DIFFUSER AND GRILLE / REGISTER SCHEDULE <br />GENERAL NOTES <br />1. <br />SIZES ARE BY THIS SCHEDULE UNLESS NOTED OTHERWISE. DIFFUSERS ARE 4 -WAY BLOW UNLESS NOTED AS 3-WAY (3-W) <br />OR 2-WAY (2-W), GO <br />TO NEXT <br />LARGER NECK SIZE FOR 2-WAY OR 3-WAY DIFFUSERS <br />2. <br />UNLESS NOTED OTHERWISE, ALL DIFFUSERS IN THE SAME SPACE SHALL BE THE SAME SIZE, REGARDLESS OF AIRFLOW, USING LARGEST SIZE FROM TABLE <br />BELOW. <br />ALL DIFFUSERS IN THE SAME CORRIDOR SHALL BE THE SAME SIZE <br />3. <br />RETURN AND EXHAUST GRILLES ARE BASED ON 450 FPM AND 72% FREE AREA (BASED ON 1/2" EGG -CRATE GRILLES) <br />4. <br />USE RETURN / EXHAUST REGISTER AND DIFFUSER WITH O.B.D. IN DRYWALL OR INACCESSIBLE CEILINGS <br />5. <br />USE RETURN / EXHAUST GRILLES AND DIFFUSERS WITHOUT O.B.D. IN LAY -IN OR ACCESSIBLE CEILINGS <br />6. <br />INSTALL M.V.D. IN BRANCH DUCTS. INSTALL SPIN -IN FITTINGS (WITHOUT SCOOPS) WITH M.V.D. IN ALL BRANCH DUCTS. <br />SEE BRANCH DUCT CONNECTION <br />DETAILS FOR SPECIFIC REQUIREMENTS <br />(1) <br />USE TYPE 1, SURFACE MOUNT BORDER, FOR GRILLES IN DRYWALL CEILINGS. USE TYPE 3, LAY -IN BORDER, FOR GRILLES IN LAY -IN CEILINGS WITH GRILLE <br />FACE <br />SIZE SHOWN <br />(2) <br />FOR SYSTEMS USING CEILING AS A RETURN AIR PLENUM, USE TYPE 3, LAY-INBORDER <br />(3) <br />BRANCH DUCT RUNOUT SIZES ARE BY THIS SCHEDULE UNLESS OTHERWISE SPECIFICALLY NOTED ON FLOOR PLANS <br />(4) <br />THROWS AT 150, 100, AND 50 FPM <br />(5) <br />NC BASED ON OCTAVE BAND 2-7 SOUND POWER LEVEL WITH A ROOM ABSORPTION OF 10 dB, re 10 - 12 WATTS <br />TYPE <br />ESIGN BASI <br />MODEL NO. <br />AIRFLOW <br />RANGE (CFM) <br />FACE SIZE / <br />MODULE SIZE (IN) <br />NECK SIZE / BRANCH <br />DUCT SIZE (IN) (3) <br />ALTERNATE BRANCH <br />DUCT SIZE (IN) <br />Ps (IN) <br />THROW (FT) <br />(4) <br />MAX. NC (5) <br />DUCTED SUPPLY DIFFUSERS <br />PRICE <br />ASPD <br />0- 135 <br />24 x 24 <br />8 DIA. <br />10 x 6 <br />0.034 <br />2 -3 - 6 <br />--- <br />PRICE <br />ASPD <br />136 - 240 <br />24 x 24 <br />10 DIA. <br />12 x 6 <br />0.055 <br />3 - 5 - 10 <br />12 <br />PRICE <br />ASPD <br />241 - 380 <br />24 x 24 <br />12 DIA. <br />14 x 8 <br />0.082 <br />5 - 7- 13 <br />15 <br />A <br />PRICE <br />ASPD <br />381 - 550 <br />24 x 24 <br />14 DIA. <br />22 x 8 <br />0.115 <br />6-9-16 <br />18 <br />PRICE <br />ASPD <br />551 - 640 <br />24 x 24 <br />16 DIA. <br />20 x 12 <br />0.114 <br />7- 10 -17 <br />14 <br />PRICE <br />ASPD <br />641 - 735 <br />24 x 24 <br />--- <br />22 x 12 <br />0.130 <br />1 7 - 11 - 19 <br />15 <br />PRICE <br />ASPD <br />0- 120 <br />12 x 12 <br />8 DIA. <br />10 x 6 <br />0,110 <br />3-5-9 <br />--- <br />PRICE <br />ASPD <br />121 - 160 <br />12 x 12 <br />8 DIA. <br />12 x 6 <br />0.131 <br />5- 7 - 11 <br />12 <br />B <br />PRICE <br />ASPD <br />161 - 190 <br />12 x 12 <br />10 DIA. <br />14 x 8 <br />0.130 <br />5 - 7- 14 <br />12 <br />DUCTED RETURN / EXHAUST GRILLES AND REGISTERS <br />PRICE <br />80 <br />0-80 <br />6 x 6 <br />6 DIA. <br />8 x 6 <br />0.025 <br />--- <br />< 20 <br />PRICE <br />80 <br />81 - 140 <br />8 x 8 <br />8 DIA. <br />10 x 6 <br />0.025 <br />--- <br />< 20 <br />PRICE <br />80 <br />141 - 220 <br />10 x 10 <br />10 DIA. <br />12 x 6 <br />0.025 <br />--- <br />< 20 <br />PRICE <br />80 <br />221 - 320 <br />12 x 12 <br />10 DIA. <br />14 x 8 <br />0.025 <br />--- <br />< 20 <br />R1 (1) <br />PRICE <br />80 <br />321 - 480 <br />18 x 12 <br />12 DIA. <br />26 x 6 OR 18 x 8 <br />0.025 <br />-_= <br />< 20 <br />PRICE <br />80 <br />481 - 730 <br />18 x 18 <br />20 x 10 <br />0.025 <br />< 20 <br />PRICE <br />80 <br />731 - 950 <br />24 x 18 <br />--- <br />20 x12 OR 26 x 10 <br />0.025 <br />--- <br />< 20 <br />PRICE <br />80 <br />951 - 1,300 <br />24 x 24 <br />--- <br />28 x 10 <br />0.025 <br />--- <br />< 20 <br />PRICE <br />80 <br />1,301 - 2,000 <br />36 x 24 <br />--- <br />26 x 14 OR 38 x 10 <br />0.025 <br />--- <br />< 20 <br />PRICE <br />80 <br />2,001 - 2,800 <br />48 x 24 <br />--- <br />54 x 10 OR 26 x 18 <br />0.025 <br />--- <br />< 20 <br />NON -DUCTED RETURN GRILLES IN CEILING PLENUMS <br />R2 (2) <br />PRICE <br />80 <br />0 - 1,000 <br />24 x 24 <br />- <br />- <br />0.015 <br />PRICE <br />80 <br />1,001 - 1,875 <br />48 x 24 <br />0.015 <br />MECHANICAL DEMOLITION NOTES <br />FAN SCHEDULE <br />ABBREVIATIONS <br />GENERAL NOTES <br />STARTER ACCESSORIES <br />EQUIPMENT ACCESSORIES <br />PWE POWER WALL EXHAUSTER <br />FIT PREMIUM EFFICIENCY MOTOR, SEE SPECS <br />A= COMBINATION MAG-X-LINE <br />1 = BEL I ZT13M <br />14 = ACCESS DOOR <br />20 = HI -PRO POLY COATING <br />30 = ADJUSTABLE MOUNTING <br />PREU = POWER ROOF EXHAUSTER UPBLAST <br />(2) INCLUDES WEIGHT OF INERTIA BASE, <br />B = MANUAL MOTOR STARTER <br />2 = 2-SPEED, 2-WINDING MOTOR <br />15 = THREE-PHASE DISCONNECT SWITCH <br />21 = FAN CAGE WITH WALL SLEEVE <br />BRACKETS <br />PRIED = POWER ROOF EXHAUSTER DOWNBLAST <br />IF APPLICABLE <br />C = HAND -OFF -AUTO SWITCH, PILOT LIGHT, <br />3 = INERTIA BASE <br />IN FAN HOUSING <br />22 = SOLID STATE SPEED CONTROLLER <br />31= DIRECT DRIVE MOTOR <br />PRS = POWER ROOF SUPPLY FAN <br />(3) EXISTING TO REMAIN <br />AND CONTROL TRANSFORMER IN <br />4 = LINED HOUSING <br />16 = PREWIRED DISCONNECT SWITCH <br />23 = OUTLET CONE <br />32 = REVERSIBLE MOTOR <br />SWSI = SINGLE WIDTH, SINGLE INLET <br />STARTER <br />5 = INLET SCREEN <br />IN FAN HOUSING <br />24 = COPLANAR SILENCER <br />33 = INFRARED OCCUPANCY SENSOR, <br />DWDI = DOUBLE WIDTH, DOUBLE INLET <br />D = VARIABLE FREQUENCY DRIVE (VFD) <br />6 = OUTLET BIRD SCREEN <br />17 = WALL CURB <br />25 = INLET AIRFLOW STRAIGHTENER <br />SENSOR SHALL ONLY ACTIVATE FAN <br />CC = CEILING CENTRIFUGAL EXHAUST <br />E = LINE REACTOR, MAIN DISCONNECT, <br />7 = WEATHERPROOF HOUSING <br />18 = EXPLOSION PROOF MOTOR WITH NON -SPARKING 26 = UL LISTED FOR SMOKE CONTROL <br />WHEN BATHROOM IS OCCUPIED <br />BVS = BELTED VENT SET <br />AND CONTROL RELAY FOR COMMUNICATION <br />8 = MOTORIZED INLET DAMPERS <br />WHEEL AND DRIVE ASSEMBLY <br />SYSTEM <br />34 = AMCA LISTED <br />CT = CONTROL TRANSFORMER <br />WITH ENERGY MANAGEMENT SYSTEM <br />9 = MOTORIZED OUTLET DAMPERS <br />19 = UL 762 LISTING WITH GREASE TROUGH, <br />27 = PROVIDE ONE (1) SPARE VFD <br />35 = WHITE PLASTIC GRILLE <br />SP = STANDBY POWER <br />F = FULL VOLTAGE NON REVERSING CONTACTOR <br />10 = MOTORIZED INLET VANES <br />HINGED FAN ACCESS, DUCT ADAPTOR PLATE, <br />FOR EACH HP SIZE SCHEDULED <br />36 = AUTOMATIC BELT TENSIONER <br />EXP = EXPLOSION PROOF MOTOR & NON -SPARKING WHEEL <br />11= INLET GRAVITY DAMPERS <br />AND CURB EXTENSION TO MAINTAIN A <br />28 = HIGH TEMPERATURE <br />37 = TIE DOWN POINTS/LIFTING LUGS <br />PROP = WALL PROPELLER FAN <br />12 = OUTLET BACKDRAFT DAMPER <br />MINIMUM 40" ABOVE ROOF <br />29 = UL 793 BUTTERFLY DISCHARGE <br />38 = MOTOR WITH THERMAL OVERLOAD <br />EP = EMERGENCY POWER <br />13 = 12" HIGH ROOF CURB <br />DAMPER <br />39 = SHALL RUN CONTINUOUSLY <br />EXT. STATIC <br />MAX. SONES <br />MOTOR 1 <br />STARTER <br />WALL / ROOF OF <br />OPERATING <br />IDENTIFICATION <br />SYSTEM <br />QUANTITY <br />DESIGN BASIS <br />MODEL NO. <br />TYPE <br />CFM <br />PRESSURE <br />/ <br />ISOLATORS <br />ACCESSORIES <br />REMARKS / DUPLICATES <br />(IN) <br />O.V. (FPM) <br />WATTS <br />AMPS <br />RPM <br />ELEC. <br />TYPE <br />LOCATION <br />ACCESSORIES <br />OPENING <br />WEIGHT (LBS) <br />EF-1,2,3,4,5 <br />TOILET EXHAUST <br />1 <br />GREENHECK <br />SP-B90 <br />CEILING <br />75 <br />0.25 <br />2.5 / - <br />65 <br />0.65 <br />- <br />115/1/60 <br />- <br />- <br />- <br />11 <br />12, 16, 22, 30, 35, 38 <br />PLUG TYPE DISCONNECT, LIGHT <br />CENTRIFUGAL <br />SWITCH CONTROL W1 DELAY <br />EF-6 <br />JANITOR CLOSET <br />1 <br />GREENHECK <br />SP-670 <br />CEILING <br />50 <br />0.25 <br />1.4/- <br />45 <br />0.53 <br />- <br />115/1/60 <br />- <br />- <br />- <br />- <br />10 <br />12, 16, 22, 30, 35, 38 <br />PLUG TYPE DISCONNECT, LIGHT <br />CENTRIFUGAL <br />SWITCH CONTROL W1 DELAY <br />I _F_ <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />ROOFTOP A/C UNIT SCHEDULE <br />GENERAL NOTES <br />STARTER ACCESSORIES <br />EQUIPMENT ACCESSORIES <br />(1 PREMIUM EFFICIENCY MOTOR, SEE SPECS <br />A = G-X-LINE <br />1 = ROOF CURB <br />11 = FANS ON EMERGENCY POWER <br />* CONTRACTOR SHALL ENSURE ROOFTOP <br />(2) INCLUDES WEIGHT OF INERTIA BASE, <br />B = MANUAL MOTOR STARTER <br />2 = ECONOMIZER OPTION <br />12 = INLET SCREEN <br />EQUIPMENT IS SECURED AND TIED DOWN TO <br />IF APPLICABLE <br />C = HAND -OFF -AUTO SWITCH, PILOT LIGHT, <br />3 = BAROMETRIC RELIEF DAMPER <br />13 = ROOF CURB ADAPTOR <br />MEET WIND LOAD REQUIREMENTS SET FORTH IN <br />(3) EXISTING TO REMAIN <br />AND CONTROL TRANSFORMER IN <br />4 = 2" PLEATED MERV 7 FILTERS <br />14 = MOTORIZED OUTSIDE AIR AND RETURN AIR DAMPERS THE 2010 FLORIDA BUILDING CODE. REFER TO <br />(4) 95°F DB AMBIENT AIR DESIGN CONDITION <br />STARTER <br />5 = TIME DELAY RELAY W/ ANTI -SHORT CYCLE <br />15 = COIL GUARD <br />STRUCTURAL DRAWINGS FOR ADDITIONAL <br />D = VARIABLE FREQUENCY DRIVE (VFD) <br />6 = WEATHERPROOF HOUSING <br />16 = FACTORY DISCONNECT SWITCH <br />REQUIREMENTS. <br />E = LINE REACTOR, MAIN DISCONNECT, <br />7 = ALTERNATE INDOOR BLOWER MOTOR <br />17 = FACTORY SUPPLY AND RETURN SMOKE DETECTORS <br />AND CONTROL RELAY FOR COMMUNICATION <br />8 = FAN SHALL RUN CONTINUOUSLY <br />WITH ENERGY MANAGEMENT SYSTEM <br />9 = 7-DAY PROGRAMMABLE THERMOSTAT <br />F = FULL VOLTAGE NON REVERSING CONTACTOR <br />10 = 90% EFF. FINAL FILTERS <br />SUPPLY FAN <br />OUTSIDE AIR CFM <br />HEATING COIL <br />COOLING <br />COIL <br />COMPRESSOR 4 <br />SUPPLY FAN <br />MOTOR 1 <br />UNIT <br />STARTER <br />IDENTIFICATION <br />AREA SERVED <br />TYPE <br />DESIGN <br />MODEL N0. <br />UNIT <br />OPERATING <br />ACCESSORIES <br />REMARKS / <br />EXT. S.P. <br />TOTAL <br />DEHUM <br />ENT. <br />LVG. <br />MIN. GTH <br />DISC. <br />BASIS <br />CFM <br />(IN) <br />S.P. <br />MINIMUM <br />MAXIMUM <br />TYPE <br />INPUT <br />CFM <br />DB / WB <br />DB / WB <br />BTU/HR <br />QUANTITY / RLA <br />ELEC. <br />HP <br />ELEC. <br />MCA <br />MOCP <br />ELEC. <br />TYPE <br />LOCATION <br />TYPE <br />ACCESSORIES <br />WEIGHT (LBS) <br />DUPLICATES <br />RTU-1 <br />NORTH SIDE EXAM ROOMS, <br />PACKAGE <br />JCI <br />J06ZJE18D2LZZ7 <br />2,660 <br />0.6" <br />- <br />250 <br />300 <br />ELECTRIC <br />13.5 KW <br />2,660 <br />76.9°F/64.5°F <br />56.8°F/55.0°F <br />76,100 <br />2 / 9.3 EA. <br />208/3/60 <br />1.5 <br />208/3/60 <br />53.3 <br />60 <br />208/3/60 <br />F <br />UNIT <br />SEE DIV. 26 <br />1,067 <br />1, 4, 5, 6, 9, 12, 14, 15, 1 <br />PROCEDURE RM <br />DX <br />@ 208V <br />MOUNTED <br />RTU-2 <br />WAITING ROOMS, BREAK RM <br />PACKAGE <br />JCI <br />J10ZJE18R2LZZ7 <br />3,900 <br />0.7" <br />- <br />400 <br />475 <br />ELECTRIC <br />13.5 KW <br />3,900 <br />77.1-F/64.6°F <br />54.2°F/53.9°F <br />124,100 <br />2 / 16.0 EA. <br />208/3/60 <br />3 <br />208/3/60 <br />58.8 <br />60 <br />208/3/60 <br />F <br />UNIT <br />_ <br />SEE DIV. 26 <br />1,107 <br />1, 4, 5, 6, 7, 9, 12, 14, 15, 16 <br />■ <br />DX <br />@ 208V <br />MOUNTED <br />RTU-3 <br />SOUTH SIDE EXAM ROOMS, <br />PACKAGE <br />JCI <br />J06ZJE18D2LZZ7 <br />2,545 <br />0.6" <br />- <br />250 <br />300 <br />ELECTRIC <br />13.5 KW <br />2,545 <br />77.0°F/64.5°F <br />56.3°F/54.6"F <br />75,500 <br />2 / 9.3 EA. <br />208/3/60 <br />1.5 <br />208/3/60 <br />53.3 <br />60 <br />208/3/60 <br />F <br />UNIT <br />_ <br />SEE DIV. 26 <br />1,067 <br />1, 4, 5, 6, 9, 12, 14, 15, 16 <br />PROCEDURE RM <br />DX <br />208V <br />MOUNTED <br />i <br />1. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFYTHE CONDITION OF ALL EXISTING EQUIPMENT, EXACT SIZES OF EXISTING <br />V Q , <br />DUCT, ETC. BEFORE DEMOLITION WORK IS BEGUN. REPORT ANY DISCREPANCIES BETWEEN PLANS AND ACTUAL FIELD CONDITIONS <br />TO ARCHITECT AND ENGINEER PRIOR TO THE COMMENCEMENT OF DEMOLITION WORK. <br />2. REMOVE THE INDICATED HVAC ITEMS AS SHOWN ON PLANS. THIS INCLUDES ALL HANGERS, STRAPS AND RELATED MATERIAL. <br />3. PATCH OPENINGS IN WALLS TO MAINTAIN THE INTEGRITY OF THE WALL WHERE AIR DEVICES HAVE BEEN REMOVED; COORDINATE <br />WITH ARCHITECT. <br />4. CONTRACTOR SHALL VERIFY CLEARANCE REQUIREMENTS AND INDICATE ROUTING OF NEW DUCTWORK BEFORE FABRICATION <br />BEGINS AS RISES AND DROPS MAYBE NECESSARY DUE TO EXISTING FIELD CONDITIONS. <br />5. ALL ITEMS INDICATED BY THE MECHANICAL DRAWINGS TO BE REMOVED SHALL BE PRESENTED TO THE OWNER IN USEABLE <br />CONDITION. IF THE OWNER WISHES TO UTILIZE THE EXISTING EQUIPMENT, CONTRACTOR SHALL MOVE THE EQUIPMENT TO ANON <br />SITE LOCATION DESIGNATED BYTHE OWNER. ITEMS NOT RETAINED BYTHE OWNER SHALL BE DISPOSED OF IN A MANNER <br />ACCEPTABLE BY LOCAL JURISDICTION. <br />MECHANICAL DUCTWORK NOTES <br />1. ALL SUPPLY AIR DUCTWORK SHALL BE RECTANGULAR OR FLEXIBLE AS INDICATED. SEE SPECIFICATIONS FOR ADDITIONAL <br />REQUIREMENTS. <br />2. ALL DUCTWORK IS SHOWN AS FREE AREA INSIDE DIMENSIONS. REFER TO SPECIFICATIONS FOR INSULATION REQUIREMENTS. DO <br />NOT INSULATE EXHAUST DUCTWORK UNLESS OTHERWISE NOTED. <br />3. FOR LOW PRESSURE DUCTWORK USE SPIN -IN AND VOLUME DAMPER FOR ROUND TAKE OFFS FROM SQUARE DUCT. <br />4. FOR LOW PRESSURE DUCTWORK USE 45 DEGREE TAPS FOR ROUND TO ROUND TAKE OFF'S. PROVIDE VOLUME DAMPERS AT EACH <br />TAKE OFF. <br />S. DO NOT CONSTRUCT OR INSTALL TAPS OUT OF REDUCERS, TEES AND OR ELBOWS. <br />6. ALLOW FOR FIELD MEASURED OFFSETS OR TRANSITIONS, ELBOWS, ETC. <br />7. DOVETAIL AND/OR SEAL TIGHT FACE MOUNTED TAP -INS ARE NOT ACCEPTABLE. <br />8. SUPPORT ALL FLEXIBLE DUCTWORK AS INDICATED IN SMACNA FIGURE 3-9, 2010 BUT NOT LESS THAN 5'-0" O.C. <br />9. USE STAINLESS STEEL BANDS FOR FLEXIBLE DUCT CONNECTIONS. <br />10. GRILLES, REGISTERS AND DIFFUSERS CONNECTED BY FLEXIBLE DUCT SHALL BE SUPPORTED INDEPENDENTLY OF THE FLEXIBLE DUCT. <br />11. COORDINATE FINAL LOCATION OF ALL REGISTERS, GRILLES, DIFFUSERS ETC. WITH ARCHITECTURAL DRAWINGS. <br />12. DO NOT USE FLEXIBLE DUCTWORK IN EXPOSED AREAS OR IN AREAS ABOVE HARD CEILINGS. <br />13, DIFFUSERS, REGISTERS, AND GRILLES SHOWN ON THE MECHANICAL DRAWINGS SHALL BE IN ACCORDANCE WITH THE DIFFUSER AND <br />GRILLE SCHEDULE. SIZING OF BRANCH DUCTWORK TO SINGLE AIR DISTRIBUTION DEVICES SHALL BE IN ACCORDANCE WITH THE <br />DIFFUSER AND GRILLE SCHEDULE UNLESS NOTED OTHERWISE. <br />14. PROVIDE MANUAL BALANCING/VOLUME DAMPERS AT ALL LOW PRESSURE BRANCH TAKE -OFFS TO DIFFUSERS AND GRILLES FROM <br />SUPPLY AND RETURN MAINS AND SUB -MAINS, AND AT ALL LOW PRESSURE DUCT SPLITS OR SUB -MAIN TAKE -OFFS. <br />15. PROVIDE ACCESS PANELS IN AREAS WITH DRYWALL CEILINGS FOR ACCESS TO VOLUME DAMPERS. COORDINATE LOCATION OF <br />ACCESS PANELS WITH ARCHITECTURAL REFLECTED CEILING PLAN. <br />16. CONTRACTOR SHALL MAINTAIN CLEARANCE FOR ACCESS TO BALANCING DAMPERS AND ALL OTHER ITEMS REQUIRING <br />MAINTENANCE ACCESS. <br />17. SPACES WITH DRYWALL CEILINGS SHALL HAVE FLANGE TYPE AIR DEVICES. <br />18. ALL LOW PRESSURE SUPPLY, RETURN, AND EXHAUST DUCTWORK SERVING TWO OR MORE AIR DISTRIBUTION DEVICES SHALL BE <br />SIZED NOT TO EXCEED 1500 FEET PER MINUTE VELOCITY AND 0.07 INCH OF FRICTION LOSS PER 100 FEET OF DUCT. <br />19. ALL DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 90A, AIR DUCT ACCESS AND INSPECTION, AND PROVIDED WITH <br />SERVICE OPENINGS TO FACILITATE REMOVAL OF DUCT AND COMBUSTIBLE MATERIALS. <br />20. ALL DUCTWORK SHALL BE LOCATED ABOVE THE CEILING UNLESS OTHERWISE NOTED. <br />MECHANICAL GENERAL NOTES <br />1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS. THE CONTRACTOR <br />IS RESPONSIBLE FOR COORDINATING THE EXACT ROUTING OF ALL SERVICES WITH EXISTING CONDITIONS AND WITH ALL OTHER <br />TRADES. IT IS INTENDED THAT A COMPLETE SYSTEM BE PROVIDED WITH ALL NECESSARY EQUIPMENT, APPURTENANCES, AND <br />CONTROLS, COMPLETELY COORDINATED WITH ALL DISCIPLINES. ALL PARAMETERS GIVEN IN THESE DOCUMENTS SHALL BE STRICTLY <br />CONFORMED WITH. ANY ITEMS AND LABOR REQUIRED FOR A COMPLETE SYSTEM IN ACCORDANCE WITH ALL APPLICABLE CODES, <br />STANDARDS, AND THESE CONTRACT DOCUMENTS SHALL BE FURNISHED WITHOUT INCURRING ANY ADDITIONAL EXPENSE TO THE <br />OWNER. CAREFULLY REVIEW ALL CONTRACT DOCUMENTS AND THE DESIGN OF OTHER TRADES BEFORE PREPARING SHOP DRAWINGS. <br />2. COORDINATE EQUIPMENT AND DUCTWORK WITH ALL OTHER DISCIPLINES AND TRADES. MAKE ALL OFFSETS AND TRANSITIONS TO <br />COORDINATE WITH OTHER TRADES WITHOUT ANY ADDITIONAL EXPENSE TO THE OWNER. <br />3. COORDINATE ALL WORK WITH OWNER TO MAINTAIN OPERATIONS AS REQUIRED, AND SCHEDULED WITH OWNER. <br />4. COORDINATE THE EXACT LOCATION AND SIZE OF ALL ROOF, WALL, AND SLAB PENETRATIONS WITH THE ARCHITECTURAL DRAWINGS. <br />5. MOUNT THERMOSTATS WHERE INDICATED ON PLANS, 5'-0" A.F.F. UNLESS NOTED OTHERWISE. <br />6. ALL EQUIPMENT, PIPING, CONDUIT, DUCT, CABLE, ETC, SHALL BE INSTALLED NO LESS THAN 12" ABOVE CEILING GRID. <br />7. ANY FAILURE OF EQUIPMENT, SYSTEM, OR UTILITY THAT MAY AFFECT OTHER AREAS OUTSIDE THE PROJECT AREA SHALL REQUIRE <br />IMMEDIATE CORRECTIVE ACTION BYTHE CONTRACTOR AND SUBCONTRACTORS, WITHIN ONE HOUR DURING DAY SHIFT <br />MONDAY-FRIDAY, AND WITHIN FOUR HOURS ON NIGHTS AND WEEKENDS. <br />8. CONTRACTOR SHALL INSTALLANY BALANCING DEVICE NECESSARY TO ACHIEVE PROPER ADJUSTING AND BALANCING OF MECHANICAL <br />SYSTEMS. <br />9. CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH THE PROJECT SCOPE, UTILITY CONNECTIONS, AND ALL BUILDING <br />SERVICES. CONTRACTOR SHALL VERIFY LOCATION OF EXISTING EQUIPMENT, DUCTWORK, ETCETERA PRIOR TO STARTING WORK. <br />REPORT ALL DISCREPANCIES BETWEEN DRAWINGS AND ACTUAL CONDITIONS TO ENGINEER PRIOR TO STARTING ANY WORK. <br />10. CONTRACTOR SHALL PROVIDE NEW FILTERS AT EXISTING AHU BEFORE OWNER OCCUPIES NEW RENOVATED AREAS. <br />11. CONTRACTOR SHALL REFERENCE THE ARCHITECTURAL DOCUMENTS FOR DETAILS REGARDING MINIMUM REQUIREMENTS FOR <br />THROUGH -PENETRATION FIRE STOP SYSTEMS. WHERE A NEW OR UNFORESEEN CONDITION EXISTS THAT IS NOT COVERED IN <br />DOCUMENTS SUCH AS TYPE OF CONDUIT, SIZE OR DIAMETER, CONTRACTOR SHALL PROVIDE "ON -SITE FOR INSPECTION" A LISTED <br />UL-RATED SYSTEM FOR ACTUAL CONDITIONS TO MEET FIRE RATING OF CONSTRUCTION CLASSIFICATION REFERENCED IN ARCHITECT'S <br />LIFE SAFETY PLANS. <br />12. STANDARD DETAILS ILLUSTRATED ON THE DRAWINGS SHALL BE APPLIED IN ALL CASES WHERE THE FEATURE OCCURS IN THE SYSTEM <br />DESIGN. <br />13. SUPPORTS, ANCHOR BOLTS, AND HANGERS FOR ALL EQUIPMENT SPECIFIED IN DIVISION 23 SHALL CONFORM TO THE SPECIFICATIONS. <br />MISCELLANEOUS STEEL BRACING SUPPORTS AND REINFORCING STEEL NEEDED TO SUPPORT EQUIPMENT SPECIFIED IN DIVISION 23 <br />SHALL BE FURNISHED AS PART OF SCOPE OF WORK OF DIVISION 23. <br />14. SEE STRUCTURAL DRAWINGS FOR HANGING REQUIREMENTS FROM ROOF TRUSSES OR FLOOR JOISTS. <br />15. SMOKE DETECTORS SHALL BE LOCATED AS INDICATED ON THE MECHANICAL PLANS AND IN CONFORMANCE WITH NFPA 90A AND <br />LOCAL CODES. <br />16. COORDINATE WORK WITH OTHER TRADES. COORDINATE ALL EQUIPMENT WITH CONTROL SYSTEM FOR A COMPLETE OPERABLE <br />SYSTEM. <br />17. COORDINATE WITH ELECTRICAL DRAWINGS AND SPECIFICATIONS FOR ALL ELECTRICAL REQUIREMENTS. <br />18. COORDINATE WITH PLUMBING DRAWINGS AND SPECIFICATIONS FOR ALL PLUMBING REQUIREMENTS. <br />19. PATCH ALL CUTTING OR DRILLING OF EXISTING FINISHED WALLS, CEILINGS, OR FLOORS. <br />20. INSTALL AN ACCESS PANEL IN HARD CEILINGS WHEREVER ACCESS IS REQUIRED FOR DAMPERS OR ANY OTHER EQUIPMENT REQUIRING <br />ACCESS. COORDINATE WALL ACCESS PANELS WITH ARCHITECT. <br />21. WHERE WORK IN RENOVATED AREAS AFFECTS SYSTEMS IN OTHER AREAS OF THE PROJECT SCOPE, THE CONTRACTOR SHALL <br />COORDINATE THIS WORK WITH THE OWNER. THIS WORK SHALL BE DONE TO FIT THE SITE OPERATIONAL SCHEDULE AND MINIMIZE <br />DISRUPTION/DISCOMFORT TO OCCUPIED AREAS. PROVIDE 48 HOURS WRITTEN NOTICE WITH ANTICIPATED DURATION OF OUTAGE. <br />22. ALL PENETRATIONS THROUGH RATED WALLS, FLOORS AND PARTITIONS MUST BE INSTALLED AND FIRESAFED TO MEET UL FIRE <br />RESISTANCE LISTING DETAILS FOR THE PENETRATION. REFER TO PROJECT SPECIFICATIONS. <br />23. COORDINATE WITH ALL TRADES FOR REQUIRED CEILING REMOVAL IN EXISTING BUILDING. NOTIFY THE ARCHITECT AND OWNER PRIOR <br />TO COMMENCING REMOVAL. REMOVE ONLY THAT PORTION OF CEILING NECESSARY TO ACCESS AND COMPLETE THE NEW WORK. <br />UPON COMPLETION OF THE ABOVE CEILING WORK, CEILING IS TO BE REINSTALLED. REPLACE ANY DAMAGED CEILING TILES WITH NEW <br />TILES TO MATCH EXISTING. <br />24. OUTSIDE AIR INTAKES SHALL BE A MINIMUM OF 10 FEET FROM EXHAUST FAN DISCHARGE AND PLUMBING VENT LOCATIONS. <br />25. CONTRACTOR SHALL COORDINATE WITH THE ARCHITECT PRIOR TO CUTTING ANY OPENING IN THE STRUCTURE. <br />26. COORDINATE ALL WORK WITH ARCHITECTURAL PHASING PLAN. <br />27. UPON COMPLETION OF WORK, AN INDEPENDENT CERTIFIED TEST & BALANCE ENGINEER SHALL BALANCE ALL SYSTEMS, AND SUBMIT A <br />WRITTEN TEST & BALANCE AND OPERATION OF CONTROLS REPORT TO ARCHITECT/ENGINEER ALONG WITH OPERATION AND <br />MAINTENANCE MANUALS. <br />OUTSIDE AIR CALCULATION CHART PER ASHRAE 62.1 <br />RTU-1 <br />DESIGN CONDITION: COOLING OPERATION <br />SYSTEM VENTILATION EFFICIENCY: 1.00 <br />REQUIRED SYSTEM OUTDOOR AIR (CFM): 212 <br />SPACE VENTILATION ANALYSIS TABLE <br />ZONE NAME /SPACE NAME <br />SUPPLY AIR <br />FLOOR AREA <br />REQUIRED <br />OUTDOOR AIR <br />TIME AVERAGED <br />REQUIRED <br />OUTDOOR AIR <br />AIR DISTRIBUTION <br />REQUIRED <br />OUTDOOR AIR <br />UNCORRECTED <br />OUTDOOR AIR <br />ZONE <br />VENTILATION <br />(CFM) <br />Z <br />(FT) <br />(CFM/FTZ) <br />OCCUPANCY <br />(CFM/PERSON) <br />EFFECTIVENESS <br />(CFM) <br />(CFM) <br />EFFICIENCY <br />NORTH ZONE <br />1 2660 <br />1 2091 <br />1 0.06 <br />18 <br />5 <br />1.0 <br />210 <br />215.5 <br />1.01 <br />TOTALS1 <br />2660 <br />1 2091 <br />1 <br />210 <br />215.5 <br />RTU-2 <br />DESIGN CONDITION: COOLING OPERATION <br />SYSTEM VENTILATION EFFICIENCY: 1.00 <br />REQUIRED SYSTEM OUTDOOR AIR (CFM): 234 <br />SPACE VENTILATION ANALYSIS TABLE <br />SUPPLY AIR <br />FLOOR AREA <br />REQUIRED <br />TIME AVERAGED <br />REQUIRED <br />AIR DISTRIBUTION <br />REQUIRED <br />UNCORRECTED <br />ZONE <br />ZONE NAME / SPACE NAME <br />(CFM) <br />Z <br />(�) <br />OUTDOOR AIR <br />OCCUPANCY <br />OUTDOOR AIR <br />EFFECTIVENESS <br />OUTDOOR AIR <br />OUTDOOR AIR <br />VENTILATION <br />(CFM/FT2) <br />(CFM/PERSON) <br />(CFM) <br />(CFM) <br />EFFICIENCY <br />CENTER ZONE <br />3900 <br />2283 <br />0.06 <br />1 20 <br />1 5 <br />1 1.0 <br />1 235 <br />237 <br />1 1.01 <br />TOTALS <br />1 3900 <br />2283 <br />1 <br />1 <br />1 <br />1 235 <br />237 <br />RTU-3 <br />DESIGN CONDITION: COOLING OPERATION <br />SYSTEM VENTILATION EFFICIENCY: 1.00 <br />REQUIRED SYSTEM OUTDOOR AIR (CFM): 201 <br />SPACE VENTILATION ANALYSIS TABLE <br />ZONE NAME / SPACE NAME <br />SUPPLY AIR <br />FLOOR AREA <br />REQUIRED <br />OUTDOOR AIR <br />TIME AVERAGED <br />REQUIRED <br />OUTDOOR AIR <br />AIR DISTRIBUTION <br />REQUIRED <br />OUTDOOR AIR <br />UNCORRECTED <br />OUTDOOR AIR <br />ZONE <br />VENTILATION <br />(CFM) <br />(FTz) <br />(CFM/FT) <br />OCCUPANCY <br />(CFM/PERSON) <br />EFFECTIVENESS <br />(CFM) <br />(CFM) <br />EFFICIENCY <br />SOUTH ZONE <br />2545 <br />1978 <br />0.06 <br />17 <br />5 <br />1.0 <br />202 <br />204 <br />1.01 <br />TOTALS <br />2545 <br />1 1978 <br />1 <br />1 <br />1 <br />1 <br />3 202 <br />204 <br />HVAC ABBREVIATIONS <br />AB = AIR BLENDER <br />AHU = AIR HANDLING UNIT <br />AD = ACCESS DOOR <br />MVD = MANUAL VOLUME DAMPER <br />T = THERMOSTAT <br />IC = INSIDE CLEAR <br />EF = EXHAUST FAN <br />HVAC LEGEND <br />® 150 SUPPLY DIFFUSER & <br />AIR QUANTITY <br />150R RETURN GRILLE & AIR <br />QUANTITY <br />® 75E EXHAUST GRILLE & AIR <br />QUANTITY <br />�- SMOKE DETECTOR <br />QT THERMOSTAT <br />MVD <br />ER•- RISE IN DUCTWORK <br />�� DROP IN DUCTWORK <br />BSUPPLY DUCTWORK <br />RETURN OR EXHAUST <br />DUCTWORK <br />MECHANICAL INDEX <br />SHEET <br />DESCRIPTION <br />MOA <br />MECHANICAL LEGEND, NOTES, AND SCHEDULES <br />MO.2 <br />MECHANICAL SPECIFICATIONS <br />MO.3 <br />MECHANICAL SPECIFICATIONS <br />MOA <br />MECHANICAL SPECIFICATIONS <br />MIA <br />MECHANICAL FLOOR PLAN - DEMOLITION <br />M1.2 <br />MECHANICAL ROOF PLAN - DEMOLITION <br />M2.1 <br />MECHANICAL FLOOR PLAN - NEW CONSTRUCTION <br />M2.2 <br />MECHANICAL ROOF PLAN - NEW CONSTRUCTION <br />M3.1 <br />MECHANICAL DETAILS <br />% Q STATE OF <br />�LORiO�,\ <br />REVISIONS <br />BY <br />�1 03.10.15 <br />IS <br />�----� <br />♦ <br />m <br />co <br />i m <br />u -a c° <br />, <br />•-• <br />�r <br />Q <br />O p E <br />u o <br />ti <br />~C x y <br />� <br />cz <br />�--■ <br />G <br />u C <br />U N �. <br />-3 <br />._ <br />o ti <br />c <br />0 <br />a <br />ti <br />N <br />Cl) <br />a <br />v��a .a <br />zv'0a <br />p�.. <br />6UCS��� <br />�oa�a <br />a� <br />�Aa <br />� <br />O O <br />10 O <br />MO <br />Cat <br />0 <br />�v Evm <br />O O OV m N <br />Z <br />0 0 ` Ln rn <br />oo. �i° <br />� <br />m M a+ W <br />"i Ln u a <br />r <br />W <br />r- fz. m <br />N N co <br />�� a <br />W <br />=m 3 <br />0 3 <br />L 3 <br />Z <br />n. <br />V <br />� <br />Z <br />W <br />Y <br />� N <br />0 <br />00 <br />� m <br />r ry <br />t' LO <br />0 <br />Z m <br />cn <br />c ui <br />c > o ai <br />Q LL C <br />U �lD Y <br />.I <br />r"'� <br />Lz 3 0 <br />O u <br />l7N yO C7 <br />U <br />•- <br />`\ <br />� <br />a oo u a <br />Q a U w Q <br />U O <br />- Z <br />Z 0 <br />J J <br />U <br />Li .� <br />C <br />cUWE vio <br />-U � - <br />0 V <br />:T-- t <br />0 w - 0 <br />CC MO N 0-0 <br />N to 0 [0 <br />� < C:) <br />co <br />0 Q (0 <br />00 <br />W <br />Li- c <br />L <br />Date: 12. 19. 14 <br />Scale: AS NOTED <br />Project Mgr: ARK <br />Drawn: . <br />Job: 14-137 <br />Sheet <br />moo 1 <br />TO THE BEST OF THE ENGINEERS KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE -SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTER 553.79 AND CHAPTER 633, FLORIDA STATUTES. <br />