SYMBOLS GENERAL NOTES: <br />A. ALL MOUNTING HEIGHTS GIVEN IN THE LEGEND, SCHEDULES, PLANS, <br />AND DRAWING NOTES ARE TO THE CENTERLINE OF THE DEVICE, UNLESS <br />OTHERWISE NOTED. <br />B. INSTALL ALL SWITCHES AT A CENTERLINE HEIGHT OF 46" A.F.F. UNLESS <br />OTHERWISE NOTED. WHERE SWITCHES OR RECEPTACLES ARE MOUNTED <br />ABOVE CASEWORK OR MILLWORK, LOCATE AT A HEIGHT OF 3'-8" MAX. <br />ABOVE FINISH FLOOR OR 3" ABOVE BACKSPLASH TO CENTERLINE. <br />C. WHERE COVERPLATES CONFLICT WITH CASEWORK OR MILLWORK, <br />SLIGHTLY ADJUST THE MOUNTING HEIGHTS OF THE WIRING DEVICES TO <br />MAKE THE COVERPLATES CLEAR THE COUNTERTOP OR BACKSPLASH BY 1". <br />D. ADDITIONAL SYMBOLS MAY BE SHOWN OR DENOTED ON OTHER <br />SHEETS. <br />E. ALL SYMBOLS, NOTES, AND ABBREVIATIONS SHOWN ON THE LEGEND <br />ARE NOT NECESSARILY USED IN THIS SET OF CONTRACT DOCUMENTS. <br />F. NUMERICAL SUBSCRIPT ADJACENT TO DEVICE FIXTURE, EQUIPMENT OR <br />JUNCTION BOX SYMBOL ON THE DRAWINGS DENOTES THE PANELBOARD <br />CIRCUIT NUMBER TO WHICH DEVICE, FIXTURE, EQUIPMENT OR WIRING IN <br />JUNCTION BOX IS CONNECTED. <br />CODE CRITERIA: <br />NOTE: <br />A. THIS LIST IS NOT INCLUSIVE OF ALL CODES AND STANDARDS THAT MAY <br />OR MAY NOT APPLY TO THIS PROJECT. <br />B. PERFORM WORK SPECIFIED IN SPECIFICATIONS IN ACCORDANCE WITH <br />STANDARDS LISTED BELOW INCLUDING AMENDMENTS OR REVISIONS. WHEN <br />THESE SPECIFICATIONS ARE MORE STRINGENT, THEY TAKE PRECEDENCE. IN <br />CASE OF CONFLICT, OBTAIN A DECISION FROM THE DESIGNER. <br />NFPA-70 (2011) <br />NATIONAL ELECTRICAL CODE <br />NFPA-72 (2010) <br />NATIONAL FIRE ALARM CODE <br />NFPA-90A (2012) <br />INSTALLATION OF AIR CONDITIONING AND VENTILATION SYSTEMS <br />NFPA-90B (2012) <br />INSTALLATION OF WARM AIR HEATING AND AIR CONDITIONING SYSTEMS <br />NFPA-91 (2010) <br />EXHAUST SYSTEMS FOR AIR CONVEYING OF VAPORS, GASES, MISTS, AND <br />NON-COMBUSTIBLE PARTICULATE SOLIDS <br />NFPA-96 (2011) <br />VENTILATION CONTROL AND FIRE PREVENTION OF COMMERCIAL COOKING <br />OPERATIONS. <br />NFPA-101 (2012) <br />LIFE SAFETY CODE <br />FLORIDA BUILDING CODE, BUILDING 5TH EDITION (2014) <br />FLORIDA BUILDING CODE, MECHANICAL 5TH EDITION (2014) <br />FLORIDA BUILDING CODE, PLUMBING 5TH EDITION (2014) <br />FLORIDA BUILDING CODE, TEST PROTOCOLS FOR HIGH WIND HURRIZANE <br />ZONES 5TH EDITION (2014) <br />FLORIDA BUILDING CODE, FUEL GAS 5TH EDITION (2014) <br />FLORIDA FIRE PREVENTION CODE 5TH EDITION (2014) <br />FLORIDA ACCESSIBILITY CODE (2014) <br />APPLICABLE STATE ENERGY CODE (2014) <br />STATE OF FLORIDA ADMINISTRATIVE CODE NO. 69A-3.012 AND 69A-60. <br />NOTE: WHERE THERE ARE DIFFERENCES BETWEEN SECTIONS OF THE <br />"BUILDING" AND "MECHANICAL" OR "PLUMBING" CODES, IT WILL BE ASSUMED <br />THAT THE BUILDING CODE TAKES PRECEDENCE. <br />SYMBOLS DESCRIPTION <br />{) PRIMEX GPS WIRELESS CLOCK (14159) 12.5" ANALOG <br />D SINGLE FACE WIRELESS MASTER CLOCK (SEE SPECIFICATIONS) <br />c z DOUBLE FACE WIRELESS MASTER CLOCK (SEE SPECIFICATIONS) <br />c INTERVAL TIMER - SIMPLEX #6306-9103 FURNISHED BY ELECTRICAL (INCLUDE CONTRC <br />SIT INTERVAL TIMER CONTROL SWITCH - SIMPLEX #6303-9202 FURNISHED BY ELECTRICAL <br />�fl MASTER CLOCK (GPS PRIMEX WIRELESS CLOCK SYSTEM) <br />EA MASTER CLOCK &-PROGRAMMER <br />a]J' PROGRAM BELL <br />MASTER CLOCK SYSTEM JUNCTION BOX <br />ALL STROBE UNITS MUST BE MOUNTED 80" AFF TO BOTTOM OF LAMP NOT DEVICE. <br />FLASHING LIGHT <br />SPEAKER/FLASHING LIGHT COMBINATION (CONNECT TO EXISTING AUDIO SYSTEM) <br />© SPEAKER/FLASHING LIGHT COMBINATION (PROVIDE TONE GENERATOR FOR USE WITH SPEAKE <br />© HORN/FLASHING LIGHT COMBINATION <br />MANUAL PULL STATION <br />Dss DUCT -SMOKE DETECTOR (SUPPLY) <br />DSR DUCT -SMOKE DETECTOR (RETURN) <br />D SMOKE DETECTOR <br />D L SMOKE DETECTOR WITH LOCAL ALARM <br />eID BEAM TYPE SMOKE DETECTOR <br />DSD DUCT -SMOKE DETECTOR (DAMPER) OR (EXHAUST) <br />L DUCT -SMOKE DETECTOR INDICATOR LIGHT (WALL MOUNTED 10"BELOW CEILING) <br />HD AUTOMATIC HEAT DETECTOR (RATE OF RISE TYPE) <br />SIDS SYSTEM CONNECTED SMOKE DETECTOR <br />SIDE SYSTEM CONNECTED SMOKE DETECTOR FOR FIREMAN'S RECALL <br />D FIRE SMOKE DAMPER <br />[EEJ SMOKE DOOR HOLDER <br />Ts TAMPER SWITCH <br />FL FLOW SWITCH <br />FJ FIREMAN'S PHONE JACK <br />sF DWELLING UNIT FIRE SPEAKER <br />❑L @- FLASHING LIGHT SPEAKER SIGNAL STATION <br />FACP CONTROL PANEL <br />FAPc PULL CABINET <br />Fa+ REMOTE ANNUNCIATOR <br />FR FIRESTAT (PROVIDED BY OTHERS) MONITOR WITH FIRE ALARM SYSTEM <br />FAPu CENTRAL PROCESSING UNIT <br />FFAcq I COMMAND CENTER <br />FAST TRANSPONDER <br />Fs I FIRE ALARM SPEAKER <br />s TWO BUTTON (CODE BLUE & STAFF ASSIST) EMERGENCY CALL STATION <br />;P SINGLE PATIENT STATION WITH CALL CORD <br />D STAFF DUTY STATION <br />D NURSE CALL DOME LIGHT <br />z NURSE CALL ZONE LIGHT <br />-P EMERGENCY PULL CORD (CORD WITHIN 6" AFF) <br />ACCESS CONTROL CARD READER (SEE SPECIFICATIONS) <br />ACCESS CONTROL DOOR REMOTE RELEASE PUSH BUTTON <br />PPI IACCESS CONTROL DOOR PUSH PLATE <br />MqN MEDICAL GAS ALARM <br />LPA LINE PRESSURE ALARM <br />Rom+ REMOTE GENERATOR ANNUNCIATOR <br />SeA BLOOD BANK ALARM <br />MSA MOISTURE SENSOR ALARM <br />DPA ROOM DIFFERENTIAL PRESSURE ALARM (COORDINATE W/DIVISION 15) <br />we VARIABLE LIGHT INTENSITY CONTROLLER (BY OTHERS) FOR EXAM LIGHT <br />b x DATA ONLY OUTLET(S) WITH "X" NUMBER OF CATEGORY 6 CABLE(S) <br />IG - VOICE/DATA OUTLET(S) WITH "X" VOICE AND "Y" DATA CATEGORY 6 CABLE(S) <br />N " VOICE ONLY OUTLETS WITH "X" VOICE CATEGORY 6 CABLE(S) <br />Q- X ABOVE COUNTER DATA ONLY OUTLET(S) WITH "X" NUMBER OF CATEGORY 6 CAI <br />14- xn ABOVE COUNTER VOICE/DATA OUTLET(S) W/ "X" VOICE & "Y" DATA CATEGORY 6 <br />14- X ABOVE COUNTER VOICE ONLY OUTLETS WITH "X" VOICE CATEGORY 6 CABLE <br />(PM) CABLE(S) INTENDED FOR USE BY PATIENT MONITORING SYSTEM <br />(MED) CABLE(S) INTENDED FOR USE BY AUTOMATED MEDICATION DISPENSER <br />N `" VOICE ONLY WALL PHONE OUTLET <br />AFF ABOVE FINISHED FLOOR <br />AFG ABOVE FINISHED GRADE <br />ABV MOUNT ABOVE COUNTER <br />ABC ABOVE CEILING <br />EDF ELECTRIC DRINKING FOUNTAIN <br />FBE FURNISHED & INSTALLED BY ELECTRICAL CONTRACTOR <br />FBO FURNISHED BY OTHERS, INSTALLED BY ELECTRICAL CONTRACTOR <br />GND GROUND <br />LION UNLESS OTHERWISE NOTED <br />WH WATER HEATER <br />WP WEATHER PROOF, NEMA 3R <br />ELECTRICAL SHEET LIST <br />SHEET <br />NUMBER SHEET NAME <br />ELECTRICAL LEGEND <br />MOUNTING HEIGHT <br />TO CENTERLINE <br />SYMBOL <br />DESCRIPTION <br />LION <br />�1 <br />CONDUIT CONCEALED IN WALL OR CEILING <br />T-0" <br />CONDUIT CONCEALED IN FLOOR OR BELOW GRADE ON SITE PLAN <br />SEE SPEC'S <br />CONDUIT EXPOSED ON WALL OR CEILING <br />SEE SPEC'S <br />HOMERUN CONDUIT, 2 CIRCUIT 3#12 AWG <br />SEE DETAIL <br />/T\ <br />TELEPHONE CONDUIT CONCEALED LION (MIN %%131") <br />/D\ <br />DICTATION SYSTEM CONDUIT CONCEALED LION MIN %%131" <br />/P\ <br />INTERNAL WIRING FURNISHED ON PRE-FAB PARTITION FBO <br />/TP <br />INTERNAL TELEPHONE RACEWAY FURNISHED WITH PRE-FAB PARTITION FBO <br />7'-0" <br />CONDUIT TURNING UP <br />CONDUIT TURNING DOWN <br />❑ <br />SURFACE MOUNTED INCANDESCENT OR HID LIGHT FIXTURE ON NORMAL BRANCH CIRCUIT <br />® <br />SURFACE MOUNTED INCANDESCENT OR HID LIGHT FIXTURE ON CRITICAL BRANCH CIRCUIT <br />® <br />SURFACE MOUNTED INCANDESCENT OR HID LIGHT FIXTURE CONN. TO LIFE SAFETY BRANCH <br />80" <br />❑ <br />RECESSED INCANDESCENT OR HID LIGHT FIXTURE ON NORMAL BRANCH CIRCUIT <br />80" <br />® <br />RECESSED INCANDESCENT OR HID LIGHT FIXTURE ON CRITICAL BRANCH CIRCUIT <br />80" <br />® <br />RECESSED INCANDESCENT OR HID LIGHT FIXTURE CONN. TO LIFE SAFETY BRANCH <br />80" <br />SURFACE MOUNTED WALL INCANDESCENT OR HID LIGHT FIXTURE ON NORMAL BRANCH CIRCUIT <br />46" <br />SURFACE MOUNTED WALL INCANDESCENT OR HID LIGHT FIXTURE ON CRITICAL BRANCH CIRCUIT <br />SURFACE MOUNTED WALL INCANDESCENT OR HID LIGHT FIXTURE CONN. TO LIFE SAFETY BRANCH <br />RECESSED WALL INCANDESCENT OR HID LIGHT FIXTURE ON NORMAL BRANCH CIRCUIT <br />CEILING <br />RECESSED WALL INCANDESCENT OR HID LIGHT FIXTURE ON CRITICAL BRANCH CIRCUIT <br />CEILING <br />P0 <br />RECESSED WALL INCANDESCENT OR HID LIGHT FIXTURE CONN. TO LIFE SAFETY BRANCH <br />❑ <br />®I <br />SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE ON NORMAL BRANCH CIRCUIT <br />®® <br />SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE ON CRITICAL BRANCH CIRCUIT <br />® <br />® <br />SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE CONN. TO LIFE SAFETY BRANCH <br />❑ <br />® <br />RECESSED FLUORESCENT LIGHT FIXTURE ON NORMAL BRANCH CIRCUIT <br />CEILING <br />® <br />RECESSED FLUORESCENT LIGHT FIXTURE ON LIFE SAFETY BRANCH CIRCUIT <br />CEILING <br />® <br />® <br />RECESSED FLUORESCENT LIGHT FIXTURE ON CRITICAL BRANCH CIRCUIT <br />18" <br />® <br />SURFACE MOUNTED FLUORESCENT FIXTURE CONNECTED TO NORMAL BRANCH CIRCUIT <br />6-0" <br />® <br />SURFACE MOUNTED FLUORESCENT FIXTURE CONNECTED TO CRITICAL BRANCH CIRCUIT <br />® <br />SURFACE MOUNTED FLUORESCENT FIXTURE CONNECTED TO LIFE SAFETY BRANCH CIRCUIT <br />CEILING <br />® <br />EXIT LIGHT, CEILING MOUNTED <br />46" <br />F-0 <br />EXIT LIGHT, WALL MOUNTED <br />vc=Y <br />TWO HEAD BATTERY POWERED EMERGENCY EGRESS LIGHT <br />80" <br />E <br />REMOTE EMERGENCY BATTERY PACK <br />5" <br />LIGHTING FIXTURE TYPE DESIGNATION -SEE LIGHTING FIXTURE SCHEDULE <br />AREA OR STREET LIGHT FIXTURE <br />°--0 <br />AREA OR STREET LIGHT FIXTURE <br />® <br />FACTORY WIRED CONTROLLER OR EQUIPMENT CONNECTION, FBO. DISCONNECTS FBE AS REQUIRED <br />® <br />MOTOR CONTROLLER OR CONTACTOR, F.B.O. W/DISCONNECT, F.B.O. W/EQUIPMENT <br />B <br />COMBINATION MOTOR STARTER DISCONNECT <br />qm <br />DISCONNECT SWITCH, NON -FUSIBLE <br />DISCONNECT SWITCH, FUSIBLE <br />112!1 RT <br />DISCONNECT SWITCH, NON -FUSIBLE RT DENOTES NEMA-3R <br />'o RT <br />DISCONNECT SWITCH, FUSIBLE RT DENOTES NEMA-3R <br />44" <br />`qK <br />MOTOR CONNECTION WITH APPROXIMATE HORSE -POWER SHOWN <br />44" <br />T <br />THERMOSTAT FBO SEE MECH. <br />44" <br />SOLENOID VALVE <br />CEILING <br />SPE <br />PHOTO -ELECTRIC SWITCH <br />CEILING <br />Tc <br />ON -OFF TIME CLOCK <br />Ps <br />PRESSURE SWITCH <br />Q <br />FLOAT SWITCH <br />FL <br />FLOW SWITCH <br />® <br />RELAY <br />® <br />TRANSFORMER <br />O <br />JUNCTION BOX <br />Pe <br />PULL BOX <br />LIGHTING PANELBOARD <br />® <br />MAIN SWITCHBOARD OR DISTRIBUTION PANEL <br />01 <br />ENCLOSED CIRCUIT BREAKER <br />sM PM <br />WALL MOUNTED PIR OCCUPANCY SENSOR - FURNISHED BY ELECTRICAL - WATTSTOPPER NO. PWA 00 <br />oc <br />CEILING MOUNTED OCCUPANCY SENSOR - FURNISHED BY ELECTRICAL - WATTSTOPPER NO. LMDC-100 <br />SLv I Lv <br />WALL MOUNTED LOW VOLTAGE SWITCH - FURNISHED BY ELECTRICAL - WATTSTOPPER NO. LMSW-101 MANUAL ON/AUTO OFF <br />SLvz 62 <br />WALL MOUNTED LOW VOLTAGE TWO BUTTON SWITCH - BY ELECTRICAL- WATTSTOPPER NO. LMSW-102 AUTO 50%/MANUAL 100%/AUTO 0 <br />soc hoc <br />WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR - FURNISHED BY ELECTRICAL- WATTSTOPPER NO. DW-100 AUTO ON/AUTO OF <br />S30C 6c <br />THREE WAY WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR - BY ELECTRICAL - WATTSTOPPER NO. DW-103 MANUAL ON/AUTO <br />oc ; <br />WEATHER RESISTENT CEILING MOUNTED OCCUPANCY SENSOR - FURNISHED BY ELECTRICAL - WATTSTOPPER NO. CB-100 <br />18" <br />I ocwP <br />WEATHER RESISTENT WALL MOUNTED OCCUPANCY SENSOR - FURNISHED BY ELECTRICAL <br />18" <br />S <br />SINGLE POLE SWITCH -(IVORY) <br />18" <br />Sz <br />TWO POLE SWITCH -(IVORY) <br />6"ABC OR 46"AFF <br />s3 <br />THREE-WAY SWITCH -(IVORY) <br />6"ABC OR 46"AFF <br />s4 <br />FOUR WAY SWITCH -(IVORY) <br />6"ABC OR 46"AFF <br />SD <br />SINGLE POLE DIMMER SWITCH 600 WATT <br />46" <br />EO.1 <br />ELECTRICAL - LEGEND, NOTES, ETC... <br />E5.1 <br />ELECTRICAL - PARTIAL FIRST FLOOR PLANS_ <br />E6.1 <br />ELECTRICAL - PARTIAL FIRST FLOOR PLANS <br />E14.1 <br />ELECTRICAL - DETAILS <br />- FURNISHED BY ELECTRICAL - WATTSTOPPER NO. RT-100 <br />SD3 THREE-WAY DIMMER SWITCH 600 WATT <br />sT THERMAL MOTOR SWITCH-(FBE) <br />s- THERMAL MOTOR SWITCH, WEATHERPROOF-(FBE) <br />STP THERMAL MOTOR SWITCH, WITH PILOT LIGHT FBE <br />SK KEY OPERATED SWITCH <br />sP SINGLE POLE SWITCH WITH PILOT LIGHT <br />SWP SINGLE POLE SWITCH, WEATHERPROOF <br />iPD SINGLE POLE, DOUBLE THROW, CENTER OFF SWITCH RED - DARK ROOM <br />tic VARIABLE INTENSITY CONTROL, F.B.O. WITH FIXTURES - SEE O.F.E. BROCHURE FOR INSTALLATION SEE DETAIL <br />I; SINGLE POLE SWITCH ON EMERGENCY BRANCH CIRCUIT RED <br />z DOUBLE POLE SWITCH ON EMERGENCY BRANCH CIRUIT RED <br />113 THREE-WAY SWITCH ON EMERGENCY BRANCH CIRUIT RED <br />�P SINGLE POLE SWITCH WITH PILOT LIGHT ON EMERGENCYE BRANCH CIRCUIT <br />B-- SINGLE RECEPTACLE, AMPERAGE, VOLTAGE, NEMA CONFIGURATION AS REQUIRED BY EQUIP. SUPPLIER OR AS NOTED <br />Q= 120V. DUPLEX RECEPTACLE IVORY <br />IQ= E 1120V. DUPLEX RECEPTACLE ON EMERGENCY BRANCH CIRCUIT RED <br />120V. DUPLEX RECEPTACLE ABOVE COUNTER(IVORY) <br />E 120V. DUPLEX RECEPTACLE ABOVE COUNTER ON EMERGENCY BRANCH CIRCUIT RED <br />�Tv 120V. DUPLEX RECEPTACLE FOR TV POWER (IVORY) <br />* 6" TO CENTERLINE BELOW FINISH CEILING <br />120V. QUADRAPLEX RECEPTACLE -(IVORY) <br />�)=0 120V. QUADRAPLEX RECEPTACLE ON EMERGENCY BRANCH CIRCUIT -(RED) <br />4)-- 1120V. QUADRAPLEX RECEPTACLE -(IVORY) <br />JD-= E 120V. QUADRAPLEX RECEPTACLE ON EMERGENCY BRANCH CIRCUIT -(IVORY) <br />S 120V. DUPLEX RECEPTACLE -SAFETY TYPE -(IVORY) <br />Qr=SE 120V. DUPLEX RECEPTACLE ON EMERGENCY BRANCH CIRCUIT -SAFETY TYPE -(RED) <br />E -- S 120V. DUPLEX RECEPTACLE -SAFETY TYPE -(IVORY) <br />e--SE. 120V. DUPLEX RECEPTACLE ON EMERGENCY BRANCH CIRCUIT -SAFETY TYPE -(RED) <br />&- T SINGLE RECEPTACLE-TWISTLOCK TYPE 120V: 20A. UNLESS OTHERWISE SPECIFIED <br />GFI GROUND FAULT TYPE RECEPTACLE -(IVORY) <br />GFI OH GROUND FAULT TYPE RECEPTACLE -ON EMERGENCY BRANCH CIRCW T�-- - - <br />GFI�WF GROUND FAULT RECEPTACLE WEATHERPROOF <br />OO 120V. DUPLEX RECEPTACLE IN CONSOLE -(I RY <br />OO E 120V. DUPLEX RECEPTACLE IN CONSOLE ON EMERGENCY BRANCH CIRCUIT RED <br />O° s 120V. DUPLEX RECEPTACLE IN CONSOLE -SAFETY TYPE -(IVORY) <br />OO SE 120V. DUPLEX RECEPTACLE IN CONSOLE ON EMERGENCY BRANCH CIRCUIT -SAFETY TYPE -(RED) <br />Oo - 120V. DUPLEX RECEPTACLE IN CONSOLE- IVORY AMPERES, VOLTAGE, & NEMA CONFIGURATION AS SPECIFIED <br />Do- E 120V. DUPLEX RECEPTACLE IN CONSOLE ON EMERGENCY BRANCH CIRCUIT- RED AMPERES, VOLTAGE, & NEMA CONFIGURATION AS SPECI <br />o0-T 120V. TWISTLOCK RECEPTACLE IN CONSOLE- IVORY AMPERES, VOLTAGE, & NEMA CONFIGUARATION AS SPECIFIED <br />Q 120V. SQUARE OR ROUND FLOOR BOX WITH (1) DUPLEX RECEPTACLE -(IVORY) <br />❑• E OE 120V. SQUARE OR ROUND FLOOR BOX WITH (1) DUPLEX RECEPTACLE EMERGENCY -(RED) <br />EW I TWO GANG FLOOR BOX WITH ONE DUPLEX RECEPTACLE AND ONE TELEPHONE OUTLET <br />F97MA THREE GANG FLOOR BOX WITH ONE DUPLEX RECEPTACLE, ONE TELEPHONE OUTLET, & ONE DICTATION OUTLET <br />F-T-711 THREE GANG FLOOR BOX WITH TWO DUPLEX RECEPTACLES, & ONE TELEPHONE OUTLET <br />@r= P 120V. DUPLEX RECEPTACLE PREWIRED IN PRE-FAB PARTITION (FBO) <br />O- SINGLE RECEPTACLE NON -EXPLOSION PROOF (HUBBELL 23000 HG) <br />® DUPLEX RECEPTACLE 20 AMP 120 VOLT <br />®E DUPLEX RECEPTACLE ON EMERGENCY BRANCH CIRCUIT 20 AMP 120 VOLT -(RED) <br />® DUPLEX RECEPTACLE 20 AMP 120 VOLT -(MOUNTED ABOVE COUNTER) <br />@*sR DUPLEX RECEPTACLE AND SINGLE POLE SWITCH UNDER COMMON PLATE <br />®- PORTABLE C-ARM OUTLET HUBBELL #2610 <br />R 120V. DUPLEX FOR RADIO EQUIPMENT POWER <br />SIGI DUPLEX RECEPTACLE, ISOLATED GROUNDING, <br />IG DUPLEX RECEPTACLE, ISOLATED GROUNDING, INSTALL ABOVE COUNTER <br />SIG QUADRAPLEX RECEPTACLE, ISOLATED GROUNDING <br />(Q---WEATHERPROOF DUPLEX RECEPTACLE <br />-w- WIREMOLD <br />m PLUGMOLD #3000 WITH HUBBELL 5252 DUPLEX RECEPTACLES 24" ON CENTER <br />MOUNTING HEIGHT <br />TO CENTERLINE <br />LION <br />AS NOTED <br />AS NOTED <br />AS NOTED <br />46" <br />CEILING <br />46" <br />46" <br />46" <br />46" <br />46" <br />46" <br />46" <br />46" <br />46" <br />46" <br />46" <br />46" <br />46" <br />46" <br />46" <br />46" <br />46" <br />46" <br />46" <br />46" <br />BOTTOM 46" <br />46" <br />46" <br />46" <br />46" <br />18" <br />18" <br />18" <br />AS SPECIFIED <br />AS SPECIFIED <br />AS NOTED <br />18" <br />18" <br />AS SPECIFIED <br />AS SPECIFIED <br />18" <br />18" <br />AS SPECIFIED <br />AS SPECIFIED <br />18" <br />AS SPECIFIED <br />-AS SPECIFIES <br />AS SPECIFIED <br />SEE DETAIL <br />SEE DETAIL <br />SEE DETAIL <br />SEE DETAIL <br />SEE DETAIL <br />SEE DETAIL <br />SEE DETAIL <br />FLOOR BOX <br />FLOOR BOX <br />FLOOR BOX <br />FLOOR BOX <br />FLOOR BOX <br />BOTTOM 61" <br />18" <br />18" <br />46" <br />BOTTOM 61" <br />18" <br />18" <br />46" <br />18" <br />46" <br />ei,�111i111/1/flop <br />G G ''•. <br />• 40 <br />- <br />No e328Q L <br />�/A r <br />A : STATE <br />'°.c�• RID R gyp. ••+�,�.•``' <br />�Jfltt/� <br />REVISIONS <br />✓ i <br />(n V' <br />DD <br />'IT CO <br />u � <br />r-^ <br />Q <br />ti ov <br />v m <br />ti N <br />U <br />X <br />U <br />CD <br />8O tCd Ln <br />U N '" <br />Lo <br />Q <br />Q�(-)oo <br />3 <br />�-' <br />3 r 3 <br />o ti <br />o <br />I- <br />N <br />SAIL <br />0 <br />V/ <br />Z <br />U <br />Ld <br />1 <br />D <br />(n <br />U <br />Z0 <br />0 <br />m <br />U <br />U <br />c Z <br />O <br />•C <br />V <br />C4 <br />-a <br />X J <br />M <br />; M- <br />Lu <br />o V <br />_ - <br />O <br />O <br />LL. <br />u Lu <br />C <br />° H <br />� <br />CO <br />O o <br />O- <br />o <br />N <br />QL O <br />J <br />LL <br />Date: 06. 03. 16 <br />Scale: AS NOTED <br />Project Mgr: PGG <br />Drawn: MCF <br />Job: 16-062 <br />Sheet <br />E0. I <br />