf <br />BALCONY LIVE LOAD 50 paf <br />STAIRS LIVE LOAD 40 psf <br />WIND: DEAD LOAD SPEED =160 MPH 3- SECOND GUST <br />(ASCE 7-10 (FSC R2017) EXPOSURE C, RISK CATEGORY II) <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10pnf, UNINHABITABLE ATTIC WITH LIMITED <br />STORAGE: 20p11, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30p9f, BALCONIES (EXTERIOR) <br />AND DEC.: 40Paf. GUARDS AND HANDRAILS: 200paf, GUARD IN -FILL COMPONENTS: SOpaf, PASSENGER <br />VEHICLE GARAGES: 60psf, ROOMS OTHER THAN SLEEPING ROOM: 4opsf, SLEEPING ROOMS: 30ps1, STAIRS: <br />40pef <br />SHOP DRAWING REVIEW: <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />WRITING BY THE ARCHITECT. <br />FOUNDATION/ SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1657. TREAT ALL <br />SOIL FOR TERMITE PROTECTION. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH, ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,600 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIORTO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED F.V PRK)RTO THE ADDITION OF PLASTICIZER. <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C-94 OR MEASURING, MIXING, TRANSPORTING, ETC <br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS <br />ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SWILL NOT EXCEED 90 MINUTES. IF FOR ANY REASON THERE IS A <br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED IT SHALL BE THE <br />RESPONSIBIUTY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON <br />COMPLIANCE NTH THE ABOVE <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A Y FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH(FOUNDATIONS): <br />B. FOR CONCRETE EXPOSED TO EARTH ANDIOR WEATHER <br />1:112' FOR Mi AND SMALLER <br />2' FORM AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3/4' FOR SLABS, WALLS AND JOISTS <br />1-tR' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />WELDED WIRE MESH: <br />WELDED WIRE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE <br />SUPPORTED WITH Y CHAIRS SPACED V-0' OC, EACH WAY. <br />REINFORCING STEEL: <br />REBAR SHALL BE ASTM A616 GRADE 40 IN CONCRETE DEFORMED BARS REBAR SHALL BE ASTM A615 <br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION, HORIZONTAL <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: 44 BAR - 25' 46 BAR - 36' <br />05 BAR - 30" 47 BAR - 42' <br />PROVIDE SW x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION. <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />WOOD TRUSSES: <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0,036' AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A448, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPk14, -DESIGN NATIONAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND 'TPIM/TCA BCSI 1' <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />WOOD TRUSSES. <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI ASO 1-1982 <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />WALL. <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY &ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />MASONRY• <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />'SPECIFICATION MASONRY STRUCTURES' (ACI 530/ ASCE 5/TMS 402, BUILDING CODE REQUIREMENTS FOR <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />MANUFACTURED IN CONFORMANCE WITH ASTM G-90, GRADE fb . 1600 PSI. BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />ALL TRUSS TO TRUSS CONNECTIONS, <br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8' <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8' TO 10,. USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />TYPE 'M' OR'S' MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />SHALL BE 318' THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />CELLS TO BE FILLED. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O <br />STRUCTURALSTEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION, STRUCTURAL STEEL SHALL BE ASTM <br />A36, Fy = 36 ksi FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A-600, GRADE B <br />Fy . 46 ksi. STRUCTURAL PIPE SHALL BE ASTM-53, GRADE B, TYPE E OR S, Fy = 35 ksi. TUBE AND PIPE <br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING, ALL <br />OTHER BOLTS SHALL BE ASTM A326-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APPLICATION <br />G. <br />TYPE <br />SPACING <br />RE.- <br />APPLICATION <br />9QE <br />TYPE <br />SPACING <br />i1EMARK9 <br />I-FURRNGTO <br />MASONRY/GONG. <br />CASE HARDENED COIL <br />NMLI LIT LONG. <br />SO.0 <br />GAMGE DOOR BUCK <br />TO MA90NRYA'x1rJC, <br />tM'DM. <br />NO WASHER <br />TAPfYJN MASONRY <br />FASTENER <br />S- <br />tI EMBEDA'ENDDI6T.. <br />rz'EDGE DIST. <br />SOD, AL. EM DOOrA <br />CASEHARDENEDCOIL <br />S'O.0 <br />INDOYlNOOWFASTENEO <br />GAMGE DOOR BJCN <br />trz'DW. W/ <br />E%PANSION BOLT <br />N•O,C <br />d'EMBED..4'END DIST.. <br />tz PT.6EE NOTE B <br />tUtI IYY LONG. <br />STAGGERED <br />INTO MA90NRYA:ONC. <br />TO MA60NRYA%WC. <br />WA6HEII <br />YEDGE DIST. <br />WINDOW BUCK <br />CASE HARDENED COIL <br />S'OF <br />-FASTENEDME-GT-1. <br />CONTACT THIS ENGINEER FOR SPACING <br />1. M, SEE-E6 <br />NAIL Irz'LONG. <br />-.E.. <br />I-MABONRY.cDNG. <br />MANNRYrGONO <br />REQUIREMENTS <br />El(-INGOWR <br />(2)YI!'DM. <br />'TAPCON' <br />OK' <br />11EMBED "No <br />/Y <br />NON-BEARINGWOOD <br />trz'° EXPSION 4-EMBED. I- END <br />OD <br />BUDK PT, BEE NOTES <br />No WASHER <br />1-IS <br />1T EDGE DIST, <br />qLL TO COFL..111 <br />W/ WASHEFI BOLANT <br />DIST.. S' EDGE DIST. <br />T WMADW BUCK 88°PAF z21/S' S. Do 4'END. DIST..I I ? <br />O, PCOL., SEE W/WASHER STAGGERED EDGE DIST. <br />TO <br />Pi STEEL <br />NOTE S <br />NOW <br />1STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND/ OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />6. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />e. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAP TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD <br />LONGWOOD, FL 32750 <br />PH: 407-774-6078 <br />FAX: 407-774.4076 <br />WWW.8bd881gNgroU <br />AA M. 000332 <br />'7 <br />=Ys�� <br />Gf <br />p� <br />J <br />® <br />mmG§4 <br />Gt <br />Sf <br />O <br />a00K <br />6 <br />0 <br />a <br />R <br />aUDDIV. to LCT.il <br />ABBOTT PARK <br />LOT #11 <br />BLK #15 <br />PROJECT# <br />04181.000-11151 <br />HODEla <br />4EBB <br />111828-CALM' <br />GARAGE OWING: <br />LEFT <br />PAGE: <br />DETAILS <br />160 MPH EXP. C <br />a <br />DpjwT <br />ATr.. 09/01/20 <br />OCAL IC: 1/4"=V-0" <br />ENEET <br />S N1 <br />