AIR TERMINAL SCHEDULE <br />SYMBOL <br />ADAPTER/NECK <br />SIZE <br />FACE SIZE <br />MAX CFM <br />MAX NC <br />MAX SP <br />THROW <br />RUNOUT <br />SIZE <br />MANUFACTURER/MODEL NO. <br />E-EX <br />--- <br />--- <br />--- <br />--- <br />--- <br />--- <br />--- <br />EXISTING TO REMAIN <br />EB <br />8"x8" <br />241lx24" <br />200 <br />28 <br />.05 <br />--- <br />8" 0/10"x6" <br />TITUS 50-F WITH EGG -CRATE CORE <br />R-EX <br />--- <br />--- <br />--- <br />--- <br />--- <br />--- <br />--- <br />EXISTING TO REMAIN <br />RPA <br />--- <br />12"x12" <br />300 <br />--- <br />--- <br />--- <br />--- <br />TITUS 50-F WITH EGG -CRATE CORE <br />RPB <br />--- <br />241lx24" <br />1500 <br />--- <br />--- <br />--- <br />--- <br />TITUS 50-F WITH EGG -CRATE CORE <br />S-EX <br />--- <br />--- <br />--- <br />--- <br />--- <br />--- <br />--- <br />EXISTING TO REMAIN <br />SA <br />6" 0/6"x6" <br />12"x12" <br />75 <br />20 <br />.07 <br />4-WAY <br />BLOW <br />6" 0/8"x4" <br />TITUS TDC <br />SB <br />8' Q1/9"x9" <br />241lx24" <br />230 <br />20 <br />.07 <br />4-WAY <br />BLOW <br />8" 0/10"x6" <br />TITUS TDC <br />AIR TERMINAL PERFORMANCE NOTES: <br />1. CONTRACTOR TO USE DUCT SPIN -IN FITTINGS WITH MANUAL VOLUME DAMPER EQUAL TO GENFLEX MODEL SM-2DEL OR APPROVED EQUAL. <br />2. FACE SIZE FOR CEILING MOUNTED AIR TERMINALS SHALL BE 24"x24" IN ALL LAY IN CEILING LOCATIONS TO FIT WITHIN GRIDS UNLESS OTHERWISE SPECIFIED. <br />3. ALL LINEAR SLOT DIFFUSERS SHALL BE CONCEALED MOUNT TYPE WITH ADJUSTABLE DISCHARGE. <br />4. PROVIDE INSULATED PLENUM - MPI-38 FOR ALL LINEAR SLOT DIFFUSERS. <br />CODE CRITERIA: <br />NOTE: <br />A. THIS LIST IS NOT INCLUSIVE OF ALL CODES AND STANDARDS THAT MAY <br />OR MAY NOT APPLY TO THIS PROJECT. <br />B. PERFORM WORK SPECIFIED IN SPECIFICATIONS IN ACCORDANCE WITH <br />STANDARDS LISTED BELOW INCLUDING AMENDMENTS OR REVISIONS. WHEN <br />THESE SPECIFICATIONS ARE MORE STRINGENT, THEY TAKE PRECEDENCE. IN <br />CASE OF CONFLICT, OBTAIN A DECISION FROM THE DESIGNER. <br />NFPA-70 (2011) <br />NATIONAL ELECTRICAL CODE <br />N F PA-72 (2010) <br />NATIONAL FIRE ALARM CODE <br />NFPA-90A (2012) <br />INSTALLATION OF AIR CONDITIONING AND VENTILATION SYSTEMS <br />NFPA-90B (2012) <br />INSTALLATION OF WARM AIR HEATING AND AIR CONDITIONING SYSTEMS <br />NFPA-91 (2010) <br />EXHAUST SYSTEMS FOR AIR CONVEYING OF VAPORS, GASES, MISTS, AND <br />NON-COMBUSTIBLE PARTICULATE SOLIDS <br />NFPA-96 (2011) <br />VENTILATION CONTROL AND FIRE PREVENTION OF COMMERCIAL COOKING <br />OPERATIONS. <br />NFPA-101 (2012) <br />LIFE SAFETY CODE <br />FLORIDA BUILDING CODE, BUILDING 5TH EDITION (2014) <br />FLORIDA BUILDING CODE, MECHANICAL 5TH EDITION (2014) <br />FLORIDA BUILDING CODE, PLUMBING 5TH EDITION (2014) <br />FLORIDA BUILDING CODE, TEST PROTOCOLS FOR HIGH WIND HURRIZANE <br />ZONES 5TH EDITION (2014) <br />FLORIDA BUILDING CODE, FUEL GAS 5TH EDITION (2014) <br />FLORIDA FIRE PREVENTION CODE 5TH EDITION (2014) <br />FLORIDA ACCESSIBILITY CODE (2014) <br />APPLICABLE STATE ENERGY CODE (2014) <br />STATE OF FLORIDA ADMINISTRATIVE CODE NO. 69A-3.012 AND 69A-60. <br />NOTE: WHERE THERE ARE DIFFERENCES BETWEEN SECTIONS OF THE <br />BUILDING AND MECHANICAL OR PLUMBING CODES, IT WILL BE ASSUMED <br />THAT THE BUILDING CODE TAKES PRECEDENCE. <br />MECHANICAL LEGEND: <br />MEDIUM PRESSURE TEE <br />RECTANGULAR DUCT TURNING DOWN <br />ROUND DUCT TURNING DOWN <br />DUCT TURNING DOWN TO SIDEWALL <br />REGISTER <br />DOUBLE LINE TO DUCTWORK <br />DUCT LINER IN LOW PRESSURE <br />DUCT OR DOUBLE WALL INSULATED <br />MEDIUM PRESSURE DUCT <br />BRANCH TAP OFF MAIN W/450 BOOT <br />FITTING OR SPIN -IN FITTING <br />W/DAMPER (LOW PRESSURE) <br />TRANSITION IN DUCT (NOT <br />DIRECTION OF AIRFLOW) <br />REGISTER TAPPING INTO BOTTOM <br />11 OF DUCT <br />FD <br />® FIRE DAMPER <br />® FIRE/SMOKE DAMPER <br />FSD <br />DUCT SMOKE DETECTOR <br />SD SMOKE DETECTOR <br />AD ACCESS DOOR <br />AFF ABOVE FINISHED FLOOR <br />BFC BELOW FINISHED FLOOR <br />VFD VARIABLE FREQUENCY DRIVE <br />TAD TRANSFER AIR DUCT <br />TAO TRANSFER AIR OPENING <br />BAS BUILDING AUTOMATION CONTROL SYSTEM <br />© PRESSURE SENSOR <br />MD MOTORIZED DAMPER <br />DUCT TERMINATION <br />450 FULL RADIUS TURN <br />SQUARE ELBOW <br />jj <br />W/TURNING VANES <br />FULL RADIUS TURN <br />CO <br />CO2SENSOR <br />OTHERMOSTAT <br />OH <br />HUMIDISTAT <br />MVDF <br />MANUAL VOLUME DAMPER <br />VAV <br />VARIABLE VOLUME BOX <br />EA <br />INDICATES A SIZE "A" EXHAUST <br />100 <br />REGISTER SET FOR 100 CFM <br />RB INDICATES A SIZE "B" RETURN <br />200 REGISTER SET FOR 200 CFM <br />SB INDICATES A SIZE "B" SUPPLY <br />200 DIFFUSER SET FOR 200 CFM <br />® SUPPLY DIFFUSER <br />zRETURN GRILLE <br />® EXHAUST GRILLE <br />UNDERCUT DOOR 3/4" <br />UNLESS OTHERWISE NOTED <br />PIPING LEGEND: <br />CD MOISTURE CONDENSATE DRAIN LINE <br />L REFRIGERANT LIQUID <br />S REFRIGERANT SUCTION <br />HGR HOT GAS REHEAT <br />-� DIRECTION OF WATER FLOW <br />PIPE TURNING DOWN <br />PIPE TURNING UP <br />PIPE SHUT OFF VALVE <br />MECHANICAL GENERAL NOTES: <br />CONTRACT REQUIREMENTS AFFECTING ALL TRADES: <br />IT IS THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR AND EACH <br />SUBCONTRACTOR TO REVIEW ALL DRAWINGS TO ASSURE COORDINATION OF <br />ALL WORK AFFECTING EACH TRADE. <br />1. FIBERGLASS DUCT INSULATION SHALL NOT PENETRATE RATED WALLS. <br />SPACE BETWEEN STUDS, HEADERS AND DUCT SHALL BE PACKED WITH <br />MINERAL FIBER SAFING INSULATION. WHERE A FIRE DAMPER IS REQUIRED <br />THE SPACE BETWEEN THE SLEEVE AND THE STUDS OR HEADERS SHALL BE <br />OF THE PROPER CLEARANCE FOR THE SIZE OF THE DUCT IN ACCORDANCE <br />WITH SMACNA REQUIREMENTS. FIRE DAMPER SLEEVES SHALL BE INSTALLED <br />AND SECURED IN ACCORDANCE WITH SMACNA STANDARDS. FIRE DAMPERS <br />SHALL BE INSTALLED IN THE PLANE OF THE RATED ASSEMBLY AND BE U.L. <br />LISTED AS AN ASSEMBLY COMPLYING WITH U.L. 555. <br />2. CONTRACTOR SHALL FURNISH AND INSTALL ACCESS PANELS IN WALLS, <br />NON -ACCESSIBLE CEILINGS, DUCTWORK AS REQUIRED AND ELSEWHERE AS <br />INDICATED ON CONTRACT DOCUMENTS WHERE SERVICE ADJUSTMENT TO <br />MECHANICAL, PLUMBING OR ELECTRICAL EQUIPMENT IS REQUIRED. <br />3. COORDINATE INSTALLATION OF PLUMBING, VENT STACKS AND CONDUIT TO <br />PERMIT INSTALLATION OF RECESSED TOILET ACCESSORIES, FIRE <br />EXTINGUISHER CABINETS AND OTHER RECESSED EQUIPMENT. WHERE SUCH <br />ITEMS ARE RECESSED IN CORRIDOR, SMOKE OR FIRE/SMOKE WALLS THEY <br />SHALL BE INSTALLED IN A FIVE -SIDE ENCLOSURE. <br />4. THE CONTRACTOR SHALL ASSEMBLE A LOG OF CERTIFICATES AND <br />INSPECTIONS ORGANIZED IN C.S.I. FORMAT PRIOR TO FINAL INSPECTION <br />INCLUDING MANUFACTURER'S CERTIFICATION OF FLAME SPREAD, SMOKE AND <br />RADIANT PANEL TEST, AND CERTIFICATE OF TESTS FOR MEDICAL GAS, <br />RADIATION SHIELDING, HVAC TEST AND BALANCE, FIRE ALARM, FIRE PUMP, <br />EMERGENCY GENERATOR, ETC. AS APPLICABLE TO THE PROJECT AND MAKE <br />AVAILABLE AT FINAL INSPECTION. <br />5. CONTRACTOR SHALL VERIFY CONSTRUCTION IS COMPLETE AND IN <br />ACCORDANCE WITH THE CONTRACT DOCUMENTS PRIOR TO FINAL <br />INSPECTION. NOTIFY THE DESIGNER PRIOR TO INSPECTION OF ANY <br />DEFICIENCIES OBSERVED. <br />6. CONTRACTOR SHALL SEAL ALL METAL JOINTS WITH GLASSFAB AND MASTIC <br />PRIOR TO INSTALLATION OF INSULATION AND PRESSURE TEST DUCTWORK <br />FOR LEAKAGE. <br />7. MANUAL VOLUME DAMPERS SHALL BE PROVIDED AT ALL RUNOUTS TO <br />SUPPLY AIR DIFFUSERS, RETURN AIR REGISTERS, EXHAUST AIR REGISTERS, <br />DIVISIONS IN DUCTWORK (SUPPLY, RETURN AND EXHAUST), AND ELSEWHERE <br />NOTED ON PLANS AND IN SPECIFICATIONS FOR BALANCING SYSTEM. <br />DAMPERS IN REGISTERS GRILLES AND DIFFUSERS ARE PROVIDED FOR FINAL <br />ADJUSTMENTS DURING TEST AND BALANCING. DO NOT RELY ON <br />DISTRIBUTION DEVICE DAMPERS FOR SYSTEM BALANCING. <br />8. COORDINATION OF ALL TRADES IS OF THE UTMOST IMPORTANCE. CEILING <br />SPACE TO ROUTE WORK IN IS MINIMAL AT BEST. CONTRACTOR SHALL LAY <br />OUT SYSTEMS IN CONJUNCTION WITH ALL TRADES TO AVOID CONFLICTS <br />PRIOR TO INSTALLATION OF WORK. <br />9. PLUMBING VENT STACKS AND HVAC EXHAUST SHALL BE KEPT A MINIMUM OF <br />25' FROM ANY OUTSIDE AIR INTAKE. OUTSIDE AIR INTAKE MAY BE AS CLOSE <br />AS 10' AWAY FROM EXHAUST FOR NON -HEALTHCARE FACILITIES. <br />10. CONTRACTOR SHALL REVIEW PLACEMENT OF ALL HVAC EQUIPMENT ON <br />ROOF WITH STRUCTURAL DRAWINGS PRIOR TO INSTALLATION. <br />11. PROVIDE SEALED ROOF CURB AROUND ALL DUCTWORK AND PIPING <br />PENETRATIONS THRU ROOF. <br />12. CONTRACTOR SHALL MAINTAIN A MINIMUM OF 6" CLEARANCE BETWEEN <br />DUCTWORK, PIPING, AND ANY PRIORITY WALLS (TWO HOUR FIRE, TWO HOUR <br />FIREISMOKE, ONE HOUR SMOKE). <br />13. PROVIDE ACCESS DOORS IN DUCTWORK FOR FIRE DAMPERS, REHEAT <br />COILS, DUCT MOUNTED SMOKE DETECTORS, AND ELSEWHERE WHERE <br />SERVICE OR ADJUSTMENT TO MECHANICAL, PLUMBING OR ELECTRICAL <br />EQUIPMENT IS REQUIRED. <br />14. PROVIDE "YOUNG" REMOTE VOLUME REGULATOR FOR ALL DAMPERS <br />LOCATED ABOVE INACCESSIBLE CEILINGS. REFER TO ARCHITECTURAL <br />DRAWINGS FINISH SCHEDULE FOR CEILING TYPES. <br />15. ALL OUTSIDE AIR INTAKES ON ROOF SHALL BE KEPT A MINIMUM OF 36" <br />ABOVE ROOF FOR HEALTHCARE FACILITIES, 12" FOR NON -HEALTHCARE. <br />PROVIDE DUCTWORK OR CURB EXTENSIONS AS NECESSARY TO PROVIDE <br />CLEARANCE. <br />16. INSTALL SMOKE DETECTORS IN RETURN AIR DUCTWORK (PRIOR TO <br />DILUTION OF OUTSIDE AIR) AND SUPPLY AIR DUCTWORK WITH SAMPLING <br />TUBES IN AIRSTREAM ACCORDING TO MANUFACTURER'S INSTALLATION <br />REQUIREMENTS. FOR ALL DUCT MOUNTED SMOKE DETECTORS PROVIDE AN <br />AIR DIFFERENTIAL TEST ACROSS DETECTOR SAMPLING TUBES, RELOCATE OR <br />ADJUST THE SAMPLING TUBES WHERE NECESSARY TO PROVIDE AN AIR <br />DIFFERENTIAL WITHIN THE ACCEPTABLE RANGE ESTABLISHED BY THE <br />MANUFACTURER. RESULTANT TEST DATA SHALL BE MADE AVAILABLE AT THE <br />FINAL SURVEY AND WILL BE INCLUDED IN LOG OF CERTIFICATES. DUCT <br />MOUNTED SMOKE DETECTORS TO BE FURNISHED AND INSTALLED BY <br />MECHANICAL CONTRACTOR AND WIRED BY ELECTRICAL CONTRACTOR. <br />17. MAINTAIN THE CLEAR SPACES AROUND, OVER AND UNDER EQUIPMENT, <br />ELECTRICAL PANELS, SYSTEMS AND SYSTEM COMPONENTS IN CEILING <br />CAVITIES NECESSARY FOR CONVENIENT OBSERVATION, OPERATION AND <br />MAINTENANCE. PAY SPECIAL ATTENTION TO ACCESS TO FIRE DAMPERS, FIRE <br />AND SMOKE DAMPERS, DUCT SMOKE DETECTORS, ELECTRIC DUCT HEATER <br />CONTROLS, FILTER ACCESS DOORS, MEDICAL GAS VALVES, FIRE <br />PROTECTION SYSTEM VALVES, ETC. DO NOT INSTALL DUCTWORK OR PIPING <br />OF ANY KIND ABOVE ELECTRICAL PANELS PER NEC. COORDINATE AND FIELD <br />VERIFY FINAL LOCATION OF ELECTRICAL PANELS WITH ELECTRICAL <br />CONTRACTOR BEFORE INSTALLATION OF DUCTWORK AND PIPING. <br />18. DO NOT INSTALL EQUIPMENT, SYSTEMS OR SYSTEM COMPONENTS <br />WHERE THEY MAY ENCROACH ON THE CLEAR SPACES NECESSARY FOR <br />OPERATION OR MAINTENANCE OF ITEMS INSTALLED BY OTHER TRADES <br />WITHOUT CONFIRMING THAT THE CLEAR SPACE REQUIREMENTS OF THE <br />OTHER TRADE WILL BE MAINTAINED. <br />19. WHERE THE WORK OF OTHER TRADES MAY ENCROACH ON CLEAR <br />SPACES REQUIRED FOR WORK INSTALLED UNDER THESE SECTIONS, <br />COORDINATE WITH THE OTHER TRADES AND THE GENERAL CONTRACTOR TO <br />MAINTAIN THE REQUIRED CLEAR SPACES. <br />20. PRIOR TO THE FINAL INSPECTION, DEMONSTRATE TO THE OWNER THAT <br />ACCESS AND CLEAR SPACES FOR ALL INSTALLED ITEMS THAT REQUIRE <br />ROUTINE OBSERVATION, OPERATION AND MAINTENANCE HAVE BEEN <br />MAINTAINED. <br />21. MECHANICAL EQUIPMENT AND PIPING INSTALLED ON ROOF SHALL BE <br />SECURED TO MEET FBC WIND LOADING REQUIREMENTS. <br />22. UNLESS SPECIFIED BY THE ARCHITECT, EXTERIOR AIR LOUVERS SHALL BE <br />RUSKIN MODEL ELF6375DXD (NOA 12-0601.22) OR APPROVED EQUAL <br />CONSTRUCTED OF EXTRUDED ALUMINUM WITH INSECT SCREEN. DUCT <br />CONNECTION SHALL BE SLOPED TOWARD EXTERIOR. <br />23. ALL THROUGH PENETRATTION FIRESTOP SYSTEMS SHALL BE INSTALLED <br />BY AN EXPERIENECED INSTALLER PER THE MANUFACTURERS INSTALLATION <br />INSTRUCTIONS. <br />24. REFER TO SPECIFICATIONS SECTION 15890 AND 15910 FOR SHEETMETAL - <br />LOW PRESSURE DUCTWORK AND SHEETMETAL SPECIALTIES MATERIAL, <br />SEALING AND INSTALLATION REQUIREMENTS. <br />MECHANICAL GENERAL NOTES CONT.:1 <br />25. REFER TO SPECIFICATIONS SECTION 15250 FOR DUCT AND REFRIGERANT <br />PIPING INSULATION MATERIAL, SEALING AND INSTALLATION REQUIREMENTS. <br />26. PROVIDE COMMISSIONING OF NEW HVAC SYSTEMS OVER 40 TON TOTAL <br />CAPACITY PER FLORIDA ENERGY EFFICIENCY CODE. <br />27. MECHANICAL EQUIPMENT SHALL NOT BE INSTALLED IN A LOCATION <br />WHERE SUBJECT TO MECHANICAL DAMAGE UNLESS PROTECTED BY <br />APPROVED BARRIERS. MECHANICAL EQUIPMENT AND SUPPORTS THAT ARE <br />EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND <br />PRESSURES IN ACCORDANCE WITH FLORIDA BUILDING CODE. <br />HIGH WIND <br />PROTECTION OF EQUIPMENT: <br />IN COMPLIANCE WITH FMC-301.15; MECHANICAL EQUIPMENT, APPLIANCES <br />AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND <br />INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE <br />WITH FBC. APPLIANCES SHALL NOT BE INSTALLED IN A LOCATION WHERE <br />SUBJECT TO MECHANICAL DAMAGE UNLESS PROVIDED WITH PROTECTION <br />FROM HIGH -VELOCITY IMPACT IN ACCORDANCE WITH FMC-303.4. THE <br />PROTECTIVE BARRIER MUST BE TESTED AND LABELED AS MEETING THE <br />HIGH -VELOCITY IMPACT TEST OF FBC SECTIONS 1626.2 OR 1626.3 OR MUST <br />BE ONE OF THE FOLLOWING: <br />1. EXTERIOR CONCRETE MASONRY WALLS OF MINIMUM NOMINAL 8-INCH <br />THICKNESS, CONSTRUCTED IN ACCORDANCE WITH CHAPTER 21 (HIGH - <br />VELOCITY HURRICANE ZONES) OF FBC. <br />2. EXTERIOR FRAME WALLS OR GABLE ENDS CONSTRUCTED IN <br />ACCORDANCE WITH CHAPTER 22 AND CHAPTER 23 (HIGH -VELOCITY <br />HURRICANE ZONES) OF FBC, SHEATHED WITH A MINIMUM 19/32-INCH CD <br />EXPOSURE 1 PLYWOOD AND CLAD WITH WIRE LATH AND STUCCO <br />INSTALLED IN ACCORDANCE WITH CHAPTER 25 OF FBC. <br />3. EXTERIOR FRAME WALLS AND ROOFS CONSTRUCTED IN ACCORDANCE <br />WITH CHAPTER 22 (HIGH -VELOCITY HURRICANE ZONES) OF FBC SHEATHED <br />WITH A MINIMUM 24-GAGE RIB DECK -TYPE MATERIAL AND CLAD WITH AN <br />APPROVED WALL FINISH. <br />4. EXTERIOR REINFORCED CONCRETE ELEMENTS CONSTRUCTED OF SOLID <br />NORMAL WEIGHT CONCRETE (NO VOIDS), DESIGNED IN ACCORDANCE WITH <br />CHAPTER 19 (HIGH -VELOCITY HURRICANE ZONES) OF FBC AND HAVING A <br />MINIMUM 2-INCH THICKNESS. <br />5. ROOF SYSTEMS CONSTRUCTED IN ACCORDANCE WITH CHAPTER 22 OR <br />CHAPTER 23 (HIGH -VELOCITY HURRICANE ZONES) OF FBC, SHEATHED WITH <br />A MINIMUM 19/32-INCH CD EXPOSURE 1 PLYWOOD OR MINIMUM NOMINAL 1- <br />INCH WOOD DECKING AND SURFACED WITH AN APPROVED ROOF SYSTEM <br />INSTALLED IN ACCORDANCE WITH CHAPTER 15 OF FBC. <br />ALL CONNECTORS SHALL BE SPECIFIED BY THE BUILDING STRUCTURAL <br />DESIGNER OF RECORD FOR ALL LOADS EXCEPT IMPACT. <br />GENERATOR FUEL OIL TANK ENCLOSURE, PIPING, VALVES, AND OTHER <br />APPURTENANCES SHALL BE SECURED AND PROTECTED FOR CONTINUED <br />OPERATION AND HAVE HURRICANE WIND RESISTANCE AND HURRICANE <br />DEBRIS IMPACT PROTECTION DESIGNED BY A STRUCTURAL ENGINEER TO <br />COMPLY WITH FBC. <br />PRIOR TO FINAL ACCEPTANCE OF PROJECT, GENERAL CONTRACTOR SHALL <br />PROVIDE WIND RESISTANCE AND HIGH -VELOCITY IMPACT PROTECTION <br />DESIGN DOCUMENTS THAT ARE SIGNED, SEALED, AND DATED BY A <br />STRUCTURAL ENGINEER REGISTERED IN THE STATE OF FLORIDA IN <br />COMPLIANCE WITH FBC. <br />PROJECT COORDINATION NOTES: <br />THE CONSTRUCTION PHASING OF THIS PROJECT IS OF THE UTMOST <br />IMPORTANCE. ALL CONTRACTORS FOR ALL DIVISIONS OF THE WORK SHALL <br />GUARANTEE THAT THEIR WORK IS IN ACCORD WITH THE PHASING PLANS <br />SHOWN IN THE ARCHITECTURAL CONTRACT DOCUMENTS. SHOULD IT BE <br />NECESSARY TO ACCOMPLISH WORK IN AREAS WHICH ARE NOT INCLUDED <br />IN THE PHASING PLANS, SUCH WORK SHALL BE DONE WITH THE MINIMUM <br />OF DISTURBANCES THAT IS POSSIBLE AND WITHOUT CAUSING THE <br />INTERRUPTION OF EXISTING SERVICES. ALL SERVICE INTERRUPTIONS THAT <br />ARE ESSENTIAL TO THE WORK SHALL BE SCHEDULED WITH THE ARCHITECT <br />AND, THEREBY, WITH THE OWNER. ALL CONTRACTORS FOR ALL TRADES <br />SHALL COOPERATE AND COORDINATE THEIR WORK TO ALLOW THE <br />COMPLETION OF ALL WORK WITH THE LEAST POSSIBLE NUMBER ON <br />INTERFERENCE'S WITH THE SERVICES OF THE EXISTING BUILDING. <br />THE DESIGN DRAWINGS OF ALL CATEGORIES AND TRADES <br />(ARCHITECTURAL, STRUCTURAL, PLUMBING, FIRE PROTECTION, MEDICAL <br />GAS, MECHANICAL, HEATING, VENTILATING AND AIR CONDITIONING AND <br />ELECTRICAL) AND ALL SPECIFICATIONS AND SHOP DRAWINGS MUST BE <br />COORDINATED AND BE VIEWED IN CONNECTION AND CONJUNCTION WITH <br />EACH OTHER TO INSURE THE PROPER LOCATION OF ALL DEVICES AND <br />EQUIPMENT. MAKE PARTICULAR NOTE OF LOCATIONS AND DIMENSIONS <br />SHOWN ON THE ARCHITECTURAL FLOOR PLANS AND ELEVATIONS. <br />M0.1 <br />MECHANICAL - LEGEND, NOTES, ETC... <br />M5.1 <br />HVAC - PARTIAL FIRST FLOOR PLANS <br />M12.1 <br />MECHANICAL - SCHEDULES <br />M14.1 <br />MECHANICAL - DETAILS <br />M14.2 <br />MECHANICAL - DETAILS <br />REVISIONS <br />v <br />. <br />v <br />N 00 <br />Y N <br />CM <br />F <br />v ro ti u <br />� vi <br />" <br />E x <br />it <br />o C: <br />g C5 <br />u • N t <br />¢ <br />E <br />Qom_. o <br />00 <br />I-� <br />0 = N 3 <br />o <br />o a <br />N <br />Z <br />OV/ <br />z <br />U <br />W <br />L.L <br />F <br />V) <br />U <br />ZO <br />00 <br />U <br />V_ <br />c Z <br />O <br />.� J <br />a V <br />C4 <br />4)M <br />J <br />Wx <br />n- <br />Q <br />a <br />� <br />o V <br />sn <br />m O <br />U Lu <br />C <br />a H <br />O <br />Wz <br />d Q <br />�• <br />CO t <br />O <br />M N <br />Q. <br />O � <br />~ <br />L Oa. <br />J <br />LL. <br />Date: 06. 03. 16 <br />Scale: AS NOTED <br />Project Mgr: DAN <br />Drawn: DEG <br />Job: 16-062 <br />Sheet <br />Mo* I <br />