Laserfiche WebLink
I I I LIP I I I I I 1 11 11' I ! I 1 I 1 11 1 1 I <br />i 1 I <br />2'-1 5/8" 2'-2" 2'-2" 2'-2" 2'-2" 2'-2" <br />I I I <br />PROPOSED UNISTRUT SUPPORT LAYOUT <br />(RECOMMENDED FINISHED CEILING HEIGHT IS 9'-011) <br />CONSTRUCTION NOTES <br />(CONTRACTOR FURNISHED -CONTRACTOR INSTALLED) <br />QP-1001 UNISTRUT (OR EQUAL) FLUSH WITH FINISHED CEILING AND FIRMLY ANCHORED IN PLACE. <br />EACH CHANNEL SHALL WITHSTAND A VERTICAL LOAD OF 100LBS. PER ANCHORAGE LOCATION, FULL LENGTH SHOWN. <br />PAINT CHANNELS THE SAME COLOR AS THE FINISHED CEILING. REFER TO SUPPORT NOTES. <br />LOCATION OF TWO P-1000 UNISTRUT (OR EQUAL).SUPPORTS FOR RADIATION SHIELD /SURGICAL LIGHT. ATTACH TO THE <br />BOTTOM OF UNISTRUT CHANNELS #1. LOCATION AND LENGTHS DETERMINED BY CENTERLINES OF MOUNTING PLATE #5. <br />OPEN CHANNEL MUST FACE FLOOR. PAINT CHANNEL THE SAME COLOR AS THE CEILING. <br />EACH CHANNEL TO SUPPORT 240 POUNDS STATIC LOAD. REFER TO SUPPORT NOTES. <br />QOMEGA C-ARM BASE PLATE: REFER TO MOUNTING DETAILS. VERIFY LOCATION WITH FULL SIZE TEMPLATE. <br />CONTRACTOR SHALL DRILL ALL ANCHORING HOLES AND ASSIST OMEGA EQUIPMENT INSTALLERS WITH THRU BOLTING. <br />CONTRACTOR IS RESPONSIBLE FOR FLOOR INTEGRITY AND BASE PLATE ANCHORING. <br />OMEGA TABLE BASE PLATE: REFER TO MOUNTING DETAILS. VERIFY LOCATION WITH FULL SIZE TEMPLATE. <br />CONTRACTOR SHALL DRILL ALL ANCHORING HOLES AND ASSIST OMEGA EQUIPMENT INSTALLERS WITH THRU BOLTING. <br />CONTRACTOR IS RESPONSIBLE FOR FLOOR INTEGRITY AND BASE PLATE ANCHORING. <br />CUSTOM FABRICATED CABINET. TYPE, STYLE AND COLOR DETERMINED BY OWNER. <br />PROVIDE ONE 3" DIA. GROMMETED HOLE IN COUNTERTOP FOR CABLE ACCESS NEAR WHERE SHOWN. <br />BRACE CABINET TO SUPPORT 300 POUNDS STATIC LOAD EVERY 48" SPAN. <br />PROVIDE SLIDING SHELF FOR KEYBOARD AND MOUSE. <br />PROVIDE NOTCH IN CABINET FOR A 10"d x 3.5"h WIRE TROUGH WHERE SHOWN IF APPLICABLE. REFER TO ELECTRICAL <br />SHEETS FOR LOCATION OF WIRE TROUGH. <br />CABINET DETAILS ARE PROVIDED FOR CONCEPTUAL PURPOSES ONLY - WORKING DRAWINGS BY OTHERS. <br />MONITORS CAN BE MOUNTED ON COUNTERTOP OR ADJACENT WALL(S) IN ASUNDRIOUS ARAYS. GC SHALL CONSULT WITH <br />FACILITY TO DETERMINE SPECIFIC MOUNTING SYSTEM(S). <br />OPTIONAL MOUNTING BRACKETS FOR THE FLAT PANEL MONITOR(S) SHALL BE INSTALLED BY GENERAL CONTRACTOR. <br />WALL BACKING OR OTHER MEANS OF STRUCTURAL SUPPORT IS STRONGLY RECOMMENDED WHEN INSTALLING WALL <br />BRACKETS. GC SHALL CONSULT WITH FACILITY TO DETERMINE EXACT WALL LOCATION(S), IF ANY, FOR THE FLAT PANEL <br />MONITORS AND TO DETERMINE SPECIFIC WALL MOUNTING SYSTEM(S) IF ANY. <br />QTHE EQUIPMENT LOCATED IN THIS ROOM CREATES 5,550 BTU /HOUR. CUSTOMER /CONTRACTOR SHALL CONSIDER AN <br />AIR CONDITIONING MEANS CAPABLE OF COOLING THE AREA WITH DOORS CLOSED. WORKING DRAWINGS BY OTHERS. <br />EQUIPMENT CLOSET DESIGN: <br />SMALL EQUIPMENT ROOMS HAVE INHERENT ISSUES THAT MUST BE ADDRESSED. THE FACILITY'S DESIGN TEAM SHALL <br />REVIEW HVAC, COOLING, AIR FLOW IN A CONFINED SPACE; WEIGHT DISTRIBUTION, FLOOR LOADING; SERVICE <br />CLEARANCE; INSTALLATION ACCESS, WORK FLOW AREAS; LIGHTING, SHADOWS, EMERGENCY LIGHTING; ELECTRICAL <br />POWER, EMERGENCY POWER; STATIC ELECTRICITY; ACOUSTICS, SOUND NUISANCE; SEISMIC, VIBRATION, SHOCK. <br />EACH EQUIPMENT CABINET HAS A MINIMUM AMOUNT OF SPACE AROUND IT THAT IS REQUIRED TO BE KEPT CLEAR SO <br />THAT SERVICE MIGHT BE PERFORMED AND CABLES / METAL FLEX CONDUIT MAY BE CONNECTED AND DRAPED. EXACT <br />CLEARANCE DIMENSIONS ARE DICTATED BY THE GREATER OF PREVAILING CODE OR THE MANUFACTURER'S <br />SPECIFICATION. REFER TO EQUIPMENT DETAILS. <br />SERVICE CLEARANCES MUST BE UNOBSTRUCTED AND MAINTAINED CLEAR. DO NOT ALLOW SERVICE CLEARANCE AREAS <br />TO BE TEMPORARILY OR PERMANENTLY OCCUPIED. <br />ALLOW ENOUGH ROOM AROUND CABINETS FOR NORMAL WORK FLOW MOVEMENT. CONSIDER THE PLACEMENT OF <br />EQUIPMENT IN RELATION TO DOORS, WINDOWS, COLUMNS, AND WALL MOUNTED DEVICES, SUCH AS SURFACE MOUNTED <br />WIRE TROUGH, CIRCUIT BREAKER PANELS, JUNCTION BOXES, ELECTRICAL OUTLETS, SAFETY EQUIPMENT, FIRE <br />EXTINGUISHERS, AND FURNITURE. <br />ALLOW EASY ACCESS TO ALL EMERGENCY POWER -OFF CONTROLS, CIRCUIT BREAKER PANELS, SMOKE DETECTORS, FIRE <br />EXTINGUISHING SYSTEMS, ETC. <br />RADIATION SHIELD/SURGICAL LIGHT MOUNTING PLATE. ALUMINUM MOUNTING PLATE WILL BE FURNISHED AND INSTALLED <br />BY THE X-RAY EQUIPMENT INSTALLERS. REFER TO PLATE DETAIL. <br />CONSULTING ENGINEERS SHALL ADJUST THE REFLECTED CEILING PLAN ACCORDINGLY. SUPPORT, ABOVE THE CEILING, <br />DESIGNED BY OTHERS. <br />QLOCATION OF TWO LONGITUDINAL RAILS AND CABLE TRACK FOR THE OMEGA OVERHEAD MONITOR BOOM. <br />THE RAILS AND TRACK ARE ATTACHED TO THE BOTTOM OF UNISTRUT CHANNELS. <br />THE RAILS AND TRACK ARE OVERLAYED ON THE UNISTRUT CHANNELS SO THE STRUCTURAL ENGINEER CAN CALCULATE <br />PRIMARY LOADING POINTS. <br />