DIVISION I - GENERAL
<br />SECTION 01045 - CUTTING AND PATCHING
<br />Scope: I. Cutting and patching Includes cutting Into existing construction for the Installation
<br />or performance of other work and patching required to restore the surfaces to their
<br />N original condition.
<br />a. Unless otherwise specifled the requirements for this section also apply to
<br />mechanical and electrical work.
<br />b. Do not cut and patch exposed work In a manner that In the Architect/Engineers
<br />opinion results in lessening the buildings aesthetic qualities. Replace any work
<br />Judged by the Architect/Engineer to be satisfactory.
<br />c. Do not cut and patch exposed work 1n a manner that would result In the
<br />_ reduction of load carrying capacity or load deflection ratio. When In doubt
<br />notify the Architect/Engineer.
<br />N SECTION 01300 SUBMITTAL'S, PRODUCTS, AND SUBSTITUTIONS
<br />o Scope: I. Format for submittals: As required for specific type and by Individual sections.
<br />2. Types of submittals and number of copies.
<br />N
<br />o
<br />a. Shop drawings, reviewed and annotated by the General Contractor: 6 copies
<br />b. Product data - 6 copies
<br />c. Samples - 2, plus extra samples as required to indicate range of color, flnlsh, and
<br />e texture to be expected.
<br />d. Mock-ups - As required In individual sections.
<br />e. Inspection and test reports - 4 copies
<br />e f. Warranties - 2 copies
<br />g.Survey data - 2 copies.
<br />h. Closeout submittals - 2 copies
<br />a
<br />DIVISION 3 - CONCRETE
<br />SECTION 03310 - CAST IN PLACE CONCRETE
<br />Scope: I. Provide cost-in-ploce concrete for general building construction, Including, without
<br />limitation:
<br />e
<br />o. Mlscelloneous patching as required.
<br />Products:
<br />I. Formwork: Plywood forms sufflclent for structural and aesthetic requirements
<br />a-
<br />2. Reinforcements
<br />a. Bars: Deformed steel, ASTM A 615, Grade 60
<br />b. Mesh: Welded wire fabric, ASTM A 185
<br />c. Supports for reinforcement: Use wire type supports complying with CRSI
<br />speclflcatlons.Use plastic supports for epoxy coated reinforcements.
<br />J. Concrete materials:
<br />N
<br />a. Cement: Portland cement, ASTM C150, Type 1.
<br />b. Aggregate: Normal weight aggregates, ASTM C 33.
<br />c. Water: Potable
<br />O
<br />N
<br />d. Fly ash: ASTM C 618 Type C or F. Fly ash not to exceed 20Z of cementltlous
<br />'v
<br />materials.
<br />4. Related Materials:
<br />a. Vapor barrier under slab on grade: 6 mll polyethylene with edges lapped taped.
<br />b. Liquid membrane forming curing compound: liquid type conforming to ASTM
<br />G309 type I-0, Class A dissipating.
<br />c. Hardener: Non- metallic, Inter lor/exterfor type.
<br />5. Concrete Mixes:
<br />a. 3000 psi for footings and slabs on grade
<br />6. Ready made Concrete: Comply with requirements of ASTM C94.
<br />a-
<br />7.Concrete Finishes:
<br />a. Float finish: Monolithic slob surfaces exposed to view.
<br />b. Trowelled Finish.. For all interior slab surfaces.
<br />N
<br />o c. Broom flnlsh: Concrete steps and exterior paving.
<br />d. Scotch flnlsh: Exterior paving base.
<br />M' o e. Hardener: Exposed concrete floors and loading areas.
<br />v
<br />N
<br />DIVISION 6 - WOOD AND PLASTICS
<br />SECTION 06100 - ROUGH CARPENTRY
<br />Scope: I. Provide rough carpentry work
<br />a. Nollers, blocking, furring and sleepers
<br />Products: 1. Lumber, flnlshed 4 sides.197 maximum moisture content.
<br />a. Light framing: Construction grade Douglas fir or southern pine, appearance
<br />grade where exposed.
<br />b. Structural framing and timbers: No. I grade Douglas fir or southern pine,
<br />appearance grade where exposed.
<br />N c. Boards: Construction grade
<br />o
<br />2. Wood for milers, furring and sleepers: Construction grade, flnlshed 4 sides,
<br />19Z moisture content. Pressure preservative treat items in contact with
<br />roof Ing. f lashing, woterproof Ing. masonry, concrete or the ground.
<br />N
<br />J. Plywood, APA rated for use and exposure.
<br />a. Backing: Interior A/C grade.
<br />4. Building paper: Asphalt saturated felt, non -perforated, ASTM D 226, Type 1.30 Ibs
<br />5. Wood treatment:
<br />a. Exterior wood AWPA standard UI and Tl. Categories UCI, UC2, UC3A,
<br />UC3B, CU4A, CU4B Alkaline Copper Ouaternary based treatment.
<br />b. Interior wood AWPA Cl Timber, AWPA C9 Plywood, AWPA C31 Lumber not
<br />°p In contact with ground and protected from water, AWPA 5 Waterborne
<br />Preservatives, AWPA M4 Disodlum Octoborate based treatment.
<br />a 6. Sealants: For settings wood bucks and nailers In exterior openings.
<br />7. Fire Retardant Treated Wood: All wood blocking within the Insulated building
<br />envelope shall be fire retardant treated to comply with AWPA C20 (lumber) and
<br />AWPA C27 (plywood) for treatment type.
<br />a. Provide UL label on each treated. Ready treated lumber.
<br />311312012 9:07:05 AM ...\Cath Lab 'I\cd\A2.2 specs.dgn
<br />SECTION 06400 - ARCHITECTURAL WOODWORK
<br />Scope: 1. Provide shop fabricated woodwork and casework.
<br />Products: I. Ouallty standard for fobrlcotlon and products: Architectural Woodwork Institute
<br />Ouallty Standards, Premium grade flush overlay unless otherwise noted.
<br />2. Wood type
<br />a. Provide sealed plywood at sinks and wet areas.
<br />3. Plastic laminate:
<br />a. Horizontal surfaces: GP-50 (0.050' nominal thickness)
<br />b. Vertical surfaces: GP-28 (0.28' nominal thickness)
<br />c. Seml-exposed surfaces: Plastic laminate BK-20
<br />4. Solid surface countertop
<br />a. As selected by Owner
<br />SECTION 07900 - JOINT SEALERS
<br />Scope: 1. Provide sealant of Intersection of building components.
<br />a. Non-elostomeric caulking compounds for Interior work
<br />Products:
<br />2. Latex (non elostomeric) sealants for Interior Joints.
<br />a. Manufacturers standard one part, non sag acrylic sealant complying with C 834
<br />SECTION 08110 - STEEL DOORS AND FRAMES
<br />Scope: I. Provide hollow metal door frames, sidelight and transom framing.
<br />Products:
<br />I. Frames: Welded construction with mitered corners: gage over 5' wide.
<br />a. Interior frames:16 gage up to 5' wide, 14 gage over 5' wide
<br />b. Exterior frames: 14 gage.
<br />2. Finish: Rust -Inhibiting primer.
<br />J. Fire rating: UL labelled, fIre-rated assembly where required.
<br />DIVISION 9 - FINISHES
<br />SECTION 09250 - GYPSUM DRYWALL
<br />Scope: I. Gypsum drywall including screw type metal support systems.
<br />2. Drywall finishing: To match existing.
<br />J. Moisture resistant gypsum board for installation In wet areas such as toilet rooms,
<br />mop rooms, Janitors closets, food service areas, behind fiberglass showers, and
<br />under the balance of wall the Installations. Do not Install in showers.
<br />4. Cementltious backer board for use in showers..
<br />Products: 1. Gypsum wallboard: ASTM C 36, of types, edge configuration and thickness indicated:
<br />In maximum lengths available to minimize end -to -end butt Joints
<br />a. Type: %' Type 'X'
<br />b. Edges: Tapered
<br />c. Thickness: As indicated, or If not otherwise Indicated, as required to comply
<br />with ASTM C840 for application system and supporting spacing Indicated.
<br />J. Wall/Partition Support Materials:
<br />a. Studs: ASTM C645: 20 gage unless otherwise indicated. Use 16 gage steel studs
<br />at shower seat supports, rolling counter service doors or where required by equipment
<br />4. Celling suspension and furring materials: Steel runners and galvanized hanger
<br />wire; stainless steel wire.
<br />5. Accessories: Galvanized steel corner beads. casing beads, control Joints
<br />6. Acoustical sealant: US Gypsum Acoustical Sealant
<br />SECTION 095I0 - ACOUSTICAL CEILINGS
<br />Scope: I. Provide acoustical ceilings and metal suspension system.
<br />2. Fire Performance Characteristics: Provide materials that are identical to those tested for
<br />the following fire performance characteristics, per ASTM test method Indicated below,
<br />by UL or other testing and Inspecting organizations acceptable to authorities having
<br />jurisdiction. Identify acoustical ceiling components with appropriate markings of
<br />applicable testing and inspecting organizations.
<br />a. Flame spread 25 or less
<br />b. Smoke developed 450 or less
<br />3. Install products per manufacturers recommendations.
<br />Products:
<br />I. Acoustical panels: As selected by Owner
<br />2. Exposed grid suspension system: To match existing.
<br />J. Extra materials
<br />a. Provide additional panels and grid In an amount equal to 2.0 percent of each type
<br />of specifled for maintenance stock.
<br />SECTION 09650 - RESILIENT FLOORING
<br />Scope: I. Provide resilient flooring and base
<br />2. Install per manufacturers recommendations
<br />3.Fire Test Performance: Provide, Class I resilient flooring which compiles with the following
<br />fire test performance criteria as determined by an Independent testing laboratory
<br />acceptable to authorities having Jurisdiction.
<br />a. Critical Radiant Flux (CRF): Not less than the following rating per ASTM E 648.
<br />0.45 watts per sq. cm.
<br />b. Flame Spread: Not more than 25 per ASTM E 84.
<br />c. Smoke Developed: Not more than 450 per ASTM E 84
<br />d. Smoke Density: Not more than 450 per ASTM E662
<br />Products: I. Flooring; As selected by Owner
<br />2. Accessories
<br />a. Wall base: 4' hlgh,%8' thick, matte finish vinyl with preformed corners. As selected by Owner.
<br />J. Adhesives (Cements): Waterproof, stabilized type as recommended by flooring
<br />manufacturer to suit material and substrate conditions.
<br />4. Concrete slob primer: Non -staining type compatible with adhesive as recommended by
<br />flooring manufacturer.
<br />5. Leveling compound: Latex type compatible with adhesive as recommended by
<br />flooring manufacturer.
<br />6. Extra materials:
<br />a. Provide additional resilient flooring for maintenance stock as
<br />directed by Owner.
<br />SECTION 09900 PAINTING
<br />Scope: !.Provide painting and surface preparation for all Interior and exterior surfaces, as required
<br />2. Prepare surface and apply per manufacturers recommendation.
<br />Products: I. Premium products for all systems
<br />2. Interior Point Schedule: New Surfaces:
<br />a. Zinc-cooted Metal
<br />I. Semi -Gloss Alkyd Enamel: 2 flnlsh coots over primer
<br />b. Primed Metal
<br />I. Seml-Gloss Alkyd Enamel: Two coots over existing primer
<br />c. Smooth Finish Dry Wall:
<br />I. Satin or Seml Gloss (Owners Option) Latex Finishes: Two coats over primer
<br />d. Existing Zinc Coated or Primed Metal:
<br />I. Seml Gloss Alkyd Enamel: (2) coats over prepared surface.
<br />DIVISION 10 - SPECIALTIES
<br />SECTION 10190 - Cubicle Curtains
<br />Scope: I. Provide extruded aluminum track for cubicle curtains.
<br />2. Provide cubicle curtains
<br />Products: I. Provide channel track of continuous lengths and curved bends as required by plan.
<br />2. Fittings to be aluminum to match finish of track.
<br />J. Carriers to have nylon wheels and nickel plated brass axles.
<br />4. Curtain: Class A product complying with NFPA 701 Top 20'
<br />of curtain to be open mesh.Color and style to be selected by Owner
<br />DIVISION 10 - SPECIAL CONSTRUCTION
<br />SECTION 13090 - Radiation Protection
<br />Scope: 1. Provide radiation shielding and radiation protection work.
<br />for radiology and radio therapy functions and where indicated
<br />on drawings including existing construction that is being relocated.
<br />2. Refer to report from Certified Health Physicist for required lead thickness.
<br />Products: I. Units lined and fabricated with lead;
<br />a. Doors
<br />b. Door frames
<br />c. Gypsum drywall
<br />d. Control window
<br />e. Sheet lead
<br />Products: I. Lead lined doors and frames where Indicated on plans.
<br />2. Gypsum drywall;
<br />a. ASTM 1396 %' Type 'X' with sheet lead factory bonded to one side.
<br />J. Existing Control window
<br />a. Size and extent as shown on drawings X-ray proof with hollow metal from
<br />and leaded gloss to provide equivalent protection of adjacent partition.
<br />4. Sheet lead,
<br />a. Sheet lead complying with FS00-L-201 grade C.
<br />Ouallty Control:
<br />I. Comply with NCRP standards for Installation.
<br />2. Test in place radiation shielding In accordance with NBS procedures. Testing
<br />to be done by Certified Health Physicist, prior to room occupancy.
<br />ca.fj. )z