m
<br />GABLE -END T_l
<br />wP RooF N`-A`
<br />ROOF WIND DESIGN PRESSURES
<br />NET (GROSS) ASCI: 7-10
<br />ZONE 1 =18.56 PSF (28.56)
<br />ZONE 2 = 32.94 PSF (42.94)
<br />ZONE 3 = 56.39 PSF (66.39)
<br />"A"= 4'-0" END ZONE DISTANCE
<br />BASIC WIND SPEED: 160 MPH
<br />WIND EXPOSURE: "C'
<br />RISK CATAGORY: If
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT+- 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 7116"
<br />O.S.B. OR 1/2" COX EXT. PLYWOOD, FOR
<br />CEMENTITIOUS TILE AND METAL ROOFING, USE
<br />MIN. 518 COX EXT. PLYWOOD, WITH 8d RING
<br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED
<br />PANEL EDGES AND 8d RING SHANK GUN NAILS
<br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. SEE
<br />DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE
<br />Bd GUN NAILS @ 4" O.C. EDGEWISE 2X4
<br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE
<br />END.
<br />ROOF/ WALLA FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />NAIL SCHEDULE
<br />SIZE
<br />TYPE
<br />MIN. LENGTH
<br />MIN. DIA.
<br />SHANK
<br />TENSILE STR.
<br />SHANK
<br />8d
<br />RING SHANK,
<br />2 1/2"
<br />0.120"
<br />170,000
<br />(Rjl6-2 RINGS
<br />SCREW SHANK
<br />PER INCH)
<br />Sd
<br />SCREW SHANK
<br />21/2"
<br />DAN"
<br />PNEUMATIC
<br />SCREW -NAILS
<br />1. NAIL SIZE PER ASTM F1664
<br />2, INTERNATIONAL STAPE, NAIL 8 TOOL
<br />ASSOCIATION ([SANTA) ESR-1539
<br />EXTERIOR 8HEATT#NG
<br />USE 1/2" COX OR 7/16" O.S.B, PLY WITH 8d RING
<br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES
<br />AND 8d RING SHANK GUN NAILS 4" O.C. TOP &
<br />BOTTOM PANEL AND 8d RING SHANK GUN
<br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS
<br />OR 7116" ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL.
<br />O
<br />C�
<br />J
<br />Zw
<br />Zo
<br />= w
<br />aZa c
<br />Sd
<br />NO
<br />2
<br />o9D
<br />8d RING SHANK GUN NAILS @ 4" O.C.
<br />.. TOP & BOTTOM EDGES .-
<br />J /
<br />z9
<br />- zw
<br />LL
<br />5C Z
<br />N
<br />0
<br />Z ZY
<br />02=D _
<br />-
<br />1_
<br />Y 3
<br />N ((w�O
<br />Z�
<br />C�J
<br />_J
<br />W
<br />CCDD W
<br />Z
<br />= U
<br />O 0
<br />Z
<br />K
<br />GO
<br />Z
<br />W
<br />C7
<br />U W
<br />U
<br />O
<br />U
<br />w
<br />(L
<br />TOP CORD BLOCKING AT 4'
<br />O.C. MAX. IN FIRST 2 FRAMING
<br />SPACES AT EACH END.
<br />RAFTER OR TRUSS �
<br />ROOF SHEATHING
<br />11
<br />.---M,I11
<br />BUILDINGUENGTH
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />Sd RING SHANK GUN NAILS
<br />6" O.C. IN FIELD `
<br />Bd RING SHANK GUN NAILS @ 12" O.C. IN
<br />FIELD or 8d X 2 1r2' SCREW SHANK
<br />PNEUMATIC SCREW -)AILS C 12" 0.8NjN
<br />FIELD /\/
<br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTMC33. MAXWUM AGGREGATE SIZE SHALL BE 3W.
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />WOOD"
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />pftpylDE B%AIR ENfFWNEO CONCRETE EXPOSED TO EARTH OR WEATHER
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ALL EXPOSED EDGES OF TO BE CHAMFERED
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, Bm EDITION
<br />CONCRETE ARE
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING. LEDGERS, BLOCKING,
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />CRIPPLERS, SILLS. ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. F0 = 1100 PSI AND A MODULUS OF
<br />FOR STRUCTURAL CONCRETE, ACI 530-13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF
<br />PROVIDE 848L CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLA83-0H-GROUND WHERE INDICATED ON
<br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASIDE 7-10 AND AISC SPECIFICATIONS
<br />DRAWINGS SEAMS TAPPED B INCHES AND SEALED WITH ADHESIVE TAPE.
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED, WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0,26 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />FORMWORK:
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347,
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK.
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FBCR 2017, em EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />OF THE WORK.
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYP #2.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />WELDED WIRE MESH'
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />WELDED WIRE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI
<br />WOOD TRUSSES:
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE
<br />SUPPORTED WITH 2' CHAIRS SPACED 3'-0' OC, EACH WAY.
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA, SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />DESIGN LOADS:
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 PSI
<br />20 pal TOP CHORD -non-concurrent
<br />10 p9 BTM CHORD -ran-conwn iTt
<br />DEAD LOAD DEADLOAD
<br />16 p4f TOP CHORD 20 p31 TOP CHORD
<br />(7 p3f w/ ASPHALT SHINGLES) 00 pef w/ No GYPCRETE)
<br />10 PSI BTM CHORD 5 pst BTM CHORD
<br />DEAD LOAD TO RESIST WIND UPLIFT: 10PSf
<br />BALCONY LIVE LOAD 60 pSf
<br />STAIRS LIVE LOAD 40 PSI
<br />WIND: DEAD LOAD SPEED =160 MPH 3- SECOND GUST
<br />(ASCE 7-10 (FBC R2017) EXPOSURE C, RISK CATEGORY 11)
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10p9f, UNINHABITABLE ATTIC WITH LIMITED
<br />STORAGE: 20PSC HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30pSf, BALCONIES (EXTERIOR)
<br />AND DECKS: 40pef, GUARDS AND HANDRAILS: 200pd, GUARD IN -FILL COMPONENTS: 50p 1, PASSENGER
<br />VEHICLE GARAGES: 50pef, ROOMS OTHER THAN SLEEPING ROOM: 40p4f, SLEEPING ROOMS: 30pef, STAIRS:
<br />40pef
<br />SHOP DRAWING REVIEW:
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT.
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />WRITING BY THE ARCHITECT.
<br />FOUNDATIOW SITE PREPARATION:
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 pSf, FOOTING
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL
<br />SOIL FOR TERMITE PROTECTION.
<br />REINFORCING STEEL:
<br />REBAR SHALL BE ASTM A615 GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615
<br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE
<br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEERS
<br />REVIEW.
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25' #6 BAR • 36"
<br />#5 BAR - 30' #7 BAR - 42"
<br />PROVIDE 36' x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />FOR ADDITIONAL INFORMATION.
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL
<br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED.
<br />DESIGN, FABRICATE. AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL
<br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND TPIPMCA BCSI V
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />WOOD TRUSSES.
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982.
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />WALL.
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />MASONRY:
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />LICENSED PROFESSIONAL ENGINEER.
<br />"SPECIFICATION MASONRY STRUCTURES" (ACI 530/ASCE 5RMS 402. BUILDING CODE REQUIREMENTS FOR
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE,
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE I'm = 1500 PSI. BLOCK SHALL BE PLACED USING
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7AO COMPONENT
<br />RUNNING BOND UNLESS OTHERWISE NOTED, LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />PLACING CONCRETE FOR IN -WALL COLUMNS, GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />ASTM 0d76, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318"
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED, REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />CELLS TO BE FILLED.
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />REINFORCING.
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O.
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />STRUCTURAL STEEL:
<br />BE MADE BY THE OEO-TECH. ENGINEER.
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />CONCRETE:
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36, Fy - 36 kSI FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A500, GRADE B,
<br />Fy - 46 k31. STRUCTURAL PIPE SHALL BE ASTM-53, GRADE B, TYPE E OR S, Fy - 35 k31. TUBE AND PIPE
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SUB.
<br />CTU
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS. WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO
<br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL
<br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT S(CEEDSd- PRIOR TO THE ADDITION OF PLASTICIZER
<br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />CONCRETE SH4LL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C44OR MEASURING, MXING, TRANSPORTING, ETC. ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL.J-BOLTS ARE TO BE STEEL.
<br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MXXIMUMTIME ALLOWED FROM WHEN WATER IS
<br />ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MNUTES. IF FOR ANY REASON THERE ISA
<br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE
<br />RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON
<br />COMPLIANCE WTH THE ABOVE.
<br />REGUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS:
<br />A Y FDR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONSI:
<br />B. FOR CONCRETE EXPOSED TO EARTH AMWOR WEATHER
<br />1-1/Z'FORASANDSAWLEt
<br />2' FOR#8 AND LARGER
<br />C FOR CONCRETE NOT EXPOSED TO WFATH6t
<br />3/4' FOR SUBS, WALLS AND JOISTS
<br />1-10 FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />APPLIGTx)N
<br />SITE
<br />TYFE
<br />SPALMG
<br />REMAPo(3
<br />APPLIGTpN
<br />9QE
<br />TYPE
<br />SPACING
<br />REAWiK9
<br />1. PT FURRWG TO
<br />CASEHMDENEDCO0.
<br />0.
<br />GARAGE OOM &ILK
<br />1N'DW.
<br />TAPCON MASONRY
<br />b-dC
<br />112"ELL41EE0., 4-ENDDIST..
<br />MASONRY/GONG
<br />NAIL 11?LOVG.
<br />TO MA9gVRYlCONC,
<br />NO WA9HER
<br />_TENFRI
<br />Ilf EDGE DIET,
<br />EGD, AL. EXT. DOORS
<br />GSE HARDENED COIL
<br />F G
<br />WINDOW000R/FA9TENED
<br />---EDOCRSULK
<br />1R'DM. W/
<br />IXPANSNxu BOLT
<br />Y4'OIC
<br />PEMBEO., 1'ENDOET,
<br />tx m,SEENOTEG
<br />NNL 11?LONG.
<br />STAGGERED
<br />INTO MA90NRY/CONC.
<br />TO MA90NRY/CONO.
<br />WASNER
<br />SEDGE DIET.
<br />wsawiauac
<br />G9EHARDENEDOOIL
<br />E•ac
<br />wlNoowGoo.1- NE.
<br />MErAL3rRAPro
<br />CONTACT THIS ENGINEER FOR SPACING
<br />tx PT,3EENOTEE
<br />NAA 11?LONG.
<br />STAGGERED
<br />INTO--
<br />MA9CNRY/DONO
<br />REQUIREMENTS
<br />EXT. SWNO DOOR
<br />RI Y1B'9w.
<br />-fAPLON'
<br />13'dL
<br />1tlY EMBED,CEIO.
<br />NON-M-NO WOOD
<br />1; EJfPNJ_ OIL
<br />4'
<br />BULK]x PT,EEENOTE3
<br />No -ENE.
<br />FASTNER
<br />OIST..I IIY EWEDRIT.
<br />WALLTOOONC.9lAB
<br />W/WASHER BOLT
<br />OBIT„S'EDGE DIET.
<br />.3-ED E318
<br />PT WIDOW BUCX
<br />vT.138•PAF xY 1/H- YqC 1-END. OTT., I IW
<br />TOSTEEL Cw., SEE WI WASHER 9TAGOEFiO NOTE e EDGE MET.
<br />UN
<br />11. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILT] X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5, FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NQA OR THE SPACING DETAILED ABOVE
<br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME, 1x MEMBERS ARE NAILED AND
<br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE.
<br />mm
<br />aU33DM & LAT
<br />ABBOTT PARK
<br />LOT #6
<br />BLK #15
<br />PROJH:CT*
<br />04181.000-06151
<br />moDErj
<br />4EWB
<br />"1499-FREEPORT"
<br />GARAGE OWn4G:
<br />RIGHT
<br />PAGE:
<br />DETAILS
<br />160 MPH EXP. C