q <br />WHE-ENO •�>� <br />HM ROOF <br />ROOF WIND DESIGN PRESSURES <br />NET(GROSS) ASIDE 7- <br />ZONE 1 = 23.79 PSF (33.79) <br />ZONE 2 = 39.48 PSF (49.48) <br />ZONE 3 = 67.16 PSF (77.16) <br />'A'= 4'-0' END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />WIND EXPOSURE: "C" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT -0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7118" <br />O.S.B. OR //P' COX EXT, PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />ON. 5/8 COX EXT. PLYWOOD, WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND 8d RING SHANK GUN NAILS <br />AT 5' O.C. AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL. <br />".F SHEATHING TO GABLE END FRAME USE <br />8d GUN NAILS @ 4" O.C. EDGEWISE 2x4 <br />BLOCKING ALL PANEL JOINTS WI IN W OF GABLE <br />END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. DIA. <br />SHANK <br />TENSILE STR. <br />SHANK <br />Bd <br />RING SHANK, <br />SCREW SHANK <br />2 1/2" <br />0.120" <br />170,000 <br />wffz- <br />(16-20 RINGS <br />PER INCH) <br />Ed <br />SCREW SHANK <br />21/2" <br />0.120" <br />PNEUMATIC <br />SCREW -NAILS <br />1. NAIL SIZE PER ASTM F1664 <br />2. INTERNATIONAL STAPE, NAIL & TOOL <br />ASSOCIATION (ISANTA) ESR-1539 <br />EXTERIOR SHEATHNG <br />USE 1l2" CDX OR 711 G" O.S.B. PLY WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES <br />AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN <br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS <br />OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />8d RING SHANK GUN NAILS @ 4" O.C. <br />„ TOP &BOTTOM EDGES „ <br />J <br />Z9 <br />O LL <br />SSQ U <br />J_ <br />� <br />z=U' <br />ZQY <br />to <br />G . <br />IM <br />TOP CORD BLOCKING AT 4' <br />O.C. MAX. IN FIRST 2 FRAMING <br />SPACES AT EACH ENO. <br />RAFTER OR TRUSS <br />IDnna cuce-rwur_ -__ <br />Emmmmimi <br />I.-_-�mm ,I <br />mmm <br />a <br />ROOF SHEATHING LAYOUT <br />AND ENOWALL BRACING <br />FOR GABLE END FRAMING <br />8d RING SHANK GUN NAILS <br />@ 6" O.C. IN FIELD 1 <br />�•- 8d RING SHANK GUN NAILS @ 12" O.C. IN <br />FIELD or Sd x 2 1/2" SCREW SHANK <br />PNEUMATIC SCREW -NAILS @ 12" 0.8,.jN <br />FIELD J\ <br />1 YH. ;Y41 SU SUb-YLUUH UtQKINU GLUGU I U ALL EAYUStU MtMtltHb <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE $HALL CONFORM TO ASTM C33 MAXIMUM AGGREGATE SIZE SHALL BE Yr. <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />WOOD: <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />PROVIDE 8%MR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVES DEPRESSIONS AND OTHER DETAILS NOT SHOWN <br />EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3/1r. <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBGR 2017, 881 EDITIONALL <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />CRIPPLERS,! <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER Fb - 1100 PSI AND A MODULUS OF <br />FOR STRUCTURAL CONCRETE, ACI 53D-13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF <br />PROVIDES CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SIABSON-GROLND JAI ERE INDICATED ON <br />PROVIDESWINGS <br />ELASTICITY 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS <br />SEAMS LAPPED B UNCHES AND SEALED WITH ADHESIVETAPE. <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORM -WORK: <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347, <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS, FOLLOW WRITTEN DIMENSIONS ONLY, ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2017, 6tn EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />IS COMPLETE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH' <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE470WNS. <br />WELDED WIRE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI <br />WONT TRUSSES: <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE <br />SUPPORTED WITH X CHAIRS SPACED T-W OC EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BV THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />W NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS, AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />GRADE 40 INBARS, <br />REBAR SHALL BE ASTM A615DEFORMED <br />MEETING THE REQUIREMENTS OF ASTM A4/8, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />A D SHALL <br />GRADE 80 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />DESIGN LOADS: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "TPIMVTCA BCSI V <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 pa} <br />VERTICAL BARS SHALL LAP 6 It BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />20 W TOP CHORD -non-Con rrt <br />RAND EVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36" <br />WOOD TRUSSES. <br />10 PM BTM CHORD-IKx1,=ori-t <br />05 BAR - 30" #7 BAR - 42' <br />PROVIDE 36' x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD <br />DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1 082. <br />TOP CHORD <br />p TOP CHORD <br />M wl ASPHALT SHINGLES) <br />(7 PST <br />(7 <br />(1 PST w/ No GVPCRE7E) <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />10 M CHORD <br />BTbf <br />5 <br />5 P BTM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />D <br />DEAD LOAD TO RESIST WIND UPLIFT: 10paf <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 pbf <br />STAIRS LIVE LOAD 40 pa <br />WALL. <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />WIND: DEAD LOAD SPEED -160 MPH 3- SECOND GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />(ASCE 7-10 (FBC R2017) EXPOSURE C, RISK CATEGORY II) <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE, <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE, TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: tOpaf, UNINHABITABLE ATTIC WITH LIMITED <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40paf, GUARDS AND HANDRAILS: 200pM, GUARD IWFILL COMPONENTS: Sopaf, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50paf, ROOMS OTHER THAN SLEEPING ROOM: 40pef, SLEEPING ROOMS: 30paf, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />4Opel <br />MASONRY; <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER <br />SHOP DRAWING REVIEW: <br />"SPECIFICATION MASONRY STRUCTURES" (ACI 530/ ASCE 5/TMS 402, BUILDING CODE REQUIREMENTS FOR <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL BLOCK WALLS SHALL BE HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SOPERCEDE THOSE <br />ALL SHOP DRAWINGS SHALL BE REVIEWED THE CONTRACTORS PRIOR SUBMITTAL TO THE ARCHITECT. <br />ANCE WITH GRADER = 1500 PSI. BLOCK SHALL BE PLACED USING <br />MANUFACTURED IN CONFORMANCE WITH ASTM <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWIN03 SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />WILL . <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />Y-U <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM 0476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318" <br />WRITING BY THE ARCHITECT <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8" TO 10'. USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATION/ SITE PREPARATION' <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2 000 FOOTING S D L pL <br />TYPE'M" OR'S' MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT, MORTAR SHALL BE <br />PROPORTIONED AND OUTLINED UNDER ASTM HORIZONTAL VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB BE COMPACTED A DRY DENSITY OF AT LEAST THE <br />SIO <br />SHALL BE THICK UNLESS OTHERWISE NOTED, REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />UNLESS O REMOVE M <br />YSHALL <br />A 7. THE <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM 0.1557. TREAT ALL <br />MAXIMUM <br />SOIL FOR TERMITE PROTECTION. <br />CELLS TO BE FILLED. <br />BE <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS, LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEGTECH. ENGINEER. <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5' N- PRIOR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C44OR MEASURING, MIXING, TRANSPORTING, ETC <br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE 13 BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS <br />ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON THERE IS <br />DELAY IN SUCH THAT A HATCH 18 HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SIWl BE THE <br />RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY NON <br />COMPLIANCE WITH THE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A 3' PDR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUDATONS): <br />B. FOR CONCRETE EXPOSED TO EARTH ANNOR WEATHER <br />1-112' FDR#6AND SMALLER <br />Y FOR NB AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />314" FOR SLABS, WALLS AND JOISTS <br />1-1(C FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />STRUCTURAL STEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />ASS, Fy = 36 KSI FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A-500, GRADE B, <br />Fy = 46 ksl. STRUCTURAL PIPE SHALL BE ASTM-53, GRADE B, TYPE E OR S, Fy = 35 kal. TUBE AND PIPE <br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />Be TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL, J-BOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APPLICATION <br />SIZE <br />TYPE <br />SPACING <br />REMARKS <br />APPLICATION <br />SRE <br />TTPE <br />SPACING <br />REAWiK3 <br />1-TFURRINGTO <br />CASE HARDENEDCOL <br />S. <br />GARAGE OOIXi BUCK <br />III DI0. <br />TAPCONNASONRY <br />S„aC <br />1I/Y EASED., 1•ENO DSIT., <br />MASONRYICONC. <br />NAIL 112'LONG. <br />TO MASONRYICONC. <br />NO WISHER <br />FASTENER <br />11R"EDOE DIET, <br />AL.EM. DOORS <br />CASE IURDENED COL <br />POIC <br />WWWW/BOOTS FASTENED <br />GARAGE DOOR HICK <br />1?Dw. W/ <br />EXP,ANHIXI HYT <br />iY OTC <br />Y EMEEU..4•ENDDIST., <br />Ir Pi, SfE NOTES <br />NAIII VS LdIG. <br />STAGGERED <br />INTO MASONRYICONC. <br />TO W9OI1i1YlW11C. <br />WASHER <br />-GE pST. <br />w. IWCK <br />CAaEHAROENEDOOL <br />vac <br />WINODwmoDRIFASTENED <br />METAL STRAP TO <br />CONTACT THIS ENGINEER FOR SPACING <br />1K PT, SEE NOTES <br />NAILII2'LONG. <br />9TAOOEREO <br />INTO MASONRYIWNC. <br />MASONRYI( O <br />REQUIREMENTS <br />EXT. 9WNG DOOR <br />(2)&19•DW. <br />'TAPCON' <br />dC <br />„2•EMBED, SEND. <br />NON-0EAwNG WOW <br />rz• EXPANBpN 4'EMBEO. Y END <br />NOK <br />HICK h PT,SEENOTES <br />NO WASHER <br />FASTNER <br />1P <br />GIST„I VL'EDGE DIST. <br />WALL TO CONC. SLAB <br />W/WASHER HjLT OIST.3'EOGE pbT. <br />2e PT WWDON BUCK 0.13C PAFa211H' POIC VEND DST.,11/! <br />PT T08TEEL COL.. SEE WI WASHER bTAGGEREO EOCE DST. <br />NOTES <br />11. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. Ix MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD <br />LONGWOOD, FL 32750 <br />PH: 407-774-6078 <br />FAX: 407-7744078 <br />www.abdoslgngroup.com <br />AA #: 0003325 <br />L0�L1 <br />}yF <br />S <br />TB <br />avHD:v 49 LOT: <br />ABBOTT PARK <br />LOT #4 <br />BLK #15 <br />PROJECTy <br />04181.000-04151 <br />MODELa <br />4EAB <br />"1672- ARIA" <br />GARAGE SWWO: <br />RIGHT <br />PAGE: <br />WTAILS <br />160 MPH EXP. C <br />