ELECTRICAL SYMBOLS
<br />NOTE: NOT ALL SYMBOLS SHOWN MAY BE REQUIRED FOR THIS PROJECT.
<br />61
<br />Rn
<br />a
<br />O N
<br />N,
<br />f
<br />IN
<br />M o
<br />N
<br />Q0
<br />00
<br />WIRING DEVICES:
<br />DUPLEX RECEPTACLE - 20A, 125V, 2P, 3W (NEMA 5-20R)
<br />IN WALL +18" OR AS NOTED.
<br />IG = (NEMA 20-R) WITH ISOLATED GROUND
<br />TL = TWIST LOCK TYPE
<br />S = SECURITY TYPE COVER AND SCREWS
<br />EQUAL TO FAILSAFE #SSB1-1D
<br />DUPLEX RECEPTACLE - 20A, 125V, 2P, 3W
<br />(NEMA 5-20R) - IN WALL 6" ABOVE
<br />COUNTER TOP OR BACK SPLASH.
<br />SIMPLEX RECEPTACLE - 20A, 125V, 2P, 3W
<br />IN WALL +18" OR AS NOTED.
<br />DOUBLE DUPLEX RECEPTACLE ( QUAD) ON EMERGENCY,
<br />CRITICAL OR LIFE SAFETY CIRCUIT AS INDICATED BY
<br />HOME RUN.
<br />DUPLEX RECEPTACLE - 20A, 125V, 3W ( NEMA 5-20R) IN WALL 8" ABOVE COUNTER TOP
<br />ON EMERGENCY, CRITICAL OR LIFE SAFETY CIRCUIT
<br />AS INDICATED BY HOME RUN
<br />DUPLEX RECEPTACLE - 20A, 125V, 2P, 3W (NEMA 5-20R)
<br />IN WALL +18" OR AS NOTED. ON EMERGENCY, CRITICAL
<br />OR LIFE SAFETY CIRCUIT AS INDICATED BY HOME RUN
<br />IG = (NEMA 20-R) WITH ISOLATED GROUND
<br />TL = TWIST LOCK TYPE
<br />S = SECURITY TYPE COVER AND SCREWS
<br />EQUAL TO FAILSAFE #SSB1-1 D
<br />DUPLEX RECEPTACLE - 20A, 125V, 2P, 3W
<br />(NEMA 5-20R) - IN WALL +18" OR AS NOTED -
<br />ONE RECEPTACLE HOT, ONE RECEPTACLE
<br />SWITCHED.
<br />DUPLEX RECEPTACLE - 20A, 125V, 2P, 3W (NEMA 5-20R).
<br />FLUSH MOUNTED IN FLOOR WITH SERVICE FITTINGS.
<br />DUPLEX RECEPTACLE - 20A, 125V, 2P, 3W (NEMA 5-20R).
<br />FLUSH MOUNTED IN FLOOR WITH SERVICE FITTINGS.
<br />ON EMERGENCY, CRITICAL OR LIFE SAFETY CIRCUIT
<br />AS INDICATED BY HOME RUN.
<br />DUPLEX RECEPTACLE - 20A, 125V, 2P, 3W
<br />(NEMA 5-20R), FLUSH MOUNTED IN CEILING.
<br />FLOOR OUTLET BOX WITH SIMPLEX
<br />RECEPTACLE - 20A, 125V, 2P, 3W,
<br />(NEMA 5-20R).
<br />OUTLET BOX IN COUNTER TOP WITH
<br />SERVICE FITTINGS AND DUPLEX RECEPTACLE
<br />20A, 125V, 2P, 3W (NEMA 5-20R).
<br />TRIPLEX RECEPTACLE - 20A, 125V, 2P, 3W
<br />(NEMA 5-20R) - IN WALL +18" OR AS NOTED.
<br />TRIPLEX RECEPTACLE - 20A, 125V, 2P, 3W
<br />(NEMA 5-20R) - IN CEILING.
<br />TRIPLEX RECEPTACLE - 20A, 125V, 2P, 3W
<br />(NEMA 5-20R) - IN WALL 8" ABOVE
<br />COUNTER TOP OR BACKSPLASH.
<br />GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE,
<br />20A, 125V, 2P, 3W IN WALL +18" OR AS NOTED.
<br />GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE,
<br />20A, 125V, 2P, 3W IN WALL +6" ABOVE COUNTER TOP
<br />OR BACK SPLASH. UNLESS OTHERWISE NOTED.
<br />QUADPLEX RECEPTACLE - 20A, 125V, 2P, 3W (NEMA 5-20R)
<br />IN WALL +18" OR AS NOTED.
<br />IG = (NEMA 20-R) WITH ISOLATED GROUND
<br />TL = TWIST LOCK TYPE
<br />S = SECURITY TYPE COVER AND SCREWS
<br />EQUAL TO FAILSAFE #SSB1-1D
<br />QUADPLEX RECEPTACLE - 20A, 125V, 2P, 3W (NEMA 5-20R)
<br />IN WALL +6" ABOVE COUNTER TOP OR BACK SPLASH.
<br />IG = (NEMA 20-R) WITH ISOLATED GROUND
<br />TL = TWIST LOCK TYPE
<br />S = SECURITY TYPE COVER AND SCREWS
<br />EQUAL TO FAILSAFE #SSB1-1D
<br />.69& DUPLEX RECEPTACLE - 20A, 125V, 2P, 3W
<br />(NEMA 5-20R) WITH SWITCH, IN TWO
<br />GANG BOX - IN WALL +18" OR AS NOTED.
<br />L,e- SIMPLEX RECEPTACLE - 20A, 125V, 2P, 3W
<br />(NEMA 5-20R) WITH FUSE HOLDER AND
<br />FUSESTAT - IN WALL OR AS NOTED.
<br />DUPLEX COMBINATION RECEPTACLE
<br />20A, 125V, 2P, 3W (NEMA 5-20) AND
<br />20A, 250V,1 PH, 2P, 3W (6-20R)
<br />IN WALL +18" OR AS NOTED.
<br />SIMPLEX POWER RECEPTACLE 250V,1 PH, 2P, 3W
<br />20A, 30A OR 50A AT OUTLET INDICATES AMPERE
<br />RATING (NEMA 6-20R, 6-30R OR 6-50R)
<br />IN WALL +18" OR AS NOTED.
<br />DUPLEX POWER RECEPTACLE - 20A, 250V,1 PH, 2P,
<br />3W (NEMA 6-20R) - IN WALL +18" OR AS NOTED.
<br />DUPLEX POWER RECEPTACLE - 20A, 277V, 2P, 3W
<br />(NEMA 7-20R) - IN WALL OR AS NOTED.
<br />SIMPLEX POWER RECEPTACLE - DUAL VOLTAGE
<br />125/250V,1 PH, 3P, 4W
<br />20A, 30A, 50A OR 60A
<br />AT OUTLET INDICATES AMPERE RATING
<br />(NEMA 14-20R, 14-30R, 14-50R OR 14-60R)
<br />IN WALL +18" OR AS NOTED
<br />COMBINATION FLOOR BOX, DOUBLE DUPLEX
<br />P RECEPTACLE - 20A 125V 2P. 3W.
<br />TO BE POURED IN PLACE.
<br />COMBINATION FLOOR BOX, DOUBLE DUPLEX
<br />R RECEPTACLE - 20A 125V 2P. 3W.
<br />TO BE USED IN RAISED FLOOR TILES.
<br />SIMPLEX POWER RECEPTACLE - 250V, 3PH, 3P, 4W-20A,
<br />30A, 50A OR 60A AT OUTLET INDICATES
<br />AMPERE RATING (NEMA 15-20R,15-30R,
<br />15-50R OR 15-60R) - IN WALL +18" OR AS NOTED.
<br />WIRING DEVICES:
<br />RAISED FLOOR DISTRIBUTION BOX
<br />LOCATED ON SLAB BELOW RAISED
<br />FLOOR TILES. WIREMOLD # SDU-PD-X
<br />SIMPLEX POWER RECEPTACLE - DUAL VOLTAGE -
<br />120V/208V, 3PH Y, 4P, 4W-20A, 30A, 50A OR 60A
<br />AT OUTLET INDICATES AMPERE RATING (NEMA
<br />18-20R, 18-30R, 18-50R OR 18-60R) - IN WALL
<br />+18" OR AS NOTED.
<br />CLOCK HANGER RECEPTACLE - 20A, 125V, 2P, 3W
<br />(NEMA 5-20R) - IN WALL +84" OR AS NOTED.
<br />OPERATING ROOM X-RAY OUTLET IN WALL
<br />60" ABOVE FLOOR TO BOTTOM OR AS NOTED.
<br />®- OUTLET WITH SPECIAL DEVICE AS NOTED - +18" AFF
<br />OR AS NOTED.
<br />® OUTLET WITH SPECIAL DEVICE AS NOTED - IN FLOOR.
<br />OUTLET WITH SPECIAL DEVICE AS NOTED - IN CEILING.
<br />Q-H JUNCTION OR OUTLET BOX IN WALL. +18" OR AS NOTED.
<br />JO JUNCTION OR OUTLET BOX IN FLOOR.
<br />- JUNCTION OR OUTLET BOX IN CEILING.
<br />09 FREE STANDING OUTLET BOX - ON CONDUIT
<br />STUB WITH TYPE DEVICE AS INDICATED +4"
<br />ABOVE FLOOR OR AS NOTED.
<br />THERMOSTAT IN WALL OR AS NOTED.
<br />SINGLE POLE WALL SWITCH. LOWER CASE LETTERS
<br />INDICATE FIXTURES ASSOCIATED WITH SWITCH.
<br />2 = 2 POLE
<br />3 = 3 WAY
<br />4 = 4 WAY
<br />P/L = SWITCH WITH PILOT LIGHT
<br />L/T = LOCKING TYPE SWITCH
<br />K = KEY TYPE SWITCH
<br />S = SECURITY TYPE COVER WITH KEY SWITCH
<br />MOUNT AT +48" UNLESS NOTED OTHERWISE.
<br />B TWO SWITCHES FOR BI-LEVEL SWITCHING
<br />MOTION DETECTOR IN CEILING
<br />MOTION DETECTOR IN WALL
<br />PUSH BUTTON - S.S. INDICATES START,
<br />STOP OR AS INDICATED.
<br />4- LOCAL LIGHT DIMMER. MOUNT AT +48" UNLESS
<br />OTHERWISE NOTED. 3 INDICATES 3 WAY
<br />4 INDICATES 4 WAY.
<br />RAISE/LOWER CONTROL FOR REMOTE
<br />LIGHT DIMMER.
<br />2 MOTOR SPEED CONTROLLER
<br />2 SPEED, 3 SPEED OR V - VARIABLE
<br />SPEED AS INDICATED.
<br />LIGHTING FIXTURES:
<br />�O 2x4 1
<br />® lx4 FLUORESCENT FIXTURE AS SPECIFIED
<br />I--O-� STRIP CONNECTED TO NORMAL POWER.
<br />�O 2x2
<br />® 2x4
<br />® lx4 FLUORESCENT FIXTURE AS SPECIFIED
<br />STRIP CONNECTED TO LIFE SAFETY OR
<br />LEGALLY REQUIRER POWER.
<br />® 2x2
<br />® 2x4
<br />® lx4 FLUORESCENT FIXTURE AS SPECIFIED
<br />I--o-� STRIP CONNECTED TO EMERGENCY OR
<br />CRITICAL POWER.
<br />2x2
<br />® 2x4
<br />® lx4 FLUORESCENT FIXTURE AS SPECIFIED
<br />I--�� STRIP CONNECTED TO EMERGENCY OR CRITICAL
<br />POWER WITH INSTANTANEOUS BATTERY
<br />® 2x2
<br />® DOWN LIGHT AS SPECIFIED.
<br />CONNECTED TO NORMAL POWER.
<br />® DOWN LIGHT AS SPECIFIED. CONNECTED TO
<br />LIFE SAFETY OR LEGALLY REQUIRER POWER.
<br />® DOWN LIGHT AS SPECIFIED. CONNECTED TO
<br />EMERGENCY OR CRITICAL POWER.
<br />WALL MOUNTED FIXTURE AS SPECIFIED MOUNTED
<br />o- +84" ABOVE FLOOR OR AS NOTED.
<br />CONNECTED TO NORMAL POWER
<br />WALL MOUNTED FIXTURE AS SPECIFIED MOUNTED
<br />+84" ABOVE FLOOR OR AS NOTED. CONNECTED TO
<br />LIFE SAFETY OR LEGALLY REQUIRER POWER.
<br />WALL MOUNTED FIXTURE AS SPECIFIED MOUNTED
<br />+84" ABOVE FLOOR OR AS NOTED.
<br />CONNECTED TO EMERGENCY OR CRITICAL POWER.
<br />® EXIT LIGHT, CEILING MOUNTED, ARROW DIRECTION
<br />AS INDICATED ON PLAN. CONNECTED TO LIFE SAFETY
<br />OR LEGALLY REQUIRER POWER.
<br />EXIT LIGHT, WALL MOUNTED +84" ABOVE FLOOR
<br />{ OR AS NOTED. ARROW DIRECTION AS INDICATED
<br />ON PLAN. CONNECTED TO LIFE SAFETY OR
<br />LEGALLY REQUIRER POWER.
<br />LIGHTING FIXTURES:
<br />WALL MOUNTED BATTERY OPERATED
<br />EMERGENCY LIGHT FIXTURE. +90" UNLESS
<br />OTHERWISE NOTED.
<br />CEILING MOUNTED BATTERY OPERATED
<br />EMERGENCY LIGHT FIXTURE.
<br />o-
<br />WALL MOUNTED SPECIAL LETTERING SIGN
<br />AS SPECIFIED. MOUNT AT +84" UNLESS
<br />OTHERWISE NOTED.
<br />REMOTE LIGHT FIXTURE FOR BATTERY
<br />OPERATED EMERGENCY LIGHTING
<br />HIGH INTENSITY DISCHARGE FIXTURE AS
<br />SPECIFIED
<br />TYPE FIXTURE AS SPECIFIED
<br />®CHANDELIER
<br />SUSPEND FROM CEILING AS NOTED.
<br />MISCELLANEOUS SYMBOLS:
<br />PROJECTOR OUTLET -IN WALL
<br />OP
<br />PROJECTOR OUTLET -IN FLOOR BOX
<br />�-
<br />REMOTE GROUND INDICATOR FOR ISOLATION
<br />DISTRIBUTION PANEL, 72" ABOVE FLOOR.
<br />OP -�
<br />PHOTOCELL
<br />nH
<br />TIME SWITCH
<br />Q
<br />REFERENCED NOTE
<br />FA-M-q
<br />AMPLIFIER
<br />- D S -
<br />DOOR STRIKE SWITCH.
<br />D . F .
<br />DRINKING FOUNTAIN
<br />E W C .
<br />ELECTRIC WATER COOLER
<br />MCB.
<br />MAIN CIRCUIT BREAKER
<br />PM
<br />RECEPTACLE POWER MODULE
<br />6 DUPLEX RECEPTACLES
<br />PUSHBUTTON
<br />CARD READER
<br />CONDUIT,
<br />RACEWAYS AND LIGHTING:
<br />EXPOSED CONDUIT OR SURFACE
<br />RACEWAY'R' INDICATES RACEWAY
<br />CONDUIT CONCEALED IN WALL OR
<br />CEILING CONSTRUCTION
<br />CONDUIT CONCEALED IN FLOOR
<br />CONSTRUCTION OR UNDERGROUND
<br />�MT�
<br />SPECIAL SYSTEM WIRING TO CENTRAL EQUIPMENT,
<br />PANEL, CABLE TRAY, TERMINAL CABINET OR
<br />NEXT DEVICE.
<br />TD = TELEPHONE AND DATA
<br />MT = EMPTY
<br />CP = MASTER CLOCK & PROGRAM SYSTEM
<br />MC = MASTER CLOCK SYSTEM
<br />IC =INTERCOM SYSTEM
<br />TV = TELEVISION SYSTEM
<br />TVC = TELEVISION REMOTE CONTROL
<br />NC = NURSE CALL SYSTEM
<br />P = PAGING SYSTEM
<br />T = TELEPHONE SYSTEM
<br />GF = CIRCUIT TO GROUND FAULT
<br />CIRCUIT BREAKER
<br />EIL = EQUIPMENT INTERLOCK
<br />MP = MUSIC/PAGING SYSTEM
<br />CPP = CENTRAL PAGE/PROGRAM SYSTEM
<br />STV = SECURITY TELEVISION SYSTEM
<br />M = MUSIC SYSTEM
<br />- - - -' -,
<br />DIRECT BURIAL CABLE
<br />HOME RUN TO PANELBOARD-NUMBER OF
<br />ARROWS INDICATES NUMBER OF CIRCUITS
<br />EXPLOSION PROOF CONDUIT WITH
<br />CONDUIT SEALS.
<br />LAY IN WIREWAY DUCT, SIZE AS NOTED.
<br />CABLE TRAY, SIZE AS NOTED.
<br />FEEDER DUCT -RATING AND NUMBER
<br />OF CONDUCTORS AS NOTED.
<br />PLUG IN DUCT -RATING AND NUMBER
<br />OF CONDUCTORS AS NOTED.
<br />PLUG IN STRIP TYPE RECEPTACLES OR
<br />OTHER OUTLETS AS NOTED.
<br />- - - E- - -
<br />UNDER FLOOR DUCT -ELECTRICAL
<br />- - - T - - -
<br />UNDERFLOOR DUCT - TELEPHONE OR
<br />OTHER LOW TENSION AS NOTED.
<br />CONDUIT UP
<br />CONDUIT DOWN
<br />PULL BOX
<br />GROUND
<br />000a
<br />BUS DUCT
<br />POWER/COMMUNICATIONS LINEAR RACEWAY
<br />- - - - - - - -
<br />MAPNET CIRCUIT
<br />FLOOR DUCT
<br />GENERAL NOTES:
<br />EQUIPMENT:
<br />1.
<br />PREFORM WORK IN CONFORMANCE WITH THE NATIONAL ELECTRICAL CODE AND ALL
<br />MOTOR OUTLET AND CONNECTION.
<br />APPLICABLE BUILDING CODES AS INTERPRETED BY THE LOCAL AUTHORITY HAVING
<br />EQUIPMENT TYPE AS NOTED.
<br />JURISDICTION.
<br />O
<br />EQUIPMENT TERMINAL POINT VERIFY
<br />2.
<br />THE EXISTING CONDITIONS ARE SHOWN AS ACCURATELY AS FIELD CONDITIONS
<br />REQUIREMENTS AND LOCATION WITH
<br />WOULD PERMIT. BIDDERS SHALL THOROUGHLY EXAMINE THE CONTRACT DOCUMENTS,
<br />EQUIPMENT MANUFACTURER.
<br />VISIT THE SITE & VERIFY ALL EXISTING CONDITIONS. THE CONTRACTOR SHALL
<br />EQUIPMENT TERMINAL POINT IN WALL
<br />REPORT TO THE ARCHITECT/ENGINEERING FIRM, BEFORE SUBMITTING A BID, ANY
<br />+18" ABOVE FLOOR VERIFY REQUIREMENTS
<br />CONDITIONS WHICH MIGHT MAKE INSTALLATION OF REQUIRED EQUIPMENT A PROBLEM.
<br />WITH EQUIPMENT MANUFACTURER.
<br />NO CONSIDERATION OR ALLOWANCE WILL BE GRANTED FOR FAILURE TO INVESTIGATE
<br />SAFETY DISCONNECT SWITCH -FUSED
<br />CONDITIONS OR MISUNDERSTANDINGS OF THE CONTRACTURAL REQUIREMENTS.
<br />UNLESS NOTED N.F. (NON -FUSED).
<br />rF-Sl
<br />FUSE HOLDER WITH FUSESTAT AND
<br />3.
<br />IT IS THE INTENT OF THESE DRAWINGS TO CALL FOR FINISHED WORK, TESTED
<br />TOGGLE SWITCH.
<br />& READY FOR OPERATION. THE WORD "PROVIDE" MEANS "FURNISHED & INSTALL
<br />MOTOR STARTER -MAGNETIC UNLESS
<br />COMPLETE & READY FOR USE.
<br />NOTED MAN. (MANUAL).
<br />®
<br />ELECTRICAL ALTERNATOR
<br />4.
<br />SEAL ALL FLOOR & FIRE -RATED WALL PENETRATIONS WITH UL APPROVED
<br />G
<br />BRANCH CIRCUIT PANELBOARD
<br />FIREPROOFING MATERIALS.
<br />SURFACE MOUNTED.
<br />5.
<br />PROVIDE MINIMUM #12 AWG WIRE SIZE AND Y4" CONDUIT FOR ALL BRANCH CIRCUITRY.
<br />BRANCH CIRCUIT PANELBOARD
<br />UNLESS OTHERWISE NOTED.
<br />FLUSH MOUNTED.
<br />POWER DISTRIBUTION PANELBOARD OR
<br />6.
<br />MOUNTING HEIGHTS GIVEN ON ELECTRICAL DRAWINGS ARE FOR BIDDING PURPOSES
<br />OTHER ELECTRICAL EQUIPMENT -SURFACE
<br />ONLY. REFER TO ARCHITECTURAL ELEVATION DRAWINGS FOR MOUNTING HEIGHTS
<br />MOUNTED OR FREE STANDING
<br />OF ALL WIRING DEVICES & EQUIPMENT JUNCTION BOXES. WHERE DISCREPANCIES
<br />OCCUR BETWEEN ELECTRICAL & ARCHITECTURAL DOCRMENTS, THE ARCHITECTURAL
<br />POWER DISTRIBUTION PANELBOARD
<br />ELEVATIONS TAKE PRECEDENCE.
<br />FLUSH MOUNTED.
<br />T-30
<br />DRY TYPE TRANSFORMER. NUMBER
<br />7.
<br />FOR ACTUAL LOCATION OF CEILING MOUNTED LIGHTING FIXTURES, SEE
<br />INDICATES KVA SIZE.
<br />ARCHITECTURAL REFLECTED CEILING PLANS.
<br />®
<br />RELAY. RATING AS NOTED.
<br />8.
<br />MECHANICAL DRAWINGS TAKE PRECEDENCE OVER DESCRIPTIONS OF MOTORS &
<br />SPECIAL CABINET OR EQUIPMENT
<br />OTHER MECHANICAL EQUIPMENT. SEE MECHANICAL DRAWINGS FOR ACTUAL
<br />AS NOTED. FLUSH MOUNTED.
<br />LOCATION OF MECHANICAL EQUIPMENT.
<br />CONTACTOR RATINGS AS SCHEDULED.
<br />9.
<br />CAREFULLY COORDINATE ALL ROUGH -IN REQUIREMENTS FOR OWNER FURNISHED
<br />O
<br />DEVICE BRANCH CIRCUIT CONNECTION
<br />EQUIPMENT WITH OWNER & EQUIPMENT SUPPLIERS.
<br />E V
<br />TO ELECTRIC FLUSH VALVE.
<br />COORDINATE WITH DIV.15.
<br />10.
<br />PROVIDE A GREEN INSULATED GROUNDING CONDUCTOR FOR ALL BRANCH CIRCUITS.
<br />0 G
<br />OPERATING ROOM POWER GROUND PANEL
<br />GROUND CONDUCTORS ARE NOT SHOWN IN WIRING DESIGNATION.
<br />WITH FOUR (4) GROUND JACKS, FOUR
<br />(4) DUPLEX HOSPITAL GRADE RECEPTACLES
<br />11.
<br />COORDINATE EQUIPMENT ITEMS NEXT TO DEVICES AND EQUIPMENT
<br />RECEPTACLES AND EQUALIZER GROUND
<br />CONNECTIONS WITH EQUIPMENT PLANS OF THE CONTRACT DOCUMENTS FOR
<br />TERMINAL BUS. ( SEE DETAIL)
<br />ACTUAL LOCATIONS AND EQUIPMENT DESCRIPTIONS.
<br />MGP
<br />MASTER REFERENCE GROUND POINT.
<br />12.
<br />ALL LIFE SAFETY OR LEGALLY REQUIRED LIGHTING CIRCUITS SHALL BE FED WITH #10 AWG.
<br />SPECIAL CABINET OR EQUIPMENT AS NOTED
<br />SURFACE MOUNTED
<br />13.
<br />COORDINATE THE LOCATION OF ALL IN -FLOOR POWER & COMBINATION BOXES
<br />THAT ARE POURED IN -PLACE OR USED IN RAISED FLOORS WITH FURNITURE
<br />UTILITY METER AND TRIM
<br />LAYOUTS & ARCHITECTURAL DETAILING OF COURTROOMS.
<br />NOTES:
<br />1. REFER TO PROJECT MANUAL AND/OR PROJECT
<br />DRAWINGS FOR MOUNTING HEIGHTS.
<br />2. UPPER CASE LETTERS'DD' AT DUPLEX RECEPTACLE
<br />INDICATES DOUBLE DUPLEX RECEPTACLE IN TWO
<br />GANG BOX.
<br />3. LETTERS'WP' AT DEVICE OR EQUIPMENT INDICATES
<br />NEMA 3R TYPE.
<br />4. LETTERS'EX' AT DEVICE INDICATES EXISTING.
<br />5. LETTERS "XP' AT DEVICE OR EQUIPMENT INDICATES
<br />EXPLOSIONPROOF TYPE.
<br />6. LETTERS'TU AT RECEPTACLE INDICATES
<br />TWIST - LOCK TYPE.
<br />S - INDICATES SECURITY TYPE, BY FAILSAFE
<br />CAT. #SSB1-1D
<br />7. LOWER CASE LETTERS AT SWITCHES AND FIXTURES
<br />INDICATES ASSOCIATED UNITS FOR SWITCHING.
<br />8. UPPER CASE LETTERS AT FIXTURE INDICATES
<br />FIXTURE TYPE.
<br />9. NUMBER AT FIXTURE OR OUTLET INDICATES
<br />PANEL CIRCUIT NUMBER.
<br />10. PLUS (+) SIGN WITH DIMENSION AT OUTLET
<br />INDICATES HEIGHT ABOVE FINISHED
<br />FLOOR LINE OR HEIGHT ABOVE FINISHED
<br />GRADE TO CENTER.
<br />GENERAL ELECTRICAL DEMOLITION NOTES:
<br />1. REFER TO ARCHITECTURAL DRAWINGS FOR EXTEND OF
<br />DEMOLITION WORK.
<br />2. VISIT SITE & VERIFY ALL EXISTING CONDITIONS PRIOR
<br />TO SUBMITTING BID. BID SHALL INCLUDE ALL REQUIRED
<br />DEMOLITION & / OR RELOCATION OF EQUIPMENT IN WORK
<br />AREA, WHETHER SUCH WORK IS OR IS NOT INDICATED ON
<br />THE DRAWINGS.
<br />3. RELOCATED EQUIPMENT & EXISTING EQUIPMENT TO REMAIN
<br />AFTER DEMOLITIONS SHALL MEET THE REQUIREMENTS OF
<br />THE NEW CONSTRUCTION WORK.
<br />4. DEMOLITION REQUIRES THE IDENTIFICATION OF CIRCUITS &
<br />THEN THE REMOVAL OF ALL EQUIPMENT.
<br />5. MAINTAIN CONTINUITY OF ALL CIRCUIT AFFECTED BY
<br />DEMOLITION, WHETHER INSIDE OR OUTSIDE OF DEMOLITION
<br />AREA.
<br />6. PATCH WALL PENETRATIONS FOR RELOCATED EQUIPMENT
<br />& RE -CONNECTED CIRCUIT PASSING THROUGH EXISTING
<br />WALLS TO REMAIN.
<br />7. REMOVE ALL UNUSED WIRING & EXPOSED CONDUIT BACK
<br />TO RESPECTIVE PANELBOARDS. CONCEALED CONDUIT MAY
<br />BE ABANDONED IN PLACE WHEN DEMOLITION WOULD NOT
<br />ALLOW EASY REMOVE (IE: CONDUIT IN BLOCK WALLS TO
<br />REMAIN). REMOVE ALL ABANDONED OUTLETS & REPAIR
<br />WALL SURFACES TO MATCH SURROUNDING WALLS.
<br />PLACEMENT OF A " BLANK COVER PLATE " OVER THESE
<br />OUTLETS WILL BE UNACCEPTABLE.
<br />8. COORDINATE NEW CEILING HEIGHTS WITH EXISTING CONDUIT,
<br />WIRE & EQUIPMENT REMAINING. IF THIS EQUIPMENT NEEDS
<br />TO BE EXTENDED OR RELOCATED IT WILL BE A PART OF
<br />THIS DEMOLITION WORK.