Laserfiche WebLink
EXHAUST FAN SCHEDULE <br />MARK <br />--- <br />EF1.1 <br />AIR QUANTITY <br />CFM <br />200 <br />E.S. P. <br />IN. H2O <br />0.25 <br />FAN TYPE <br />--- <br />CENTRIFUGAL <br />FAN SPEED <br />RPM <br />1694 <br />DRIVE TYPE <br />--- <br />I DIRECT <br />INTERLOCK - <br />--- <br />RTU-1 <br />SOUND CRITERIA <br />SONES <br />5.5 <br />MOTOR POWER <br />HP <br />1/10 <br />TIP SPEED <br />FPM <br />3604 <br />ELECTRICAL <br />V/PHIHZ <br />115/1/60 <br />UNIT LOCATION <br />--- <br />ROOF <br />UNIT MANUFACTURER <br />--- <br />GREENHECK <br />UNIT MODEL NO. <br />--- <br />G-065-VG <br />AREA SERVED <br />--- <br />ONCOLOGY <br />LAB <br />MECHANICAL SYSTEMS SUMMARY SHEET <br />PROJECT NAME: <br />FLORIDA MEDICAL CLINIC - ZEPHYRHILLS <br />ONCOLOGY EXPANSION <br />PROJECT OWNER: <br />FLORIDA MEDICAL CLINIC <br />PROJECT ADDRESS: <br />38135 Market Square <br />Zephyrhills, Florida 33542 <br />TOTAL AREA: <br />3,124 SQ. FT. <br />DESIGN CRITERIA <br />OUTDOOR AIR SUMMER TEMP DB/WB <br />937/78`'F <br />OUTDOOR AIR WINTER TEMP DB <br />340F <br />INDOOR AIR TEMP DB <br />750F <br />INDOOR HUMIDITY <br />50-60%RH <br />BUILDING ENVELOPE <br />CMU WALL + INSULATION <br />R-11 <br />METAL ROOF + INSULATION <br />R-19 <br />WINDOW, MEDIUM SOLAR GRAY TINT <br />U-0.41 <br />WINDOW SHADING COEFFICIENT <br />SHGC-0.25 <br />ENVELOPE CONDITIONS PRESENTED FOR REFERENCE ONLY <br />REFER TO ARCHITECTURAL PLANS FOR ACTUAL CONSTRUCTION. <br />SIZING METHOD <br />ASHRAE COMPUTER PROGRAM <br />+ SUPPLEMENTAL CALCULATIONS <br />TOTAL COOLING REQUIRED <br />WITH OUTSIDE AIR <br />116,089 BTUH <br />TOTAL SENSIBLE GAIN <br />88,484 BTUH <br />TOTAL LATENT GAIN <br />27,605 BTUH <br />TOTAL GRAINS WATER DEHUMIDIFICATION <br />19.0 GRAINS <br />HEATING <br />12.0 KW <br />TOTAL HEATING REQUIRED <br />WITH OUTSIDE AIR <br />40,956 BTUH <br />5/25/16 2:36 PM <br />SCHEDULE NOTES: <br />1. INSULATED ALUMINUM ROOF CURB, DISCONNECT SWITCH, AND <br />BACKDRAFT DAMPER FOR ROOF MOUNTED EXHAUST FANS. <br />2. EXHAUST FANS SHALL BE WIRED SUCH THAT THEY RUN CONTINUOUSLY <br />WITH RESPECTIVE AIR HANDLING UNIT. <br />3. FOR PURPOSES OF FIRE CONTROL ALL FANS ARE TO BE INTERLOCKED - <br />WITH AIR HANDLING UNIT INDICATED ON SCHEDULE. IF AIR HANDLING UNIT IS <br />SHUT DOWN MANUALLY OR BY THE FIRE ALARM SYSTEM THEN RESPECTIVE <br />EXHAUST FANS SHALL SHUT DOWN. <br />ROOF MOUNTED FANS SHALL BE CONSTRUCTED AND INSTALLED FOR <br />IGH WIND APPLICATION TO MEET FBC WIND LOAD REQUIREMENTS. <br />IANUFACTURER SHALL PROVIDE SIGNED AND SEALED STRUCTURAL PLANS <br />OR SECUREMENT TO STRUCTURE. <br />VARIABLE AIR VOLUME BOX SCHEDULE <br />WITH ELECTRIC HEAT ON SELECT BOXES <br />EXISTING <br />SCHEDULE NOTES. - <br />BASIS OF DESIGN: <br />PRICE <br />PROVIDE: <br />PRESSURE INDEPENDENT, DOUBLE WALL CONSTRUCTION WITH <br />3/4" 4LB/FT3 INSULATION <br />COORDINATE WITH CONTROL SYSTEM INSTALLER FOR APPROPRIATE <br />SELECTION OF THERMOSTATS AND COORDINATE WITH TEMPERATURE <br />CONTROL SYSTEM FOR DDC OPERATION. <br />CONTROL SYSTEM SUPPLIER WILL PROVIDE DDC CONTROLLERS FOR <br />FACTORY INSTALLATION. <br />PROVIDE ACCESS AND NECESSARY CLEARANCE FOR MAINTENANCE. <br />WHERE RUNOUT SIZE IS SHOWN ON DRAWING, FOLLOW DRAWING <br />OTHERWISE PROVIDE MIN. CONNECTION SIZE SHOWN. EQUIVALENT <br />RECTANGULAR DUCT SIZES MAY BE USED. <br />PROVIDE FACTORY MOUNTED HEAVY DUTY DISCONNECTS OR REMOTE <br />DISCONNECTS WHERE REQUIRED. <br />MARK <br />B1.1 <br />B1.2 <br />B1.3 <br />B3.28 <br />AREA SERVED <br />INFUSION <br />CONFERENCE <br />OFFICES <br />EXAM RMS <br />TOTAL AIR CFM <br />1540 <br />1040 <br />950 <br />575 <br />HEATING AIR CFM <br />616 <br />416 <br />380 <br />345 <br />MANUFACTURER <br />Price <br />Price <br />Price <br />Price <br />MODEL NO. <br />SDV Size -12 <br />SDV Size -10 <br />SDV Size -10 <br />SDV Size -8 <br />MAX. UNIT PD IN. WC <br />0.8 <br />0.8 <br />0.8 <br />0.8 <br />MIN. INLET SP IN. WC <br />0.05 <br />0.04 <br />0.03 <br />0.03 <br />UNIT INLET SIZE <br />12"%%C <br />10"0/00/0C <br />10"%0/0C <br />8"%%C <br />MIN. DUCT RUNOUT FROM MAIN <br />16"0/60/aC <br />14"%%C <br />14"%%oC <br />12"%%C <br />ENTERING AIR TEMP%%DF <br />60 <br />60 <br />50 <br />60 <br />LEAVING AIR TEMP %%DF HEAT <br />90 <br />90 <br />90 <br />90 <br />HEATING CAPACITY KW <br />5 <br />3 <br />3 <br />3 <br />STEPS CONTROL <br />SCR <br />SCR <br />SCR <br />SCR <br />ELECTRICAL - VIPH <br />277/1 <br />27711 <br />277/1 <br />277/1 <br />AMPS <br />1 18.05 <br />1 10.83 <br />1 10.83 <br />1 10.83 <br />5/31116 9:22 AM <br />EXISTING PACKAGE ROOFTOP UNIT SCHEDULE <br />SCHEDULE NOTES: <br />MARK <br />RTU-1 <br />RTU-1 ADJUSTED <br />RTU-3 <br />RTU-3 ADJUSTED <br />COOLING CAPACITY <br />MBH <br />229 <br />116 <br />460 <br />460 <br />SENSIBLE CAPACITY <br />MBH <br />89 <br />SUPPLY AIR MAX <br />CFM <br />5600 <br />3530 <br />12,000 <br />12,000 <br />OUTSIDE AIR MAX <br />CFM <br />560 <br />445 <br />1200 <br />1200 <br />EXTERNAL STATIC PRESSURE <br />IN. WTR <br />2.0 <br />2.0 <br />EVAPORATOR FAN MOTOR <br />HP <br />5 <br />15 <br />MAX. FAN SPEED <br />RPM <br />800 <br />875 <br />ENT. COIL AIR TEMP. DBIWB <br />OF/OF <br />81/67 <br />81/67 <br />LVG. COIL TEMP. DBIWB <br />°F/°F <br />54/53.8 <br />54.8/54.8 <br />AMBIENT CONDENSER TEMP. <br />OF <br />95 <br />95 <br />ELECTRIC HEAT <br />KW <br />NONE <br />NONE <br />FILTER EFFICIENCY <br />% <br />30% <br />30% <br />FILTER THICKNESS <br />INCHES <br />2" <br />2" <br />ELECTRICAL <br />V/PHIHZ <br />460/3160 <br />460/3/60 <br />MINIMUM CIRCUIT AMPACITY <br />A <br />53 <br />100 <br />MAX. OVERCURRENT PROTECT. <br />A <br />60 <br />125 <br />DIMENSIONS LxWxH <br />IN. <br />OPERATING WEIGHT <br />LBS <br />LOCATION <br />ROOF <br />ROOF <br />MANUFACTURER <br />TRANE <br />TRANE <br />MODEL <br />TCH240 <br />MANUFACTURE DATE <br />08/94 <br />AREA SERVED <br />ONCOLOGY <br />SPEC. DIV. <br />5/25/16 2:39 PM <br />Building: <br />FMC, ZEPHYRHILLS - ONCOLOGY EXPANSION <br />RTU-1 <br />System Tag/Name: <br />maximum cooling <br />Operating Condition Description: <br />Units (select from pull -down list) <br />IP <br />w/o diversity <br />w/ diversity <br />Inputs for System <br />Name <br />Units System Diversity <br />F-Systern <br />Check Figures <br />Floor area served by system <br />Population of area served by system <br />As <br />PS <br />sf 3,024 <br />P 44 D 60% <br />26 <br />8.7 P/1000 sf <br />Design primary supply fan airflow rate <br />Vpsd <br />cfm 3,390 D 70% <br />2,373 <br />0.78 cfm/sf <br />OA req'd per unit area for system (Weighted average) <br />Ras <br />cfm/sf 0.06 <br />0.06 ave cfm/sf <br />OA re 'd per person fors stem area (Weighted average) <br />R s <br />cf m/p 5.0 <br />5.00 ave cfm/p <br />Outdoor air intake provided for system <br />OA <br />cfm <br />Inputs for Potentially Critical zones <br />Potentially Critical Zones <br />Zone Name <br />Zone title <br />turns purple italic for critical zone(s) <br />61.1 B1.2 BA2.3 <br />Totals/averages <br />Zone Tag <br />Waiting Conference Offices <br />Occupancy Category <br />Select from pull -down list: <br />Offices ace Offices ace Offices ace <br />Floor Area of zone <br />Az <br />sf <br />1,242 788 994 <br />3,024 total sf <br />Design population of zone <br />Pz <br />P (default value listed,- may be overridden_) <br />20 17 7 <br />44 total P <br />Design total supply to zone (primary plus local recirculated) <br />Vdzd <br />cfm <br />1,500 1040 850 <br />3,390 total cfm <br />Induction Terminal Unit, Dual Fan Dual Duct or Transfer Fan? <br />Select from pull -down list or leave blank if N/A: <br />Frac. of local recirc. air that is representative of system RA <br />Er <br />1.00 average <br />Inputs for Operating Condition Analyzed <br />Percent of total design airflow rate at conditioned analyzed <br />Ds <br />% <br />30% <br />30% 30% 30% <br />30% average <br />Air distribution type at conditioned analyzed <br />Select from pull -down list: <br />CSCRH CSCRH CSCRH <br />Zone air distribution effectiveness at conditioned analyzed <br />Ez <br />0.80 0.80 0.80 <br />0.80 average <br />Primary air fraction of supply air at conditioned analyzed <br />Ep <br />1.00 average <br />Results of Minimum ASHRAE 62.1 Ventilation Rate Procedure (EQp1) <br />System Ventilation Efficiency <br />Ev <br />0.91 <br />Outdoor air intake required for system (EQp1) <br />Vot <br />cfm <br />344 <br />Outdoor air per unit floor area <br />VotfAs <br />cfm/sf <br />0.11 <br />Outdoor air per person served by system (including diversity) <br />VotlPs <br />cfm/p <br />13.0 <br />Outdoor air as a % of design primary supply air <br />Ypd <br />% <br />10% <br />OP�\EL <br />L <br />I C F�.•••2 <br />No $4 tS'�•N <br />=0: :D- <br />�-n• <br />�O D OAS <br />gS116 <br />REVISIONS <br />f, <br />• <br />0' <br />y 00 <br />N <br />C� O <br />E <br />N C <br />./ <br />.� <br />it <br />o � • E <br />O O1, <br />U • N -L <br />¢ <br />E <br />o <br />�--� <br />ti <br />��i <br />N <br />C� <br />1 <br />u <br />C� <br />Fz <br />(n <br />_O <br />Z <br />U <br />L.LJ <br />(n <br />U <br />ZO <br />00 <br />U <br />U_ <br />c Z <br />O <br />.H J <br />U <br />CV <br />WM <br />X- _J <br />M- <br />- <br />LU <br />U <br />O <br />O <br />u LU <br />° _H <br />� <br />O <br />M <br />00 t <br />O <br />M <br />Q <br />O <br />~ <br />6- <br />CL 0 <br />J <br />1.1.. <br />Date: 06.03. 16 <br />Scale: AS NOTED <br />Project Mgr: DAN <br />Drawn: DEG <br />Job: 16-062 <br />Sheet <br />M12*1 <br />