CORNER OF <br />HOME <br />GARAGE SIDE <br />ROOF DIAPHRAGM NAILING SCHEDULE <br />RIDGE LINE 0_1 <br />15/32" CDX <br />PLYWOOD OR <br />7/16" OSB <br />RIDGE LINE <br />140 MPH (ult) 3 SECOND GUST EXPOSURE "C" WIND ZONE 140 MPH (ult) 3 SECOND GUST EXPOSURE "C" WIND ZONE <br />8d RING SHANK NAILS @ 6" O.C. & 8d RING SHANK NAILS @ 6" O.C. EDGES & <br />+ + + + + 4" O.C. @ GABLE END WALL OR GABLE TRUSS 8d RING SHANK NAILS @ 6" O.C. INTERMEDIATE a <br />0.113 INCH NOMINAL SHANK DIAMETER 0.113 INCH NOMINAL SHANK DIAMETER <br />RING DIAMETER OF 0.012 OVER SHANK DIAMETER RING DIAMETER OF 0.012 OVER SHANK DIAMETER <br />16 TO 20 RINGS PER INCH 16 TO 20 RINGS PER INCH <br />0.280 INCH FULL ROUND HEAD DIAMETER 0.280 INCH FULL ROUND HEAD DIAMETER <br />2 INCH NAIL LENGTH 2 INCH NAIL LENGTH <br />NOTE: FOR 8d RING SHANK NAILS 0.113x 2x 3/8" RING SHANK COIL GUN NAILS MAY BE USED <br />1) SEE STRUCTURAL NOTES FOR SHEATHING SPECIFICATIONS AND WIND SPEED. <br />2) END JOINTS OF THE ROOF SHEATHING SHALL BE STAGGERED AND OCCUR OVER FRAMING MEMBER. <br />3) SCHEDULE ASSUMES SHEATHING IS FASTENED DIRECTLY TO SOUTHERN YELLOW PINE OR DOUGLAS FIR OR BETTER. IF ROOF FRAMING CONSISTS <br />OF A LESSER GRADE OF LUMBER, CONTRACTOR MUST CONTACT ENGINEER OF RECORD FOR ALTERNATE NAILING PATTERN. <br />+ + <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ + <br />+ <br />+ + <br />+ + <br />+ + + + <br />+ <br />+ <br />+ <br />+ <br />+ + <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ + <br />+ + <br />+ + + + + + + <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ + <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ <br />+ + <br />+ + + <br />+ <br />+ <br />+ <br />+ <br />+ + <br />+ + <br />++ <br />+++ <br />++++++++ <br />+ <br />Backer and Filler Block Dimensions <br />BCI®Joist <br />Backer Block <br />Thickness <br />Filler Block Thickness <br />Series <br />3/4" or 7/el <br />5000s 1.8/1.7 <br />wood panels <br />Two 3/4" wood panels or 2 x <br />1-1/8" or two 1/2" <br />6000s 1.8/1.7 <br />wood panels <br />2 x _ + 5/8" or 3/4" wood panel <br />1-1/8" or two 1/2" <br />6500s 1.8/1.7 <br />wood Panels <br />2 x _ + 5/8" or 3/4" wood panel <br />1-1 /8" or two 1/2" <br />602.0 <br />wood panels <br />2 x _ + 5/8" or 3/4" wood panel <br />1902.0 <br />2 x _ lumber <br />Double 2 x _ lumber <br />DOUBLE JOIST CONSTRUCTION <br />(Not required if both loaded equally from above) <br />Filler blocking / <br />1/8" gap --� <br />FILL CELL <br />kn <br />w <br />FE <br />CONT. #5 > STD. 90" <br />HOOK <br />BAR <br />STD. 90" HOOK r BOND BEAM <br />BOND BEAM STEP <br />SCALE: N.T.S. <br />SIMPS( <br />w/(22)10d <br />NAILS TYP. GIRDER TRUSS <br />- CONT. #5 <br />BAR 2X TOP PLATE <br />5/8'9 <br />#5 CONT. THRU <br />FROM BOLT <br />FOUNDATION <br />TO HIGHEST <br />BOND BEAM <br />2 X B.U.0 <br />SIMPSON MGT <br />w/(22)10d <br />NAILS TYP. <br />INTERIOR/EXT WALL SEE <br />PLAN FOR MORE INFO <br />CONT. BASE PLATE <br />BEARING COLUMN <br />PLYWOOD FLOOR <br />SEE PLAN FOR REQ'D <br />COLUMN AND <br />SHEATHING PER PLAN <br />CONNECTION <br />TJI TO BE CUT TO ALLOW <br />FOR BLOCKING/TJI <br />MASONRY WALL OR <br />INTERIOR BRG. WALL <br />TJI PER PLAN <br />OTHERWISE SOLID <br />BLOCKING TO MATCH <br /># OF 2nd FLOOR <br />Solid block all posts from <br />STUDS <br />above to bearing below. <br />SECTION <br />@ INT. BRG. WALL <br />N.T.S. <br />1/8" min. 2" min. <br />2" max }Small <br />gap „ <br />• �4 max. <br />_V <br />i� <br />Clinch nails <br />when <br />possible <br />1) Support back of web during nailing to prevent damage to <br />web -flange connection. <br />2) Block solid between joists for full length of span. Tight fit � <br />7 <br />3) Leave 1/8" gap between top of filler blocking and bottom of top flange. Zx4/plywood/OSB web stiffener 2" min. <br />4) Place joists together and nail from each side with 2 rows of 10d nails required when indicated or 4" max. <br />2x_: CONTRACTOR TO PROVIDE 2x TO FILL THE HEIGHT at 12" o.c., clinched when possible. Stagger rows from opposite -Hangers with side nailing. <br />OF THE JOIST ASA REQUIRED LEAVING Ye" GAP @ TOP sides by 6". - Hangers with sides not containing WEB STIFFENER <br />top flange of joist. <br />DOUBLE JOIST CONNECTION - Birdsmouth cuts. N.T.S. <br />- Under 2nd floor column w/ loads <br />N.T.S. higher th-- 1 snnu, <br />SQUASH BLOCKS AT INTERIOR <br />BEARING <br />Vertical load transfer =1900 plf max along load bearing wall. <br />Load bearing wall must stack <br />* over squash=20 blocks and <br />Non -stacking walls <br />require additional wall or beam below.* <br />consideration. Check <br />local building <br />code for appropriate <br />details in One 10d box <br />areas=20 of high or---20 sinker <br />lateral load. nail each side <br />10'-0" at bearing. <br />TANK -LESS W/H <br />H C G <br />O O 0 <br />5'-0" <br />STUB -OUT FOR 1 r_�a � o <br />GAS METER O o `� <br />U <br />= <br />• MEASUREMENTS ARE FROM FINISHED FLOOR <br />• ROUGH -IN GAS TO RIGHT (ALWAYS) - 12" OFF -CENTER <br />• ROUGH -IN ELECTRIC TO LEFT (ALWAYS) - 12" OFF -CENTER <br />GAS CONNECTION DETAIL <br />"*ONLY APPLIES TO HILLSBOROUGH AND PASCO COUNTY"" <br />RAFTER SPAN TABLE <br />MEMBER SIZE AND SPACING <br />MAXIMUM LENGTH <br />MEMBER CONNECTIONS* <br />2" X 4" @ 16" O.C. <br />7'-5" <br />(2)16d TOENAILS <br />2" X 6" @ 16" O.C. <br />10'-8" <br />(2)16d TOENAILS <br />2" X 8" @ 16" O.C. <br />13'-9" <br />(3)16d TOENAILS <br />2" X 10" 16" O.C. <br />16'-5" <br />1 SIMPSON HTS20 OR (3 16d TOENAILS <br />2" X 12" 16" O.C. <br />19'-3" <br />(1) SIMPSON HTS20 OR 4 16d TOENAILS <br />2" X 4" @ 24" O.C. <br />6'-1" <br />(2)16d TOENAILS <br />2" X 6" @ 24" O.C. <br />8'-6" <br />(2)16d TOENAILS <br />2" X 8" @ 24" O.C. <br />11'-0" <br />(2)16d TOENAILS <br />2" X 10" @ 24" O.C. <br />13'-0" <br />(3)16d TOENAILS <br />2" X 12" @ 24" O.C. <br />15'-4" <br />(1) SIMPSON HTS20 OR (3)16d TOENAILS <br />* TOENAIL CONNECTIONS DESIGNED FOR SHEAR ONLY (i.e. RAFTER TO RIDGEBEAM). <br />** SOUTHERN YELLOW PINE, 55 PSF LOADING <br />Squash block <br />(2x4 minimum) <br />Bearing wall, Versa -Lam LVL or <br />Glulam Beam <br />NO HOLES (EXCEPT <br />KNOCKOUTS) ALLOWED <br />IN BEARING ZONES —� <br />DO NOT cut, notch <br />or drill flanges <br />Boise Joist Blocking <br />1IRP 3" Il ndl nails at R" n c <br />Q'/ Provide adequate bearing <br />for each lapped joist. <br />odnails SECTION @ INT. BRG. WALL <br />N.T.S. <br />MINIMUM SPACING = 2x GREATEST <br />D DIMENSION OF LARGEST HOLE <br />(see table below) (KNOCKOUT EXEMPTS) D <br />(see table below) <br />BLOCKING PANEL, INTERIOR <br />Vertical load transfer =1900 plf max. along bearing wall <br />Required on interior walls: -for vertical load transfer <br />when load bearing - for lateral support when joists <br />meet over wall, or wall stacks directly over wall or-t7 <br />beam below Load bearing wall must stack over <br />bl=11.1 <br />ocking and wall or beam below.* <br />t� Joist <br />When joists meet over wall, provide <br />1 3/4" minimum bearing for each. I -Joist can be offset <br />up to 3" to avoid <br />vertical plumbing <br />3" max <br />JOISTS OFFSET <br />Use 10dx3" nails at 6"o.c. for all joist <br />blocking panel *Non -stacking walls <br />require additional consideration.— <br />tD 6 <br />6„ A 1Y" ROUND HOLE MAY 6„ 6„ DO NOT CUT HOLES <br />BE CUT ANYWHERE IN CANTILEVER LARGER THAN 1Yz" <br />THE WEB. PROVIDE AT ROUND IN <br />LEAST 3" OF CLEARANCE CANTILEVERS. <br />FROM OTHER HOLES <br />MINIMUM DISTANCE FROM SUPPORT, LISTED BELOW, IS REQUIRED FOR ALL HOLED GREATER THAN 1Y" <br />8 <br />V-0" <br />1'-l" <br />1'-2" <br />1'-2" <br />1'-3" <br />1'-0" <br />1'-7" <br />1'A 1" <br />2'-4" <br />2'-9" <br />3'-2" <br />3'-7" <br />Any 16" joist 12 <br />V-0" <br />1'-1" <br />1'-2* <br />V-2" <br />V-3" <br />1'-9" <br />2'-4" <br />2'-11" <br />3'-7" <br />4'-2" <br />4'-9" <br />5'4" <br />Span (ft) 16 <br />V-0" <br />1'-1" <br />1'-2" <br />1'-2" <br />V-7" <br />2'•5" <br />3'-2" <br />3'-10" <br />4'-9" <br />5'-7" <br />6'-4" <br />T-2" <br />20 <br />V-0" <br />1'-1" <br />1'-2" <br />1'-2" <br />2'-0" <br />3'-0" <br />4'-0" <br />4'-10" <br />5'-11" <br />W-11" <br />7'-11" <br />8'-11" <br />24 <br />V-0" <br />1'-1 " <br />1'-2" <br />V-3" <br />2'-5" <br />3'-7" <br />4'-9" <br />5'-10" <br />7'-2" <br />8'4" <br />9'-6" <br />10'-9" <br />NOTES: <br />1. JOISTS MUST BE PROPERLY DESIGNED TO MEET BUILDING CODE REQUIREMENTS. <br />2. TABLE IS FOR UNIFORMLY LOADED MAXIMUM LOADS OF 40 PSL(LIVE) AND 15 PSF (DEAD) ON SIMPLE SPAN APPLICATIONS ONLY. <br />3. REFER TO JOIST SPECIFIER GUIDE FOR INSTALLATION AND OTHER INFO. <br />4. SELECT A TABLE ROW BASED ON JOIST DEPTH AND THE ACTUAL JOIST SPAN ROUNDED UP TO THE NEAREST TABLE SPAN. SCAN ACROSS <br />THE ROW TO THE COLUMN HEADED BY THE APPROPRIATE ROUND HOLE DIAMETER OR RECTANGULAR HOLE SIDE. USE THE LONGEST SIDE OF <br />A RECTANGULAR HOLE. THE TABLE VALUES IS THE CLOSEST THAT THE CENTERLINE OF THE NEAREST SUPPORT. <br />5. THE ENTIRE WEB MAY BE CUT OUT. DO NOT CUT THE FLANGES. HOLES APPLY TO EITHER SINGLE OR MULTIPLE JOISTS IN REPETITIVE <br />MEMBER CONDITIONS. <br />6. FOR MULTIPLE HOLES, THE AMOUNT OF UNCUT WEB BETWEEN HOLES MUST EQUAL AT LEAST TWICE THE DIAMETER (OR LONGEST SIDE) OF <br />THE LARGEST HOLE. <br />7. %" ROUND KNOCKOUTS IN THE WEB MAY BE REMOVED BY USING A SHORT PIECE OF METAL PIPE AND HAMMER. <br />8. HOLES MAY BE POSITIONED VERTICALLY ANYWHERE IN THE WEB. THE JOIST MAY BE SET WITH THE %" KNOCKOUT HOLES TURNED WITHER <br />UP OR DOWN. <br />9. THIS TABLE WAS DESIGNED TO APPLY TO THE DESIGN TO APPLY TO THE DESIGN CONDITIONS COVERED BY TABLES ELSEWHERE IN HIS <br />PUBLICATION. USE THE BC CALC SOFTWARE TO CHECK OTHER HOLE SIZES OR HOLES UNDER OTHER DESIGN CONDITIONS. IT MAY BE <br />POSSIBLE TO EXCEED THE LIMITATIONS OF THIS TABLE BY ANALYZING A SPECIFIC APPLICATION WITH THE BC CALC SOFTWARE. <br />HOLE CUTTING CHART <br />N.T.S. <br />N.T.S. <br />Web Stiffener Fastener Schedule <br />Joist BearingLocation <br />Series Depth End Intermediate <br />® <br />BC15000s <br />9-1/2" <br />11-7/8" <br />2-8d <br />2-8d <br />2-8d <br />3-8d <br />14" <br />2-8d <br />- <br />BCI 6000s® <br />BCI6500s® <br />9-1/2" <br />11-7/8" <br />2-8d <br />2-8d <br />2-8d <br />3-8d <br />14" <br />2-8d <br />5-8d <br />16" <br />2-8d <br />6-8d <br />BCI600 <br />11-7/8" <br />2-8d <br />3-8d <br />14" <br />2-8d <br />5-8d <br />16" <br />2-8d <br />6-8d <br />BCI90s® <br />-7 " <br />3-16d <br />3-16d <br />14" <br />5-16d <br />5-16d <br />16" <br />6-16d <br />6-16d <br />TYPICAL SIMPSON MGT TO <br />BUILT-UP COLUMN DETAIL <br />TYPICAL SIMPSON LUS/HUS/HUC <br />INSTALLATION <br />MIN. EMBEDMENT <br />SCHEDULE FOR <br />AND QUANTITY <br />)F FASTENERS <br />TYPICAL SIMPSON HETA20 / <br />Plumbing HETAL20 INSTALLATION <br />A/C CHASE 4" PVC <br />SLEEVE THRU STEM <br />WALL <br />Backer block (12" wide min.) — I <br />Nail with 10-10d nails. - <br />Install tight to top flange. SLEEVE THRU STEM ' <br />Joist hanger SEE PLAN FOR a . • • <br />FOUNDATION INFO ° <br />STEM FOUNDATION <br />\ Filler block. <br />Nail with <br />10-10d nails. <br />Backer block required where top <br />mount hanger load exceeds 250 lbs. <br />Install tight to top flange. <br />1/4"-2" gap <br />Backer Block <br />"Top Mount" "Face Mount" <br />Backer block shall be tight Backer block shall be tight <br />to bottom of top flange with to top of bottom flange with <br />1/4"-2" gap at top of bottom 1/4"-2" gap at bottom of top <br />flange. flange. <br />eb stiffner as <br />Web stiffeners are not required when top required if hanger <br />flange is laterally supported by joist hanger. doesn't meet <br />height <br />requirements <br />0.6 X Joist <br />r depth <br />I -JOISTS BUCKETS <br />N.T.S. <br />GRADE <br />. v <br />r— REINF. SEE PLAN <br />FINISH GRADE <br />j <br />A/C CHASE 4" PVC (2) #5 REBAR <br />SLEEVE THRU FOOTING <br />MONO FOUNDATION <br />TYP. FND. PENETRATIONS <br />SCALE: N.T.S. <br />SIMPSON HETA20 / HETAL20 <br />INSTALLATION @ MID SPAN <br />NOTE: <br />UPLIFT VALUE <br />IS BASED ON <br />S.P.F. <br />LOCATION OF <br />' SECOND H10A <br />SIMPSON H10A • • (WHEN <br />w/ (18)10d x 1 1/2" REQUIRED) <br />NAILS <br />UPLIFT =1015# <br />TYPICAL SIMPSON H10A <br />INSTALLATION <br />TYPICAL SIMPSON MTS <br />/ HTS INSTALLATION <br />TOP (2) #5's x 4' 0" <br />CENETERED @ PIPE <br />PENETRATION <br />PLUMBING LINE <br />PVC OR SCH40 SLEEVE <br />-L.L— SEE FND. PLN. <br />SIZE & REINF. <br />12" BELOW PIPE VERTICAL THRU FND. <br />GRADE <br />TOP (2) #5's x 4' 0"—\ <br />CENETERED @ PIPE <br />PENETRATION <br />PVC OR SCH40 SLEEVE <br />r—PLUMBING LINE <br />t0 Z A • v • <br />d <br />SEE FND. PLN. <br />SIZE & REINF. <br />PIPE PERPENDICULAR TO FND. <br />TOP (2) #5's x 4'-0" PVC OR SCH40 SLEEVE <br />CENETERED @ PIPE <br />PENETRATIONFl— <br />APLUMBING LINE <br />G a' ° <br />a <br />4' ° °a G <br />.4 q <br />° ° a e <br />v <br />SEE FND. PLN. <br />SIZE & REINF. <br />/ <br />aaf7it,��rf�' <br />• ,`�\,�1,alttttt <br />,. <br />CPV <br />c) ,gyp- <br />' F ••� • <br />••'••... <br />�. <br />.... <br />�srrrlluttt <br />To the best of the Engineers knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2017 Florida Building Code - <br />Residentlal 0th Edition. Engineers signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineers signature and seal. <br />F �E <br />8 �m 14 <br />N <br />0 CS O n 04N LL LL <br />040 <br />a co vi M W rn <br />aCL <br />d�ti: WO <br />'f. 'a co CA 0 W OF <br />0 <br />�mgo <br />_0911 _ <br />We o � 'O 00 <br />2EO1pj <o 0 <br />Z A W N O O 7 �aMZ 1 <br />ILILW N <br />z ° 0 000❑ <br />W <br />ZN c9 <br />z g <br />LL N <br />E3 <br />Z <br />(y 0 ILL <br />LU <br />11�N LU <br />OUJ <br />N c <br />V1 � <br />(z m <br />,U �• <br />x <br />U � <br />• <br />o <br />M <br />M <br />z <br />o <br />z <br />Zo <br />aLL <br />> <br />0� <br />z• <br />QE <br />O <br />E: V <br />(6 <br />t-- C1 <br />of <br />8 <br />9 V <br />a�W <br />o a <br />0 p <br />U <br />z <br />o <br />CN <br />°�$ <br />o <br />wz <br />¢ <br />� C <br />- ( <br />�o <br />Z <br />>z <br />z <br />Jb <br />�`z <br />rn <br />N Cn <br />1 <br />$9 <br />W <br />a <br />U <br />ado <br />yLL <br />aZ <br />ow <br />�� <br />= <br />o <br />gl <br />'_ <br />a <br />v <br />0 <br />12 <br />03 <br />T <br />L <br />of <br />0 <br />>� <br />M <br />■ - r_ <br />yT, <br />J <br />O <br />�1 <br />CD <br />L..L <br />2 <br />C <br />Z N <br />r <br />r*... <br />T r- <br />2 M o N <br />L.In <br />T­ <br />r <br />M <br />NO <br />o <br />z <br />z <br />r_ <br />E y <br />>u w <br />d <br />U _J Q p <br />JOB <br />NO : 20-0561 <br />SCALE : AS NOTED <br />SHEET NO. <br />SN 1 <br />