A <br />OA&E-ENO <br />A <br />ROOF WIND DESIGN PRESSURES <br />NET(GROSS) I7 <br />ZONE 1 •23.79 PSF (33.79) <br />ZONE 2 •39.48 PSF (49.48) <br />ZONE 3 •67.16 PSF (77.16) <br />"A"• 4'-O" END ZONE DISTANCE <br />BASIC WAND SPEED: 160 MPH <br />WAND EXPOSURE:'C" <br />RISK CATAGORV: 11 <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT +- 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16' <br />O.S.B. OR 1/7' CDX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. 5/8 COX EXT. PLYWOOD, WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND Bd RING SHANK GUN NAILS <br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL <br />ROOF SHEATHING TO GABLE END FRAME USE <br />8d GUN NAILS 0 4" O.C. EDGEWISE 2x4 <br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE <br />END. <br />ROOF/ WALU FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. DIA <br />SHANK <br />TENSILE STR. <br />SHANK <br />Sd <br />RING SHANK, <br />212' <br />0, 120" <br />170000 <br />RING <br />SCREW SHANK <br />10 RINGS <br />E6.2R INCH) <br />8d <br />SCREW SHANK <br />212' <br />0.120' <br />PNEUMATIC <br />SCREW -NAILS <br />1. NAIL SIZE PER ASTM F1664 <br />2. INTERNATIONAL STAPE, NAIL & TOOL <br />ASSOCIATION (ISANTA) ESR-1539 <br />EXTERIOR SHEATHING <br />USE 12' CDX OR 7/16' O.S.B. PLY WITH Sd RING <br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES <br />AND Bd RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL. AND 8d RING SHANK GUN <br />NAILS AT &' O.C. AT INTERMEDIATE SUPPORTS <br />OR 7/16' ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUR SPECS.)SEE DETAIL <br />8d RING SHANK GUN NAILS 0 4" O.C. <br />TOP & BOTTOM EDGES <br />J <br />2 <br />Z <br />7 W , <br />t7 LL <br />2 <br />ti <br />N�D O <br />to . <br />Z v <br />j <br />SaSdZ <br />x U3UJ� <br />2 U <br />ED . <br />Z ro <br />EcR <br />W <br />W <br />U w <br />L) <br />O <br />TOP CORD BLOCKING AT 4' <br />O.C. MAX. IN FIRST 2 FRAMING <br />SPACES AT EACH END. -� <br />RAFTER OR TRUSS <br />ROOF SHEATHING -� <br />(, BUILDING LENGTH U <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />C8d RING SHANK GUN NAILS <br />6' O.C. IN FIELD ` <br />8d RING SHANK GUN NAILS 0 17' O.C. IN <br />FIELD or Ed x 2 12' SCREW SHANK <br />PNEUMATIC SCREW -NAILS 0 17 0.S.)N <br />FIELD J\ <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPUCA13LE BUILDING CODE STANDARDS: FBC-R 2017, 6N EDITION <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, ACI 530-13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011. ASCE 7-10 AND AISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />OF THE WORK. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33 MOOMM AGGREGATE SIZE SHALL BE SIC <br />WOOD: <br />PROVIDE 6%A0R ENTRAINED CONCRETE DPOSED TO EARTH OR WEATHER <br />NONSEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3W. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb - 1100 PSI AND A MODULUS OF <br />PROVIDE 64IL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SIABMNGROUND WHERE INDICATED ON <br />ELASTICITY - 1,400,OD0 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />DRAWINGS. SEAMS LAPPED S INCHES AND SEALED WITH ADHESIVE TAPE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONSTRUCTURAL USES <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />FORMWORK: <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347, <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />"RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2017, 6N EDITION. SEE NAILING SCHEDULE ON PLANS. <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP $2. <br />WELDED WIRE MESH: <br />WELDED WIRE MESH; SHALL BE ASTM A185, GRADE 85 AND BE PLACED IN ACCORDANCE MATH THE ACI <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE <br />SUPPORTED WITH 2' CHAIRS SPACED T-O' OC, EACH WAY. <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />WOOD TRUSSES: <br />TO E DESIGNED A FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR <br />8AND E <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SMALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND <br />REBAR HALL E TM A615 GRADE 401N CONCRETE DEFORMED BARS REBAR SHALL BE ASTM A615 <br />S B AS <br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />IN MASONRY DEFORMED BARB FREE FROM OIL SCALE AND RUST AND PLACED IN ACCORDANCE GRADE 80 ON <br />A <br />DESIGN LOADS: <br />WITHE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14. "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL1. <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 pBi <br />AND VERTICAL BARS SHALL LAP 8 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />FOR HAND ETAL-PCA E-C N <br />20 psf TOP CHORD -Ronaon.-t <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25' 08 BAR - 38" <br />WOOD TRUSSES. <br />10 pa BTM CHORD-nonconcurtent <br />05 BAR - 30" #7 BAR - 42' <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36' x 36' CORNER BARS, BOND BEAM ONLY, LIPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982. <br />TOP CHARD p CHORD <br />STOP <br />(7 PBTw/ASPHALT SHINGLES) psT W/ No GYPCRETE) <br />(7 9 (1 <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />5 p <br />10AD BTM CHORD 5 ptl BTM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WAND UPLIFT: 10psf <br />MINIMUM 101NCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 Pd <br />WALL. <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 W <br />WIND: DEAD LOAD SPEED =1R2017) MPH 3-SECOND GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />(ASCE (FBA EXPOSURE C. RISK CATEGORY II) <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBIUTV & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: T, UNINHABITABLE ATTIC WITH LIMITED <br />BIT ATTIC <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />W <br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30ps1, BALCONIES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40pef, GUARDS AND HANDRAILS: 200pd, GUARD IN -FILL COMPONENTS: 50pd, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50ps1, ROOMS OTHER THAN SLEEPING ROOM: 40pa1, SLEEPING ROOMS: 30psT, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40PBf <br />MASONRY: <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: <br />"SPECIFICATION MASONRY STRUCTURES" (ACI 530/ASCE 5/TMS 402, BUILDING CODE REQUIREMENTS FOR <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />THE H <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-B0, GRADE I'm = 1500 PSI. BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISENOTED. LAY-UP MASONRY WALLS 70 BOTTOM OF TIE BEAMS BEFORE <br />WI(COLUMNS. <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />CONCRETE FOR IN -WALL GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM C-478, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 31W <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED NA SLUMP OF 8" TO 10", USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATION/ SITE PREPARATION' <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 Ff. FOOTING <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE <br />SHALL BE Sir THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL <br />CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT CEO -TECHNICAL ENGINEER TO VERIFY <br />REINFORCING. <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL REBAR 6 X BAR NO. 146 BAR DIAMETERS)., U.N.O. <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />STRUCTURAL STEEL: <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />CONCRETE: <br />BPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTw <br />A98 F • 36 kW FOR ANGLES PLATES AND W-SHAPES STRUCTURAL TUBING SHALL BE ASTM A-500 Co- <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />CONTRACTOR SWILL SUBMIT PROPOSED MX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5' 4N-PRIOR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C-94 OR MEASURING, MIXING, TRANSPORTING, ETC. <br />CONCRETE TICKETS SWILL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAAMM TIME ALLOWED FROM WHEN WATER IS <br />ADDED TO THE MIX UNnL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES, IF FOR ANY REASON THERE 13 A <br />DELAY W SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SWILL BE THE <br />RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON <br />COMPLIANCE WITH THE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A 3' FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS): <br />3 B. FOR CONCRETE EXPOSED TO EARTH AtNDIOR WEATHER <br />1.1/!' FOR05 AND SMALLER <br />Y FOR AS AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3W FOR SLABS, WALLS AND JOISTS <br />14W FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />Y <br />Fy = 48 kel. STRUCTURAL PIPE SHALL BE ASTM-53, GRADE 8, TYPE E OR S. Fy = 35 kel. TUBE AND PIPE <br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE 70 BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APPLH:ATKIN <br />MiE <br />ttPE <br />SPAgNO <br />REMARKS <br />PAPL-11. <br />SINE <br />I TYPE <br />BPAgNG <br />REI.fARKB <br />t x]PT FlARING TO <br />CISE HARDENED CYML <br />GARAGE DOOR BUq( <br />1l4"qA <br />TPPCON MASONRY <br />I s, <br />110"EMBED., 4"ENO tlsT., <br />MASONRY/GONG. <br />NAIL 110 LONG, <br />0, <br />TO MASONRYtiONC. <br />NO WASHER <br />FASTENER <br />11?EDGE tlST. <br />s00. AL. EAT DWNB <br />-HA-EDCgI <br />0"OIC <br />N1NOgY,DOOR/FASTENED <br />GARAGE DOCA BUCK <br />1IY dAW <br />IXPM1910H BOLT <br />b'OIC <br />PEMBEO.rEW qsT.. <br />1x Pf, SEE NOTES <br />WlIL 11?LONG. <br />STAOpEREO <br />I-- <br />TO MASDNRYM/JNC. <br />WASHER <br />3•EDGE 01W. <br />WnNoowsuae <br />CAREIUROENEDCgL <br />B•an <br />WINDOW,DOIXLFAsicee^ <br />METALeTRAfTo <br />CONTACT THIS ENGINEER FOR SPACING <br />tx Pr. BEE NOlEO <br />NNL,1?LONG. <br />OTAGOERED <br />INTO <br />REQUIREMENTS <br />IXT. sYANG DJIXi <br />p13NSVIA. <br />'NPR: 1' <br />,NY EMBED. O•END. <br />NON -BEARING WJOO <br />1!Y" E%PPN91pN 4"EMSEO.PEND <br />N"OC <br />BUCK h PT,SEENCTEB <br />NOWASHER <br />NASTIER <br />,F O� <br />tlST.,112"ED3E tlaT. <br />WALLTOOONC. 9lAB <br />VI/WASHER BOLT tlsT.,SEDGE dsT. <br />PXPi WINDONN BUCIt 0.190°PAFx]1/B' 0"OIC a"E_.1T.,, 1IT' <br />t0 STEEL COL. BEE <br />NDTEB 1N1 W,--, eTPvroEREO EOOE dST. <br />NOTES <br />1. STAPSTAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS WINDOWS AND EXTERIOR SW NG DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILT( X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />& WINDOW AND DOOR BUCKS SHALL BE AS WADE OR W DER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SW NG DOOR WITH A WOOD DOOR FRAME. 4. MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED WV TAPCONS OR PAF TO THE SUBSTRATE. <br />lw <br />1441 N. RONALD REAGAN BLVD <br />LONGWOOD,FL32750 <br />PH: 407-774-6078 <br />FAK 407-7744078 <br />www.abdeslgngmup.eom <br />AA 8: 0003328 J <br />y <br />a <br />a <br />OV <br />A4 <br />h <br />z <br />LT <br />It <br />S <br />w <br />O <br />V <br />SVHDIV. & LOT: <br />ABBOTT <br />PARK <br />LOT #10 <br />BLK #8 <br />PROJECT# <br />04181.000-10081 <br />MODEL' <br />4EBB <br />"1828-CALI" <br />GARAGE SWING: <br />LEFT <br />PAGE: <br />DETAILS <br />160 MPH EXP. C <br />- t-kn M0i'Z1114., <br />SCALE: 1 /4"= f - O" <br />SHEET <br />s N1 <br />