AIR TERMINAL SCHEDULE
<br />SYMBOL
<br />ADAPTER/NECK
<br />SIZE
<br />FACE SIZE
<br />MAX CFM
<br />MAX NC
<br />MAX SP
<br />THROW
<br />RUNOUT
<br />SIZE
<br />MANUFACTURER/MODEL NO.
<br />E-EX
<br />---
<br />---
<br />---
<br />---
<br />---
<br />---
<br />---
<br />EXISTING TO REMAIN
<br />EB
<br />8"x8"
<br />241lx24"
<br />200
<br />28
<br />.05
<br />---
<br />8" 0/10"x6"
<br />TITUS 50-F WITH EGG -CRATE CORE
<br />R-EX
<br />---
<br />---
<br />---
<br />---
<br />---
<br />---
<br />---
<br />EXISTING TO REMAIN
<br />RPA
<br />---
<br />12"x12"
<br />300
<br />---
<br />---
<br />---
<br />---
<br />TITUS 50-F WITH EGG -CRATE CORE
<br />RPB
<br />---
<br />241lx24"
<br />1500
<br />---
<br />---
<br />---
<br />---
<br />TITUS 50-F WITH EGG -CRATE CORE
<br />S-EX
<br />---
<br />---
<br />---
<br />---
<br />---
<br />---
<br />---
<br />EXISTING TO REMAIN
<br />SA
<br />6" 0/6"x6"
<br />12"x12"
<br />75
<br />20
<br />.07
<br />4-WAY
<br />BLOW
<br />6" 0/8"x4"
<br />TITUS TDC
<br />SB
<br />8' Q1/9"x9"
<br />241lx24"
<br />230
<br />20
<br />.07
<br />4-WAY
<br />BLOW
<br />8" 0/10"x6"
<br />TITUS TDC
<br />AIR TERMINAL PERFORMANCE NOTES:
<br />1. CONTRACTOR TO USE DUCT SPIN -IN FITTINGS WITH MANUAL VOLUME DAMPER EQUAL TO GENFLEX MODEL SM-2DEL OR APPROVED EQUAL.
<br />2. FACE SIZE FOR CEILING MOUNTED AIR TERMINALS SHALL BE 24"x24" IN ALL LAY IN CEILING LOCATIONS TO FIT WITHIN GRIDS UNLESS OTHERWISE SPECIFIED.
<br />3. ALL LINEAR SLOT DIFFUSERS SHALL BE CONCEALED MOUNT TYPE WITH ADJUSTABLE DISCHARGE.
<br />4. PROVIDE INSULATED PLENUM - MPI-38 FOR ALL LINEAR SLOT DIFFUSERS.
<br />CODE CRITERIA:
<br />NOTE:
<br />A. THIS LIST IS NOT INCLUSIVE OF ALL CODES AND STANDARDS THAT MAY
<br />OR MAY NOT APPLY TO THIS PROJECT.
<br />B. PERFORM WORK SPECIFIED IN SPECIFICATIONS IN ACCORDANCE WITH
<br />STANDARDS LISTED BELOW INCLUDING AMENDMENTS OR REVISIONS. WHEN
<br />THESE SPECIFICATIONS ARE MORE STRINGENT, THEY TAKE PRECEDENCE. IN
<br />CASE OF CONFLICT, OBTAIN A DECISION FROM THE DESIGNER.
<br />NFPA-70 (2011)
<br />NATIONAL ELECTRICAL CODE
<br />N F PA-72 (2010)
<br />NATIONAL FIRE ALARM CODE
<br />NFPA-90A (2012)
<br />INSTALLATION OF AIR CONDITIONING AND VENTILATION SYSTEMS
<br />NFPA-90B (2012)
<br />INSTALLATION OF WARM AIR HEATING AND AIR CONDITIONING SYSTEMS
<br />NFPA-91 (2010)
<br />EXHAUST SYSTEMS FOR AIR CONVEYING OF VAPORS, GASES, MISTS, AND
<br />NON-COMBUSTIBLE PARTICULATE SOLIDS
<br />NFPA-96 (2011)
<br />VENTILATION CONTROL AND FIRE PREVENTION OF COMMERCIAL COOKING
<br />OPERATIONS.
<br />NFPA-101 (2012)
<br />LIFE SAFETY CODE
<br />FLORIDA BUILDING CODE, BUILDING 5TH EDITION (2014)
<br />FLORIDA BUILDING CODE, MECHANICAL 5TH EDITION (2014)
<br />FLORIDA BUILDING CODE, PLUMBING 5TH EDITION (2014)
<br />FLORIDA BUILDING CODE, TEST PROTOCOLS FOR HIGH WIND HURRIZANE
<br />ZONES 5TH EDITION (2014)
<br />FLORIDA BUILDING CODE, FUEL GAS 5TH EDITION (2014)
<br />FLORIDA FIRE PREVENTION CODE 5TH EDITION (2014)
<br />FLORIDA ACCESSIBILITY CODE (2014)
<br />APPLICABLE STATE ENERGY CODE (2014)
<br />STATE OF FLORIDA ADMINISTRATIVE CODE NO. 69A-3.012 AND 69A-60.
<br />NOTE: WHERE THERE ARE DIFFERENCES BETWEEN SECTIONS OF THE
<br />BUILDING AND MECHANICAL OR PLUMBING CODES, IT WILL BE ASSUMED
<br />THAT THE BUILDING CODE TAKES PRECEDENCE.
<br />MECHANICAL LEGEND:
<br />MEDIUM PRESSURE TEE
<br />RECTANGULAR DUCT TURNING DOWN
<br />ROUND DUCT TURNING DOWN
<br />DUCT TURNING DOWN TO SIDEWALL
<br />REGISTER
<br />DOUBLE LINE TO DUCTWORK
<br />DUCT LINER IN LOW PRESSURE
<br />DUCT OR DOUBLE WALL INSULATED
<br />MEDIUM PRESSURE DUCT
<br />BRANCH TAP OFF MAIN W/450 BOOT
<br />FITTING OR SPIN -IN FITTING
<br />W/DAMPER (LOW PRESSURE)
<br />TRANSITION IN DUCT (NOT
<br />DIRECTION OF AIRFLOW)
<br />REGISTER TAPPING INTO BOTTOM
<br />11 OF DUCT
<br />FD
<br />® FIRE DAMPER
<br />® FIRE/SMOKE DAMPER
<br />FSD
<br />DUCT SMOKE DETECTOR
<br />SD SMOKE DETECTOR
<br />AD ACCESS DOOR
<br />AFF ABOVE FINISHED FLOOR
<br />BFC BELOW FINISHED FLOOR
<br />VFD VARIABLE FREQUENCY DRIVE
<br />TAD TRANSFER AIR DUCT
<br />TAO TRANSFER AIR OPENING
<br />BAS BUILDING AUTOMATION CONTROL SYSTEM
<br />© PRESSURE SENSOR
<br />MD MOTORIZED DAMPER
<br />DUCT TERMINATION
<br />450 FULL RADIUS TURN
<br />SQUARE ELBOW
<br />jj
<br />W/TURNING VANES
<br />FULL RADIUS TURN
<br />CO
<br />CO2SENSOR
<br />OTHERMOSTAT
<br />OH
<br />HUMIDISTAT
<br />MVDF
<br />MANUAL VOLUME DAMPER
<br />VAV
<br />VARIABLE VOLUME BOX
<br />EA
<br />INDICATES A SIZE "A" EXHAUST
<br />100
<br />REGISTER SET FOR 100 CFM
<br />RB INDICATES A SIZE "B" RETURN
<br />200 REGISTER SET FOR 200 CFM
<br />SB INDICATES A SIZE "B" SUPPLY
<br />200 DIFFUSER SET FOR 200 CFM
<br />® SUPPLY DIFFUSER
<br />zRETURN GRILLE
<br />® EXHAUST GRILLE
<br />UNDERCUT DOOR 3/4"
<br />UNLESS OTHERWISE NOTED
<br />PIPING LEGEND:
<br />CD MOISTURE CONDENSATE DRAIN LINE
<br />L REFRIGERANT LIQUID
<br />S REFRIGERANT SUCTION
<br />HGR HOT GAS REHEAT
<br />-� DIRECTION OF WATER FLOW
<br />PIPE TURNING DOWN
<br />PIPE TURNING UP
<br />PIPE SHUT OFF VALVE
<br />MECHANICAL GENERAL NOTES:
<br />CONTRACT REQUIREMENTS AFFECTING ALL TRADES:
<br />IT IS THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR AND EACH
<br />SUBCONTRACTOR TO REVIEW ALL DRAWINGS TO ASSURE COORDINATION OF
<br />ALL WORK AFFECTING EACH TRADE.
<br />1. FIBERGLASS DUCT INSULATION SHALL NOT PENETRATE RATED WALLS.
<br />SPACE BETWEEN STUDS, HEADERS AND DUCT SHALL BE PACKED WITH
<br />MINERAL FIBER SAFING INSULATION. WHERE A FIRE DAMPER IS REQUIRED
<br />THE SPACE BETWEEN THE SLEEVE AND THE STUDS OR HEADERS SHALL BE
<br />OF THE PROPER CLEARANCE FOR THE SIZE OF THE DUCT IN ACCORDANCE
<br />WITH SMACNA REQUIREMENTS. FIRE DAMPER SLEEVES SHALL BE INSTALLED
<br />AND SECURED IN ACCORDANCE WITH SMACNA STANDARDS. FIRE DAMPERS
<br />SHALL BE INSTALLED IN THE PLANE OF THE RATED ASSEMBLY AND BE U.L.
<br />LISTED AS AN ASSEMBLY COMPLYING WITH U.L. 555.
<br />2. CONTRACTOR SHALL FURNISH AND INSTALL ACCESS PANELS IN WALLS,
<br />NON -ACCESSIBLE CEILINGS, DUCTWORK AS REQUIRED AND ELSEWHERE AS
<br />INDICATED ON CONTRACT DOCUMENTS WHERE SERVICE ADJUSTMENT TO
<br />MECHANICAL, PLUMBING OR ELECTRICAL EQUIPMENT IS REQUIRED.
<br />3. COORDINATE INSTALLATION OF PLUMBING, VENT STACKS AND CONDUIT TO
<br />PERMIT INSTALLATION OF RECESSED TOILET ACCESSORIES, FIRE
<br />EXTINGUISHER CABINETS AND OTHER RECESSED EQUIPMENT. WHERE SUCH
<br />ITEMS ARE RECESSED IN CORRIDOR, SMOKE OR FIRE/SMOKE WALLS THEY
<br />SHALL BE INSTALLED IN A FIVE -SIDE ENCLOSURE.
<br />4. THE CONTRACTOR SHALL ASSEMBLE A LOG OF CERTIFICATES AND
<br />INSPECTIONS ORGANIZED IN C.S.I. FORMAT PRIOR TO FINAL INSPECTION
<br />INCLUDING MANUFACTURER'S CERTIFICATION OF FLAME SPREAD, SMOKE AND
<br />RADIANT PANEL TEST, AND CERTIFICATE OF TESTS FOR MEDICAL GAS,
<br />RADIATION SHIELDING, HVAC TEST AND BALANCE, FIRE ALARM, FIRE PUMP,
<br />EMERGENCY GENERATOR, ETC. AS APPLICABLE TO THE PROJECT AND MAKE
<br />AVAILABLE AT FINAL INSPECTION.
<br />5. CONTRACTOR SHALL VERIFY CONSTRUCTION IS COMPLETE AND IN
<br />ACCORDANCE WITH THE CONTRACT DOCUMENTS PRIOR TO FINAL
<br />INSPECTION. NOTIFY THE DESIGNER PRIOR TO INSPECTION OF ANY
<br />DEFICIENCIES OBSERVED.
<br />6. CONTRACTOR SHALL SEAL ALL METAL JOINTS WITH GLASSFAB AND MASTIC
<br />PRIOR TO INSTALLATION OF INSULATION AND PRESSURE TEST DUCTWORK
<br />FOR LEAKAGE.
<br />7. MANUAL VOLUME DAMPERS SHALL BE PROVIDED AT ALL RUNOUTS TO
<br />SUPPLY AIR DIFFUSERS, RETURN AIR REGISTERS, EXHAUST AIR REGISTERS,
<br />DIVISIONS IN DUCTWORK (SUPPLY, RETURN AND EXHAUST), AND ELSEWHERE
<br />NOTED ON PLANS AND IN SPECIFICATIONS FOR BALANCING SYSTEM.
<br />DAMPERS IN REGISTERS GRILLES AND DIFFUSERS ARE PROVIDED FOR FINAL
<br />ADJUSTMENTS DURING TEST AND BALANCING. DO NOT RELY ON
<br />DISTRIBUTION DEVICE DAMPERS FOR SYSTEM BALANCING.
<br />8. COORDINATION OF ALL TRADES IS OF THE UTMOST IMPORTANCE. CEILING
<br />SPACE TO ROUTE WORK IN IS MINIMAL AT BEST. CONTRACTOR SHALL LAY
<br />OUT SYSTEMS IN CONJUNCTION WITH ALL TRADES TO AVOID CONFLICTS
<br />PRIOR TO INSTALLATION OF WORK.
<br />9. PLUMBING VENT STACKS AND HVAC EXHAUST SHALL BE KEPT A MINIMUM OF
<br />25' FROM ANY OUTSIDE AIR INTAKE. OUTSIDE AIR INTAKE MAY BE AS CLOSE
<br />AS 10' AWAY FROM EXHAUST FOR NON -HEALTHCARE FACILITIES.
<br />10. CONTRACTOR SHALL REVIEW PLACEMENT OF ALL HVAC EQUIPMENT ON
<br />ROOF WITH STRUCTURAL DRAWINGS PRIOR TO INSTALLATION.
<br />11. PROVIDE SEALED ROOF CURB AROUND ALL DUCTWORK AND PIPING
<br />PENETRATIONS THRU ROOF.
<br />12. CONTRACTOR SHALL MAINTAIN A MINIMUM OF 6" CLEARANCE BETWEEN
<br />DUCTWORK, PIPING, AND ANY PRIORITY WALLS (TWO HOUR FIRE, TWO HOUR
<br />FIREISMOKE, ONE HOUR SMOKE).
<br />13. PROVIDE ACCESS DOORS IN DUCTWORK FOR FIRE DAMPERS, REHEAT
<br />COILS, DUCT MOUNTED SMOKE DETECTORS, AND ELSEWHERE WHERE
<br />SERVICE OR ADJUSTMENT TO MECHANICAL, PLUMBING OR ELECTRICAL
<br />EQUIPMENT IS REQUIRED.
<br />14. PROVIDE "YOUNG" REMOTE VOLUME REGULATOR FOR ALL DAMPERS
<br />LOCATED ABOVE INACCESSIBLE CEILINGS. REFER TO ARCHITECTURAL
<br />DRAWINGS FINISH SCHEDULE FOR CEILING TYPES.
<br />15. ALL OUTSIDE AIR INTAKES ON ROOF SHALL BE KEPT A MINIMUM OF 36"
<br />ABOVE ROOF FOR HEALTHCARE FACILITIES, 12" FOR NON -HEALTHCARE.
<br />PROVIDE DUCTWORK OR CURB EXTENSIONS AS NECESSARY TO PROVIDE
<br />CLEARANCE.
<br />16. INSTALL SMOKE DETECTORS IN RETURN AIR DUCTWORK (PRIOR TO
<br />DILUTION OF OUTSIDE AIR) AND SUPPLY AIR DUCTWORK WITH SAMPLING
<br />TUBES IN AIRSTREAM ACCORDING TO MANUFACTURER'S INSTALLATION
<br />REQUIREMENTS. FOR ALL DUCT MOUNTED SMOKE DETECTORS PROVIDE AN
<br />AIR DIFFERENTIAL TEST ACROSS DETECTOR SAMPLING TUBES, RELOCATE OR
<br />ADJUST THE SAMPLING TUBES WHERE NECESSARY TO PROVIDE AN AIR
<br />DIFFERENTIAL WITHIN THE ACCEPTABLE RANGE ESTABLISHED BY THE
<br />MANUFACTURER. RESULTANT TEST DATA SHALL BE MADE AVAILABLE AT THE
<br />FINAL SURVEY AND WILL BE INCLUDED IN LOG OF CERTIFICATES. DUCT
<br />MOUNTED SMOKE DETECTORS TO BE FURNISHED AND INSTALLED BY
<br />MECHANICAL CONTRACTOR AND WIRED BY ELECTRICAL CONTRACTOR.
<br />17. MAINTAIN THE CLEAR SPACES AROUND, OVER AND UNDER EQUIPMENT,
<br />ELECTRICAL PANELS, SYSTEMS AND SYSTEM COMPONENTS IN CEILING
<br />CAVITIES NECESSARY FOR CONVENIENT OBSERVATION, OPERATION AND
<br />MAINTENANCE. PAY SPECIAL ATTENTION TO ACCESS TO FIRE DAMPERS, FIRE
<br />AND SMOKE DAMPERS, DUCT SMOKE DETECTORS, ELECTRIC DUCT HEATER
<br />CONTROLS, FILTER ACCESS DOORS, MEDICAL GAS VALVES, FIRE
<br />PROTECTION SYSTEM VALVES, ETC. DO NOT INSTALL DUCTWORK OR PIPING
<br />OF ANY KIND ABOVE ELECTRICAL PANELS PER NEC. COORDINATE AND FIELD
<br />VERIFY FINAL LOCATION OF ELECTRICAL PANELS WITH ELECTRICAL
<br />CONTRACTOR BEFORE INSTALLATION OF DUCTWORK AND PIPING.
<br />18. DO NOT INSTALL EQUIPMENT, SYSTEMS OR SYSTEM COMPONENTS
<br />WHERE THEY MAY ENCROACH ON THE CLEAR SPACES NECESSARY FOR
<br />OPERATION OR MAINTENANCE OF ITEMS INSTALLED BY OTHER TRADES
<br />WITHOUT CONFIRMING THAT THE CLEAR SPACE REQUIREMENTS OF THE
<br />OTHER TRADE WILL BE MAINTAINED.
<br />19. WHERE THE WORK OF OTHER TRADES MAY ENCROACH ON CLEAR
<br />SPACES REQUIRED FOR WORK INSTALLED UNDER THESE SECTIONS,
<br />COORDINATE WITH THE OTHER TRADES AND THE GENERAL CONTRACTOR TO
<br />MAINTAIN THE REQUIRED CLEAR SPACES.
<br />20. PRIOR TO THE FINAL INSPECTION, DEMONSTRATE TO THE OWNER THAT
<br />ACCESS AND CLEAR SPACES FOR ALL INSTALLED ITEMS THAT REQUIRE
<br />ROUTINE OBSERVATION, OPERATION AND MAINTENANCE HAVE BEEN
<br />MAINTAINED.
<br />21. MECHANICAL EQUIPMENT AND PIPING INSTALLED ON ROOF SHALL BE
<br />SECURED TO MEET FBC WIND LOADING REQUIREMENTS.
<br />22. UNLESS SPECIFIED BY THE ARCHITECT, EXTERIOR AIR LOUVERS SHALL BE
<br />RUSKIN MODEL ELF6375DXD (NOA 12-0601.22) OR APPROVED EQUAL
<br />CONSTRUCTED OF EXTRUDED ALUMINUM WITH INSECT SCREEN. DUCT
<br />CONNECTION SHALL BE SLOPED TOWARD EXTERIOR.
<br />23. ALL THROUGH PENETRATTION FIRESTOP SYSTEMS SHALL BE INSTALLED
<br />BY AN EXPERIENECED INSTALLER PER THE MANUFACTURERS INSTALLATION
<br />INSTRUCTIONS.
<br />24. REFER TO SPECIFICATIONS SECTION 15890 AND 15910 FOR SHEETMETAL -
<br />LOW PRESSURE DUCTWORK AND SHEETMETAL SPECIALTIES MATERIAL,
<br />SEALING AND INSTALLATION REQUIREMENTS.
<br />MECHANICAL GENERAL NOTES CONT.:1
<br />25. REFER TO SPECIFICATIONS SECTION 15250 FOR DUCT AND REFRIGERANT
<br />PIPING INSULATION MATERIAL, SEALING AND INSTALLATION REQUIREMENTS.
<br />26. PROVIDE COMMISSIONING OF NEW HVAC SYSTEMS OVER 40 TON TOTAL
<br />CAPACITY PER FLORIDA ENERGY EFFICIENCY CODE.
<br />27. MECHANICAL EQUIPMENT SHALL NOT BE INSTALLED IN A LOCATION
<br />WHERE SUBJECT TO MECHANICAL DAMAGE UNLESS PROTECTED BY
<br />APPROVED BARRIERS. MECHANICAL EQUIPMENT AND SUPPORTS THAT ARE
<br />EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
<br />PRESSURES IN ACCORDANCE WITH FLORIDA BUILDING CODE.
<br />HIGH WIND
<br />PROTECTION OF EQUIPMENT:
<br />IN COMPLIANCE WITH FMC-301.15; MECHANICAL EQUIPMENT, APPLIANCES
<br />AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
<br />INSTALLED TO RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE
<br />WITH FBC. APPLIANCES SHALL NOT BE INSTALLED IN A LOCATION WHERE
<br />SUBJECT TO MECHANICAL DAMAGE UNLESS PROVIDED WITH PROTECTION
<br />FROM HIGH -VELOCITY IMPACT IN ACCORDANCE WITH FMC-303.4. THE
<br />PROTECTIVE BARRIER MUST BE TESTED AND LABELED AS MEETING THE
<br />HIGH -VELOCITY IMPACT TEST OF FBC SECTIONS 1626.2 OR 1626.3 OR MUST
<br />BE ONE OF THE FOLLOWING:
<br />1. EXTERIOR CONCRETE MASONRY WALLS OF MINIMUM NOMINAL 8-INCH
<br />THICKNESS, CONSTRUCTED IN ACCORDANCE WITH CHAPTER 21 (HIGH -
<br />VELOCITY HURRICANE ZONES) OF FBC.
<br />2. EXTERIOR FRAME WALLS OR GABLE ENDS CONSTRUCTED IN
<br />ACCORDANCE WITH CHAPTER 22 AND CHAPTER 23 (HIGH -VELOCITY
<br />HURRICANE ZONES) OF FBC, SHEATHED WITH A MINIMUM 19/32-INCH CD
<br />EXPOSURE 1 PLYWOOD AND CLAD WITH WIRE LATH AND STUCCO
<br />INSTALLED IN ACCORDANCE WITH CHAPTER 25 OF FBC.
<br />3. EXTERIOR FRAME WALLS AND ROOFS CONSTRUCTED IN ACCORDANCE
<br />WITH CHAPTER 22 (HIGH -VELOCITY HURRICANE ZONES) OF FBC SHEATHED
<br />WITH A MINIMUM 24-GAGE RIB DECK -TYPE MATERIAL AND CLAD WITH AN
<br />APPROVED WALL FINISH.
<br />4. EXTERIOR REINFORCED CONCRETE ELEMENTS CONSTRUCTED OF SOLID
<br />NORMAL WEIGHT CONCRETE (NO VOIDS), DESIGNED IN ACCORDANCE WITH
<br />CHAPTER 19 (HIGH -VELOCITY HURRICANE ZONES) OF FBC AND HAVING A
<br />MINIMUM 2-INCH THICKNESS.
<br />5. ROOF SYSTEMS CONSTRUCTED IN ACCORDANCE WITH CHAPTER 22 OR
<br />CHAPTER 23 (HIGH -VELOCITY HURRICANE ZONES) OF FBC, SHEATHED WITH
<br />A MINIMUM 19/32-INCH CD EXPOSURE 1 PLYWOOD OR MINIMUM NOMINAL 1-
<br />INCH WOOD DECKING AND SURFACED WITH AN APPROVED ROOF SYSTEM
<br />INSTALLED IN ACCORDANCE WITH CHAPTER 15 OF FBC.
<br />ALL CONNECTORS SHALL BE SPECIFIED BY THE BUILDING STRUCTURAL
<br />DESIGNER OF RECORD FOR ALL LOADS EXCEPT IMPACT.
<br />GENERATOR FUEL OIL TANK ENCLOSURE, PIPING, VALVES, AND OTHER
<br />APPURTENANCES SHALL BE SECURED AND PROTECTED FOR CONTINUED
<br />OPERATION AND HAVE HURRICANE WIND RESISTANCE AND HURRICANE
<br />DEBRIS IMPACT PROTECTION DESIGNED BY A STRUCTURAL ENGINEER TO
<br />COMPLY WITH FBC.
<br />PRIOR TO FINAL ACCEPTANCE OF PROJECT, GENERAL CONTRACTOR SHALL
<br />PROVIDE WIND RESISTANCE AND HIGH -VELOCITY IMPACT PROTECTION
<br />DESIGN DOCUMENTS THAT ARE SIGNED, SEALED, AND DATED BY A
<br />STRUCTURAL ENGINEER REGISTERED IN THE STATE OF FLORIDA IN
<br />COMPLIANCE WITH FBC.
<br />PROJECT COORDINATION NOTES:
<br />THE CONSTRUCTION PHASING OF THIS PROJECT IS OF THE UTMOST
<br />IMPORTANCE. ALL CONTRACTORS FOR ALL DIVISIONS OF THE WORK SHALL
<br />GUARANTEE THAT THEIR WORK IS IN ACCORD WITH THE PHASING PLANS
<br />SHOWN IN THE ARCHITECTURAL CONTRACT DOCUMENTS. SHOULD IT BE
<br />NECESSARY TO ACCOMPLISH WORK IN AREAS WHICH ARE NOT INCLUDED
<br />IN THE PHASING PLANS, SUCH WORK SHALL BE DONE WITH THE MINIMUM
<br />OF DISTURBANCES THAT IS POSSIBLE AND WITHOUT CAUSING THE
<br />INTERRUPTION OF EXISTING SERVICES. ALL SERVICE INTERRUPTIONS THAT
<br />ARE ESSENTIAL TO THE WORK SHALL BE SCHEDULED WITH THE ARCHITECT
<br />AND, THEREBY, WITH THE OWNER. ALL CONTRACTORS FOR ALL TRADES
<br />SHALL COOPERATE AND COORDINATE THEIR WORK TO ALLOW THE
<br />COMPLETION OF ALL WORK WITH THE LEAST POSSIBLE NUMBER ON
<br />INTERFERENCE'S WITH THE SERVICES OF THE EXISTING BUILDING.
<br />THE DESIGN DRAWINGS OF ALL CATEGORIES AND TRADES
<br />(ARCHITECTURAL, STRUCTURAL, PLUMBING, FIRE PROTECTION, MEDICAL
<br />GAS, MECHANICAL, HEATING, VENTILATING AND AIR CONDITIONING AND
<br />ELECTRICAL) AND ALL SPECIFICATIONS AND SHOP DRAWINGS MUST BE
<br />COORDINATED AND BE VIEWED IN CONNECTION AND CONJUNCTION WITH
<br />EACH OTHER TO INSURE THE PROPER LOCATION OF ALL DEVICES AND
<br />EQUIPMENT. MAKE PARTICULAR NOTE OF LOCATIONS AND DIMENSIONS
<br />SHOWN ON THE ARCHITECTURAL FLOOR PLANS AND ELEVATIONS.
<br />M0.1
<br />MECHANICAL - LEGEND, NOTES, ETC...
<br />M5.1
<br />HVAC - PARTIAL FIRST FLOOR PLANS
<br />M12.1
<br />MECHANICAL - SCHEDULES
<br />M14.1
<br />MECHANICAL - DETAILS
<br />M14.2
<br />MECHANICAL - DETAILS
<br />REVISIONS
<br />v
<br />.
<br />v
<br />N 00
<br />Y N
<br />CM
<br />F
<br />v ro ti u
<br />� vi
<br />"
<br />E x
<br />it
<br />o C:
<br />g C5
<br />u • N t
<br />¢
<br />E
<br />Qom_. o
<br />00
<br />I-�
<br />0 = N 3
<br />o
<br />o a
<br />N
<br />Z
<br />OV/
<br />z
<br />U
<br />W
<br />L.L
<br />F
<br />V)
<br />U
<br />ZO
<br />00
<br />U
<br />V_
<br />c Z
<br />O
<br />.� J
<br />a V
<br />C4
<br />4)M
<br />J
<br />Wx
<br />n-
<br />Q
<br />a
<br />�
<br />o V
<br />sn
<br />m O
<br />U Lu
<br />C
<br />a H
<br />O
<br />Wz
<br />d Q
<br />�•
<br />CO t
<br />O
<br />M N
<br />Q.
<br />O �
<br />~
<br />L Oa.
<br />J
<br />LL.
<br />Date: 06. 03. 16
<br />Scale: AS NOTED
<br />Project Mgr: DAN
<br />Drawn: DEG
<br />Job: 16-062
<br />Sheet
<br />Mo* I
<br />
|