Footer <br />Re -Bar (sized <br />according to <br />foundation plan) <br />#4 awg CU bare w/ 10' stubbed <br />outside of slab at service <br />location. Connect to footer steel <br />w/ (2) ground clamps 5' apart <br />LIFER GROUND DETAIL <br />N.T.S. <br />GENERAL ELECTRICAL NOTES <br />ALL ELECTRICAL DESIGN AND WORK SHALL BE IN STRICT <br />COMPLIANCE WITH THE 2014 NATIONAL ELECTRIC CODE <br />• PER NEC SECTION 210.12 (B) ALL 15A & 20A, 120V <br />BRANCH CIRCUITS SUPPLYING OUTLETS REQUIRE <br />AFCI PROTECTION <br />• <br />CARBON MONOXIDE PROTECTION PER FLORIDA <br />STATUTES 553.885 (2). TO BE INSTALLED WITHIN 10' <br />OF EVERY SLEEPING ROOM <br />I <br />• ALL OUTLETS SHOULD BE AFCI PER NEC - U.N.O. <br />�I <br />j • PER NEC SECTION 210.8(B)(5) ALL 15A & 20A, 15V <br />RECEPTACLES INSTALLED OUTDOORS MUST BE <br />GFCI-PROTECTED <br />II <br />• PER NEC SECTION 210.8(B)(5) ALL 15A & 20A, 15V <br />RECEPTACLES INSTALLED WITHIN 6' OF SINK (IN <br />NON -DWELLING OCCUPANCIES-i.e. OUTDOOR <br />SUMMER KITCHENS RECEPTACLES) MUST BE <br />GFCI-PROTECTED <br />ELECTRICAL RISER DIAGRAM <br />OPTIONAL OVERHEAD • PER NEC SECTION 406.8(B)(1) 15A & 20A <br />SERVICE SAME AS 150 = #1 Copper or 2/ 0 Aluminum I RECEPTACLES IN A WET LOCATION MUST BE WITHIN <br />UNDERGROUND 150 OR 200 200 = 2 /0 Copper or 4 /0 Aluminum in 2" AN ENCLOSURE THAT IS WEATHERPROOF WHEN AN <br />AMP SERVICE ATTACHMENT IS PLUGGED IN AN ALL NON -LOCKING <br />Conduit. A/C DISCONNECT RECEPTACLES SHALL BE LISTED AS WEATHER <br />RESISTANT <br />CMTER DMAINISC. - - • PER NEC SECTION 406.11 IN DWELLING UNITS, ALL <br />150 OR r 1 #12 COPPER TO APPLIANCES AND GFI 15A & 20A, 15V RECEPTACLES SHALL BE LISTED AS <br />- 200 AMP TYPICAL TAMPER -RESISTANT <br />ELECTRICAL #14 COPPER TO LIGHTS AND OUTLETS <br />_ J PANEL #10 COPPER TO WATER HEATER • PER NEC SECTION 800.156 NO LESS THAN ONE <br />SERV. BY #8 COPPER TO RANGE COMMUNICATION OUTLET SHALL BE INSTALLED <br />POWER CO. - #6 COPPER TO HVAC WITHIN EACH DWELLING UNIT <br />N.T.S. j __� #4 GROUNDING WIRE WITH CODE APPROVED CLAMP TO EITHER: • PER NEC SECTION R314.3 AND R315.1 SMOKE <br />A) APPROVED GROUNDING ROD WITH MINIMUM 8' DEPTH j DETECTORS TO BE INSTALLED INSIDE EACH <br />B) BONDED TO CONTINUOUS FOOTING STEEL SLEEPING AREA <br />-- INTERSYSTEM BONDING TERMINATION PER NEC 250.94 . ALL SMOKE ALARMS SHALL BE LISTED AND LABELED <br />IN ACCORDANCE WITH UL 217, PER FBC 314.1. GC TO <br />NOTE: INSTALL; KIDDE MODEL # 14618A SMOKE ALARM, OR <br />ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE APPROVED EQUAL <br />PROVISIONS OF THE NFPA 70, LOCAL CODES AND LOCAL POWER/UTILITY COMPANY <br />_._ ___._._ __. _____-- __ _ __ _..., • PROVIDE GAS DROPS AS PER COMMUNITY ONLY <br />• JUNCTION BOX AT WATER HEATER, RANGE AND/OR <br />DRYER TO BE 220V IN NON GAS COMMUNITIES, AND <br />110V IN COMMUNITIES THAT HAVE GAS OPTIONS <br />PROVIDE APPROPRIATE RECEPTACLE PER <br />APPLIANCE <br />• ALL LAMPS SHALL BE HIGH -EFFICACY TO COMPLY <br />WITH FBC-EC R404.1 - (LOW -VOLTAGE LAMPS <br />EXCLUDED). <br />• PER FBC-R M1305.1 A LEVEL WORKING SPACE NOT <br />LESS THAN 30" DEEP AND 30" WIDE SHALL BE <br />PROVIDED IN FRONT OF THE CONTROL SIDE OF ANY <br />APPLIANCE <br />ABBREVIATIONS LEGEND <br />ROOF NOTES <br />EXTERIOR ELEVATION GENERAL NOTES <br />• INSTALL ROOF VENTING PER MFR WRITTEN <br />ABV <br />ABOVE <br />INSTRUCTIONS PER FBC R806 <br />• <br />FRONT ELEVATIONS BANDING, MOLDING, <br />AC <br />AIR CONDITIONER <br />COLUMNS AND TRIM SHALL RECEIVE A SAND <br />AFF <br />ABOVE FINISHED FLOOR <br />• ALL OVERHANG DIMENSIONS ARE TO EDGE OF <br />FINISH. SEE ELEVATION FOR DEPTH OR RAISED <br />AHU <br />AIR HANDLER UNIT <br />RAFTER. REFERENCE WALL SECTIONS/DETAILS <br />BANDING <br />BLK <br />BLOCK <br />FOR ALL OVERHANGS NOT DIMENSIONED. <br />• <br />SIDE AND REAR ELEVATIONS BANDING AROUND <br />CABS <br />CABINETS <br />WINDOWS AND DOORS MAY BE OPTIONAL PER j <br />CLG <br />CEILING <br />• ALL UNDERLAYMENT MUST BE INSTALLED IN <br />COMMUNITY SPECS -SEE COMMUNITY ' <br />CHR <br />CHAIR RAIL <br />COMPLIANCE WITH FBC R501.1.1 <br />SPECIFICATIONS OR CONSULT THE <br />COFF <br />COFFERED <br />CONSTRUCTION MANAGER. ALL BANDING SHALL <br />• EACH 4' OFF RIDGE VENT REQUIRES (1) 46" x 3" CUT <br />RECEIVE A SAND FINISH <br />COL <br />COLUMN <br />OUT IN ROOF SHEATHING PER MFR WRITTEN <br />COND <br />CONDENSER <br />INSTRUCTIONS <br />• <br />ROOF COVERING SEE COMMUNITY <br />CRN <br />CROWN MOULDING <br />SPECIFICATIONS OR CONSULT THE <br />CVAC <br />CENTRAL VACUUM SYSTEM <br />CONSTRUCTION MANAGER, SEE STRUCTURAL <br />DBL <br />DOUBLE <br />SHEETS FOR SHEATHING REQUIREMENTS <br />DIAG <br />DIAGONAL <br />DR <br />DOOR <br />• <br />FLASHING SHALL BE INSTALLED AT WALL AND <br />DRY <br />DRYER <br />ROOF INTERSECTIONS, DECK AND WALL <br />DW <br />DISHWASHER <br />INTERSECTIONS, AT GUTTERS, AT ALL CHANGES IN <br />ROOF SLOPE OR DIRECTION, AND AROUND ROOF <br />EB <br />EYEBROW <br />OPENINGS <br />FL <br />FLOOR LINE (MAT. CHANGE) <br />FLR <br />FLOOR <br />. <br />WINDOW PAN FLASHING SHALL BE IN <br />FP <br />FIREPLACE <br />ACCORDANCE WITH FBC R703.8 <br />FXD <br />FIXED <br />FXT <br />FIXTURE <br />• <br />WALL HEIGHTS VERIFY ALL BEARING WALL <br />GLS <br />GLASS <br />HEIGHTS WITH FINAL TRUSS LAYOUTS <br />HB <br />HOSE BIB <br />-- - --- <br />KS <br />KNEE SPACE <br />- — - <br />• <br />LATH PER FBC R703.7.1, LATH AND LATH <br />LAV <br />LAVATORY <br />ROOF VENT CALCULATION <br />ATTACHMENTS SHALL BE OF <br />LT <br />LAUNDRY TUB <br />_..._ __ <br />CORROSION -RESISTANT MATERIALS. EXPANDED <br />METAL OR WOVEN WIRE LATH SHALL BE <br />MRBL <br />MARBLE <br />FORMULA: <br />ATTACHED WITH 11/2-INCH-LONG (38 MM). 11 GAGE <br />MC <br />MEDICINE CABINET <br />NAILS HAVING A 7/16-INCH (11.1 MM) HEAD, OR <br />MIR <br />MIRROR <br />1 SQUARE INCH VENT FOR EVERY 300 SQUARE INCHES <br />7/8-INCHLONG (22.2 MM), 16 GAGE STAPLES, <br />MTL <br />METAL <br />OF CEILING <br />SPACED NOT MORE THAN 6 INCHES (152 MM), OR <br />OH <br />OVERHEAD <br />*144 SQ. IN. = 1 SQ. FT. <br />AS OTHERWISE APPROVED <br />OPNG <br />OPENING <br />BLDG. CEILING (SF) x 144 = BLDG (SQ. IN.) <br />OPT <br />OPTIONAL <br />BLDG. (SQ. IN.) / 300 = SQ. IN. OF VENT REQUIRED <br />• <br />PLASTER PER R703.7.2, PLASTERING WITH <br />SQ. IN. OF VENT REQUIRED / 2 = 50% AT HIGH AND 50% <br />PORTLAND CEMENT PLASTER SHALL BE NOT LESS <br />R & S <br />CLOTHES ROD and SHELF <br />AT LOW. <br />THAN THREE COATS WHERE APPLIED OVER METAL <br />REF <br />REFRIGERATOR <br />LATH OR WIRE LATH AND SHALL BE NOT LESS <br />SD <br />SOAP DISH <br />PER FBC SECTION R806.2: 40% MIN, BUT NOT MORE <br />THAN TWO COATS WHERE APPLIED OVER <br />SDLTS <br />SIDE LIGHTS <br />THAN 50% OF VENTILATION MUST BE PROVIDED BY <br />MASONRY, CONCRETE, PRESSURE -PRESERVATIVE <br />SGD <br />SLIDING GLASS DOOR <br />VENTILATORS LOCATED NO MORE THAN T-0" BELOW <br />TREATED WOOD OR DECAY -RESISTANT WOOD AS <br />SH (2) <br />SHELVES (QUANTITY) <br />THE RIDGE OR HIGHEST POINT OF THE SPACE <br />SPECIFIED IN SECTION R317.1 OR GYPSUM <br />SHWR <br />SHOWER <br />BACKING. IF THE PLASTER SURFACE IS <br />COMPLETELY COVERED BY VENEER OR OTHER <br />TB <br />TOWEL BAR <br />BASIS OF CALCULATION: ("OR EQUAL" ACCEPTABLE) <br />FACING MATERIAL OR IS COMPLETELY <br />TPH <br />TOILET PAPER HOLDER <br />CONCEALED, PLASTER APPLICATION NEED BE <br />T&S <br />TUB and SHOWER <br />(a) OFF RIDGE VENTS - STAMPCO W/ 36 SQ IN (NFVA) <br />ONLY TWO COATS, PROVIDED THE TOTAL <br />TEMP <br />TEMPERED <br />PER LINEAL FT <br />THICKNESS IS AS SET FORTH IN TABLE R702.1(1). <br />TR <br />TRANSOM <br />ON WOOD -FRAME CONSTRUCTION WITH AN <br />VOL <br />VOLUME <br />(b) SOFFIT VENTS - GP T3-1/3" FULL VENT PERFORATED <br />ON -GRADE FLOOR SLAB SYSTEM, EXTERIOR <br />WC <br />WATER CLOSET <br />W/ 9.19 SQ IN (NFVA) PER LINEAL FT <br />PLASTER SHALL BE APPLIED TO COVER, BUT NOT <br />EXTEND BELOW, LATH, PAPER AND SCREED. THE <br />WD <br />WOOD <br />CALCULATED LINEAL FOOT OF SOFFIT VENT SHALL <br />PROPORTION OF AGGREGATE TO CEMENTITIOUS <br />WH <br />WATER HEATER <br />NOT INCLUDE NON -VENTED FIRE RATED SOFFIT <br />MATERIALS SHALL BE AS SET FORTH IN TABLE <br />WNCT <br />WAINSCOT <br />LOCATED LESS THAN S FROM PROPERTY LINE <br />R702.1(3) <br />WS <br />WATER SOFTENER <br />WASH <br />WASHER <br />• <br />WEEP SCREED PER R703.7.2.1 A MINIMUM <br />0.019-INCH (0.5 MM) (NO. 26 GALVANIZED SHEET <br />GAGE), CORROSION -RESISTANT WEEP SCREED OR <br />PLASTIC WEEP SCREED, WITH A MINIMUM <br />VERTICAL ATTACHMENT FLANGE OF 31/2 INCHES <br />(89 MM) SHALL BE PROVIDED AT OR BELOW THE <br />j <br />FOUNDATION PLATE LINE ON EXTERIOR STUD <br />WALLS IN ACCORDANCE WITH ASTM C926. THE <br />WEEP SCREED SHALL BE PLACED NOT LESS THAN <br />4 INCHES (102 MM) ABOVE THE EARTH OR 2 INCHES <br />(51 MM) ABOVE PAVED AREAS AND SHALL BE OF A <br />- - --- - <br />TYPE THAT WILL ALLOW TRAPPED WATER TO <br />DRAIN TO THE EXTERIOR OF THE BUILDING. THE <br />WEATHER -RESISTANT BARRIER SHALL LAP THE <br />ATTACHMENT FLANGE. THE EXTERIOR LATH SHALL <br />COVER AND TERMINATE ON THE ATTACHMENT <br />FLANGE OF THE WEEP SCREED <br />• <br />WATER -RESISTIVE BARRIERS PER R703.7.3, <br />WATER -RESISTIVE BARRIERS SHALL BE INSTALLED <br />AS REQUIRED IN SECTION R703.2 AND, WHERE <br />APPLIED OVER WOOD -BASED SHEATHING, SHALL <br />INCLUDE A WATER -RESISTIVE VAPOR -PERMEABLE <br />BARRIER WITH A PERFORMANCE AT LEAST <br />EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. <br />THE INDIVIDUAL LAYERS SHALL BE INSTALLED <br />INDEPENDENTLY SUCH THAT EACH LAYER <br />PROVIDES A SEPARATE CONTINUOUS PLANE AND <br />ANY FLASHING (INSTALLED IN ACCORDANCE WITH <br />SECTION R703A) INTENDED TO DRAIN TO THE <br />WATER -RESISTIVE BARRIER IS DIRECTED <br />BETWEEN THE LAYERS <br />GENERAL NOTES <br />• ALL CONSTRUCTION SHALL MEET THE LATEST <br />EDITION OF CODES ADOPTED BY THE LOCAL <br />GOVERNING AGENCIES <br />• PER FBC R302.5 NO OPENINGS FROM A PRIVATE <br />j GARAGE ARE PERMITTED DIRECTLY INTO SLEEPING <br />I AREAS, ALL OPENINGS SHALL HAVE SOLID WOOD, <br />INSULATED STEEL OR 20 MIN. FIRE RATED DOORS <br />j NOT LESS THAN 1-3/8 INCHES THICKNESS, EQUIPPED <br />WITH A SELF CLOSING DEVICE. ALL DUCTS IN THE <br />GARAGE OR PENETRATING THE WALL OR CEILING <br />SEPARATING THE GARAGE AND DWELLING SHALL BE <br />CONSTRUCTED OF MIN. 26 GA. SHEET METAL, 1 INCH <br />MINIMUM RIGID CLASS 0 OR 1 DUCT BOARD, OR <br />OTHER APPROVED MATERIAL AND SHALL HAVE NO <br />OPENINGS INTO THE GARAGE <br />i <br />• PER FBC TABLE R-302.6 GARAGE SHALL BE <br />SEPARATED FROM RESIDENCE AND ITS ATTIC W/ <br />MIN. 112" GYP BOARD ATTACHED IN ACCORDANCE <br />WITH TABLE R702.3.5. HABITABLE ROOMS SHALL BE <br />SEPARATED FROM ROOM ABOVE W/ MIN 5/8" TYPE <br />I <br />"X" GYP BOARD, WHERE THE SEPARATION IS A <br />FLOOR -CEILING ASSEMBLY. ANY STRUCTURE <br />SUPPORTING THE ASSEMBLY SHALL BE PROTECTED <br />W/ MIN 1/2" GYP BOARD <br />• PER FBC R302.12 IN COMBUSTIBLE CONSTRUCTION <br />WHERE THERE IS USEABLE SPACE BOTH ABOVE <br />AND BELOW THE CONCEALED SPACE OF A <br />FLOOR/CEILING ASSEMBLY, DRAFT STOPS SHALL BE <br />INSTALLED SO THAT THE AREA OF THE CONCEALED <br />SPACE DOES NOT EXCEED 1,000 SQUARE FEET. <br />j DRAFT STOPPING SHALL DIVIDE THE CONCEALED <br />SPACE INTO APPROXIMATELY EQUAL AREAS AND <br />INSTALLED PER FBC R302.12 & R302.12.1 <br />• PER FBC R-312.1 PORCHES, BALCONIES OR RAISED <br />FLOOR SURFACES LOCATED MORE THAN 30" ABOVE <br />FINISHED FLOOR OR GRADE SHALL HAVE GUARDS <br />! NOT LESS THAN 36" IN HEIGHT. PER FBC R-312.1.2 <br />OPEN SIDES OF STAIRS WITH A TOTAL RISE OF <br />MORE THAN 30" ABOVE FINISHED FLOOR OR GRADE <br />SHALL HAVE GUARDS NOT LESS THAN 34" IN HEIGHT <br />MEASURED VERTICALLY FROM THE NOSING OF THE <br />TREADS <br />I <br />i • PER FBC R-312.1.3 REQUIRED GUARDS ON OPEN <br />SIDES OF STAIRWAYS, RAISED FLOOR AREAS, <br />BALCONIES AND PORCHES SHALL HAVE <br />INTERMEDIATE RAILS OR ORNAMENTAL CLOSURES <br />WHICH DO NOT ALLOW PASSAGE OF A SPHERE 4" <br />OR MORE IN DIAMETER <br />• PER FBC R-308.4.5 GLAZING IN WALLS, ENCLOSURES <br />OR FENCES CONTAINING OR FACING HOT TUBS, <br />SPAS, WHIRLPOOLS, SAUNAS, STEAM ROOMS, <br />BATHTUBS, SHOWERS AND INDOOR OR OUTDOOR <br />SWIMMING POOLS WHERE THE BOTTOM EXPOSED <br />EDGE OF THE GLAZING IS LESS THAN 60 INCHES <br />MEASURED VERTICALLY ABOVE ANY STANDING OR <br />WALKING SURFACE, SHALL BE CONSIDERED A <br />HAZARDOUS LOCATION. G.C. TO VERIFY IF <br />HOMEOWNER SELECTS ANY OF THESE ITEMS <br />LISTED. IF ANY OF THESE ITEMS LISTED IS <br />INSTALLED, SUCH GLAZING FACING THOSE ITEMS IS <br />j TO BE TEMPERED <br />• PER FBC R312.2, PROVIDE WINDOW FALL <br />PROTECTION IN ACCORDANCE WITH R312.2.1 AND <br />R312.2.2 <br />• GAS OPT. PER COMMUNITY. VERIFY WITH BLDR <br />.I <br />• C.J. = RECOMMENDED MASONRY CONTROL JOINT <br />LOCATION <br />� • ALL FINISHES, MATERIALS, HOUSEWRAP, WINDOW <br />AND DOOR FLASHING, TAPING AND SEALANTS TO BE <br />INSTALLED PER BUILDER PROVIDED <br />SPECIFICATIONS OR MFR WRITTEN INSTRUCTIONS <br />I • ALL FINISH DETAILS & TYPICAL PLAN NOTES <br />PROVIDED BY BUILDER IN ACCORDANCE WITH <br />TYPICAL BUILDER SPECIFICATIONS <br />• REFER TO STRUCTURAL ENGINEERING DRAWINGS <br />FOR ALL EXTERIOR WALL STUD SPECIES, SIZES AND <br />j SPACING <br />ti <br />LID o <br />ti <br />O ° <br />U) APEX <br />W <br />W <br />Z_ qj <br />U <br />m <br />w <br />W <br />W <br />Z <br />0 tds W N <br />Q true design studios <br />O <br />J 9000 REGENCY SQUARE BLVD. N <br />u' SUITE 100, JACKSONVILLE, FL 32211 <br />ZO 904.821.5200 p <br />s✓ <br />O <br />11HOMON' <br />U <br />O <br />lL <br />U <br />Z_ <br />O <br />J <br />Z <br />U <br />W <br />x <br />W <br />Q VJ <br />Q M w <br />W <br />m 1111111111111111101 <br />0 ` W <br />w O Cn <br />O F <br />w Q O <br />z <br />m > o <br />W W <br />Z Q <br />0 M w mow�// a <br />f= LL <br />U LL W 0 <br />LL <br />Q <br />W x <br />0 <br />O <br />O <br />0 <br />Z <br />= W <br />U ~ <br />Z <br />Abbott Park rt <br />x a <br />W — - U_ <br />a LOT 002-02-A W <br />Q- -- - - - -- -� <br />U <br />0 <br />W <br />PROJECT NO: <br />2020.001719 Z <br />DRAWN: <br />SLC w <br />CHKD: U_ <br />JAC O <br />AR <br />0 <br />0 <br />uO <br />w <br />J <br />Q <br />U <br />U) <br />U) <br />O <br />Z_ <br />0 <br />U) <br />02-26-2020 O <br />Z <br />REVISIONS: <br />No. Description Date LU <br />w <br />U) <br />- - - w <br />w <br />-- J <br />d <br />rn <br />O <br />AOOO Z <br />0 <br />0 <br />