Design No, U465
<br />Nonbearing Wall Rating — 1 HR.
<br />Existing fire rated membrane
<br />PARTITION TYPES
<br />L\�Flill frrt\441� Glai
<br />N
<br />0
<br />N
<br />o N
<br />N
<br />0
<br />N
<br />:.x
<br />o �
<br />1. Floor and Ceiling Runners — (not shown) Channel shaped run-
<br />ners, 3-5/8 in. wide (min), 1-1/4 in. legs, formed from min No. 25 MSG
<br />(min No. 20 MSG when item 4C is used) gals steel, attached to floor
<br />and ceiling with fasteners spaced 24 in.. OC max.
<br />2. Steel Studs — Channel shaped, 3-5/8 in, wide (loin), 1-1/4 in. legs,
<br />3/8 in. folded back returns, formed from min No. 25 MSG (min No. 20
<br />MSG when Item 4C is used) gale steel spaced 24 in. OC max.
<br />3. Batts and Blankets* — (Optional) — Mineral wool or glass fiber baits
<br />partially or completely tilling stud cavity.
<br />See Batts and Blankets (BZ)Z) category for names of Classified companies.
<br />3A. Fiber, Sprayed* — As an alternate to Batts and Blankets (Item 3)
<br />Spray applied cellulose insulation material. The fiber is applied with
<br />water to completely fill the enclosed cavity in accordance with the
<br />application instructions supplied with the product. Nominal dry den-
<br />sity of 3.0 Ib/ft3.
<br />U S GREENFIBER L L C— Cocoon stabilized cellulose insula-
<br />tion.
<br />3B. Fiber, Sprayed* — As an alternate to Batts and Blankets (Item 3) and
<br />Item 3A - Spray applied cellulose insulation material. The fiber is
<br />applied with water to interior surfaces in accordance with the ap lica-
<br />tion instructions supplied with the product. Applied to completely fill
<br />the enclosed cavity. Minimum dry density of 4.3 pounds per cubic ft.
<br />NU -WOOL CO INC — Cellulose Insulation
<br />4. Gypsum Board* — 5/8 in. thick, 4 ft wide, attached to steel studs and
<br />floor and ceiling track with 1 in. long, Type S steel screws spaced 8 in.
<br />OC. along edges of board and 12 in, OC in the field of the board. Joints
<br />oriented vertically and staggered can opposite sides of the assembly.
<br />When attached to item 6 (resilient channels) or 6A (furring channels),
<br />wallboard is screw attached to furring channels with 1 in. long, Type S
<br />steel screws spaced 12 in. OC.
<br />AMERICAN GYPSUM CO —Types AG-C, AGX-C.
<br />BEIJING NEW BUILDING MATERIALS CO LTD —Type
<br />DBX-1.
<br />BPB AMERICA INC —Types 1, ECIRG, ProRoc 4vpe X, ProRoc
<br />Type C.
<br />BPB CANADA INC — ProRoc Type C, ProRoc Type X or ProRoc
<br />Type Abuse -Resistant.
<br />CANADIAN GYPSUM COMPANY —Types AR, C,111-AR,
<br />IP-X2, IPC-AR, SCX, SHX, WRC or WRX.
<br />G-P GYPSUM CORP, SUB OF
<br />GEORGIA-PACIFIC CORP —Types 5, 9, C, DAP, DD, DA, DGG,
<br />DS, GPFS6.
<br />LAFARGE NORTH AMERICA INC —Types LGFC2, LGFC2A,
<br />LGFC6, LGFC6A, LGFC-C, LGFC-C/A.
<br />NATIONAL GYPSUM CO —Types FSK, FSK-C, FSK-G, FSW-C,
<br />FSW G, FSW.
<br />PABCO GYPSUM, DIV OF
<br />PAP
<br />COAST BUILDING PRODUCTS INC —Type PG-C or
<br />.l G-{ .
<br />SIAM GYPSUM INDUSTRY (SARABURI) CO LTD —Type
<br />EX-1
<br />STANDARD GYPSUM L L C —Type SG-C.
<br />TEMPLE -INLAND FOREST PRODUCTS CORP —Type TG-C.
<br />UNITED STATES GYPSUM CO —Type AR, C, FRX-G, IP-AR,
<br />IP-X2, IPC-AR, SCX, SHX, WRC or WRX.
<br />USG MEXICO S A DE C V —Type AR, C, IP-AR, IP-X2, IPC-AR,
<br />SCX, SHX, WRC or WRX.
<br />4A. Gypsum Board* -- (As alternate to Item 4) - Nom 5/8 in. thick n�yp-
<br />sum panels with beveled, square or tapered edges, applied vertically or
<br />horizontally. Vertical joints centered over studs and staggered one stud
<br />cavity on opposite sides of studs. Horizontal edge joints and horizontal
<br />butt joints on opposite sides of studs need not be staggered or backed.
<br />Panels attached to steel studs and floor runner with I in. long Type S
<br />steel screws spaced 8 in. OC when applied horizontally, or 8 in. OC
<br />along vertical and bottom edges and 12 in. OC in the field when panels
<br />are applied vertically.
<br />CANADIAN GYPSUM COMPANY — Types AR, C, IP-AR,
<br />IP-X2, IPC-AR, SCX, SHX, WRC or WRX.
<br />UNITED STATES GYPSUM CO T ype AR, C, FRX-G, IP-AR,
<br />IP-X2, IPC-AR, SCX, SHX, WRC or WRX.
<br />USG MEXICO S A DE C V — Type AR, C, IP-AR, IP-X2, IPC-
<br />AR, SCX, SHX, WRC or WRX.
<br />4B. Gypsum. Board* — (As an alternate to Items 4 or 4A) — Nom 3/4 in.
<br />thick, 4 ft wide, installed as described in Item 4A witli screw length
<br />increased to 1-1/4 in.
<br />CANADIAN GYPSUM COMPANY —Types AR, IP-AR.
<br />UNITED STATES GYPSUM CO Types AR, IP-AR.
<br />USG MEXICO S A DE C V —Types AR, A' -AR.
<br />5_ joint Tape and Compound — Vinyl, dry or premixed joint compound,
<br />applied in two coats to joints and screw heads; paper tape, 2 in. wide,
<br />embedded in first layer of compound over all joints. As an alternate,
<br />nominal 3/32 in. thick gypsum veneer plaster may be applied to the
<br />entire surface of Classified veneer baseboard. Joints reinforced.
<br />6. Resilient Channel — (Optional -Not Shown) — 25 MSG galy steel
<br />resilient channels spaced vertically max 24 in. OC, flange portion
<br />attached to each intersecting stud with 1/2 in. long typpe S-12 panhead
<br />steel screws, Not for use with Type FRX gypsum panels.
<br />6A. Steel Framing Members (Not Shown)' — As an alternate to Item 3,
<br />furring channels and resilient sound isolation clip as described below:
<br />a. Furring Channels — Formed of No. 25 MSG galv steel. 2-3/8
<br />in. wide by 7/8 in. deep, spaced 24 in. OC perpendicular to
<br />studs_ Channels secured to studs as described in ltem'b. Ends of
<br />adjoining channels are overlapped 6 in. and tied together with
<br />double strand of No. 18 SWG galy steel wire near each end of
<br />overlap. As an alternate, ends of adjoining channels may be over-
<br />lapped 6 in, and secured together with two self -tapping 46 fram-
<br />ing screws, min. 7/16 in. long at the midpoint of the overlap,
<br />with one screw on each flange of the channel.
<br />b. Steel Framing Members' — Used to attach furring channels
<br />(Item a) to studs (Item 1). Clips spaced 48 in. OC., and secured to
<br />studs with 1 5/8 in. wafer or hex head Type S steel screw
<br />through the center grommet_ Furring channels are friction fitted
<br />into clips.
<br />PAC INTERNATIONAL INC — Type RSIC-1.
<br />*Bearing the UL Classification Mark
<br />gypsum board, and studs to the
<br />of the fire rated membrane
<br />acoustical telling
<br />' gypsum board each side of 3 518'
<br />at 1-4' on center
<br />enuatlon batts
<br />SECTION T HRU ONE HOUR WALL
<br />no scale
<br />ZF
<br />a
<br />x birch cap painted
<br />x 4 birch trim
<br />Anted
<br />3' Gypsum board each side
<br />3YB' metal studs at I'-4' on center
<br />SECTION AT LOW WALL
<br />12n=1 —On
<br />YF lead lined gypsum board on 3%'
<br />metal studs at Y-4' on center
<br />Polyethelene Film 15 mil
<br />lap 12, at Joints
<br />Batt insulation
<br />Caulk and seal around existing window
<br />SECTION AT WINDOW
<br />%' cementltlous file backer board.
<br />Thinset ceramic tile. Refer to
<br />finish schedule.
<br />galvanized metal studs
<br />1'-4' O.C.
<br />%' gypsum wallboard, moisture
<br />resistant In wet conditions
<br />Acoustic attenuation or
<br />thermal insulation butt
<br />V NON RATED METAL FRAME
<br />FOR TILE FINISH
<br />TYPE D
<br />HEIGHT: If the does not extend full height of wall, backer board
<br />transitions to Y8' gypsum wallboard above wainscot. Gypsum
<br />board extends to 4' above finish ceiling unless otherwise noted.
<br />Refer to elevations and or finish schedule for height of tile.
<br />Single layer %' gypsum wallboard with
<br />�16 ° lead lining on x-ray side of partition to 7'-0' a.f.f.
<br />attached with P type 'S' drywall screws
<br />3Y8' metal studs @ I'A' O.C.
<br />Acoustic attenuation or
<br />thermal Insulation butt
<br />Single layer %' gypsum
<br />wallboard on studs attached on
<br />control side of partition and
<br />above 7'-0' on x-ray side attach
<br />with P type 'S' drywall screws
<br />NON -RATED LEAD LINED
<br />METAL FRAME
<br />TYPE E
<br />HEIGHT: Gypsum board extends to 4" above flnlsh telling
<br />unless otherwise noted.
<br />Single layer s/' type 7' gypsum wallboard on each side of stud
<br />attached with P type 'S' drywall screws spaced La 8' O.C. along
<br />edge of board and i2' O.C. In field of board. Extend and seal
<br />partition to underside of rated membrane. Caulk all edges per
<br />U.L. descriptions.
<br />3 % " metal studs c 1'-4' O.C.
<br />Acoustic attenuation or
<br />thermal insulation butt
<br />ONE HOUR FIRE RATED
<br />METAL FRAME (U.L.'U465)
<br />TYPE A
<br />NOTE: Seal partition tight to the underside of the
<br />fire rated membrane
<br />Single layer %' gypsum wallboard
<br />on each side of stud attached
<br />with I' type 'S' drywall screws
<br />3%' metal studs -0 I'-4' O.C.
<br />Acoustic attenuation or
<br />thermal Insulation bait
<br />d-
<br />B % NON -RATED METAL FRAME
<br />TYPE B
<br />HEIGHT: Gypsum board extends to 4' above finish ceiling
<br />unless otherwise noted.
<br />Single layer %' moisture resistant gypsum
<br />wallboard on wet sides) of stud attached
<br />with P type 'S' drywall screws --
<br />3%' galvanized metal studs
<br />@ I'A' O.C.
<br />Acoustic attenuation or
<br />thermal insulation bott
<br />C NON -RATED METAL FRAME
<br />%" G sum board v INTERIOR WET CONDITIONS
<br />8 Gyp
<br />TYPE C
<br />HEIGHT: Gypsum board extends to 4" above flnlsh. ceiling
<br />unless otherwise noted.
<br />PARTITION NOTES
<br />All fire rated assemblies are to be continuous extending up to and sealed to the fire rated membrane.
<br />03 �4O�2n_l,_On
<br />Stencil all fire rated partitions above ceilings with appropriate warnings.
<br />Indicate intersections or changes In direction of rated construction steneiling
<br />not -to -exceed 20'-0' on center.
<br />0
<br />412412009 8:35:/3 AM ...\cd\A4-0 detalls.dgn
<br />Project No. 09002.00
<br />A400
<br />© 2009 BH/PK Architects, Inc.