DIVISION I - GENERAL <br />SECTION 01045 - CUTTING AND PATCHING <br />Scope: I. Cutting and patching Includes cutting Into existing construction for the Installation <br />or performance of other work and patching required to restore the surfaces to their <br />N original condition. <br />a. Unless otherwise specifled the requirements for this section also apply to <br />mechanical and electrical work. <br />b. Do not cut and patch exposed work In a manner that In the Architect/Engineers <br />opinion results in lessening the buildings aesthetic qualities. Replace any work <br />Judged by the Architect/Engineer to be satisfactory. <br />c. Do not cut and patch exposed work 1n a manner that would result In the <br />_ reduction of load carrying capacity or load deflection ratio. When In doubt <br />notify the Architect/Engineer. <br />N SECTION 01300 SUBMITTAL'S, PRODUCTS, AND SUBSTITUTIONS <br />o Scope: I. Format for submittals: As required for specific type and by Individual sections. <br />2. Types of submittals and number of copies. <br />N <br />o <br />a. Shop drawings, reviewed and annotated by the General Contractor: 6 copies <br />b. Product data - 6 copies <br />c. Samples - 2, plus extra samples as required to indicate range of color, flnlsh, and <br />e texture to be expected. <br />d. Mock-ups - As required In individual sections. <br />e. Inspection and test reports - 4 copies <br />e f. Warranties - 2 copies <br />g.Survey data - 2 copies. <br />h. Closeout submittals - 2 copies <br />a <br />DIVISION 3 - CONCRETE <br />SECTION 03310 - CAST IN PLACE CONCRETE <br />Scope: I. Provide cost-in-ploce concrete for general building construction, Including, without <br />limitation: <br />e <br />o. Mlscelloneous patching as required. <br />Products: <br />I. Formwork: Plywood forms sufflclent for structural and aesthetic requirements <br />a- <br />2. Reinforcements <br />a. Bars: Deformed steel, ASTM A 615, Grade 60 <br />b. Mesh: Welded wire fabric, ASTM A 185 <br />c. Supports for reinforcement: Use wire type supports complying with CRSI <br />speclflcatlons.Use plastic supports for epoxy coated reinforcements. <br />J. Concrete materials: <br />N <br />a. Cement: Portland cement, ASTM C150, Type 1. <br />b. Aggregate: Normal weight aggregates, ASTM C 33. <br />c. Water: Potable <br />O <br />N <br />d. Fly ash: ASTM C 618 Type C or F. Fly ash not to exceed 20Z of cementltlous <br />'v <br />materials. <br />4. Related Materials: <br />a. Vapor barrier under slab on grade: 6 mll polyethylene with edges lapped taped. <br />b. Liquid membrane forming curing compound: liquid type conforming to ASTM <br />G309 type I-0, Class A dissipating. <br />c. Hardener: Non- metallic, Inter lor/exterfor type. <br />5. Concrete Mixes: <br />a. 3000 psi for footings and slabs on grade <br />6. Ready made Concrete: Comply with requirements of ASTM C94. <br />a- <br />7.Concrete Finishes: <br />a. Float finish: Monolithic slob surfaces exposed to view. <br />b. Trowelled Finish.. For all interior slab surfaces. <br />N <br />o c. Broom flnlsh: Concrete steps and exterior paving. <br />d. Scotch flnlsh: Exterior paving base. <br />M' o e. Hardener: Exposed concrete floors and loading areas. <br />v <br />N <br />DIVISION 6 - WOOD AND PLASTICS <br />SECTION 06100 - ROUGH CARPENTRY <br />Scope: I. Provide rough carpentry work <br />a. Nollers, blocking, furring and sleepers <br />Products: 1. Lumber, flnlshed 4 sides.197 maximum moisture content. <br />a. Light framing: Construction grade Douglas fir or southern pine, appearance <br />grade where exposed. <br />b. Structural framing and timbers: No. I grade Douglas fir or southern pine, <br />appearance grade where exposed. <br />N c. Boards: Construction grade <br />o <br />2. Wood for milers, furring and sleepers: Construction grade, flnlshed 4 sides, <br />19Z moisture content. Pressure preservative treat items in contact with <br />roof Ing. f lashing, woterproof Ing. masonry, concrete or the ground. <br />N <br />J. Plywood, APA rated for use and exposure. <br />a. Backing: Interior A/C grade. <br />4. Building paper: Asphalt saturated felt, non -perforated, ASTM D 226, Type 1.30 Ibs <br />5. Wood treatment: <br />a. Exterior wood AWPA standard UI and Tl. Categories UCI, UC2, UC3A, <br />UC3B, CU4A, CU4B Alkaline Copper Ouaternary based treatment. <br />b. Interior wood AWPA Cl Timber, AWPA C9 Plywood, AWPA C31 Lumber not <br />°p In contact with ground and protected from water, AWPA 5 Waterborne <br />Preservatives, AWPA M4 Disodlum Octoborate based treatment. <br />a 6. Sealants: For settings wood bucks and nailers In exterior openings. <br />7. Fire Retardant Treated Wood: All wood blocking within the Insulated building <br />envelope shall be fire retardant treated to comply with AWPA C20 (lumber) and <br />AWPA C27 (plywood) for treatment type. <br />a. Provide UL label on each treated. Ready treated lumber. <br />311312012 9:07:05 AM ...\Cath Lab 'I\cd\A2.2 specs.dgn <br />SECTION 06400 - ARCHITECTURAL WOODWORK <br />Scope: 1. Provide shop fabricated woodwork and casework. <br />Products: I. Ouallty standard for fobrlcotlon and products: Architectural Woodwork Institute <br />Ouallty Standards, Premium grade flush overlay unless otherwise noted. <br />2. Wood type <br />a. Provide sealed plywood at sinks and wet areas. <br />3. Plastic laminate: <br />a. Horizontal surfaces: GP-50 (0.050' nominal thickness) <br />b. Vertical surfaces: GP-28 (0.28' nominal thickness) <br />c. Seml-exposed surfaces: Plastic laminate BK-20 <br />4. Solid surface countertop <br />a. As selected by Owner <br />SECTION 07900 - JOINT SEALERS <br />Scope: 1. Provide sealant of Intersection of building components. <br />a. Non-elostomeric caulking compounds for Interior work <br />Products: <br />2. Latex (non elostomeric) sealants for Interior Joints. <br />a. Manufacturers standard one part, non sag acrylic sealant complying with C 834 <br />SECTION 08110 - STEEL DOORS AND FRAMES <br />Scope: I. Provide hollow metal door frames, sidelight and transom framing. <br />Products: <br />I. Frames: Welded construction with mitered corners: gage over 5' wide. <br />a. Interior frames:16 gage up to 5' wide, 14 gage over 5' wide <br />b. Exterior frames: 14 gage. <br />2. Finish: Rust -Inhibiting primer. <br />J. Fire rating: UL labelled, fIre-rated assembly where required. <br />DIVISION 9 - FINISHES <br />SECTION 09250 - GYPSUM DRYWALL <br />Scope: I. Gypsum drywall including screw type metal support systems. <br />2. Drywall finishing: To match existing. <br />J. Moisture resistant gypsum board for installation In wet areas such as toilet rooms, <br />mop rooms, Janitors closets, food service areas, behind fiberglass showers, and <br />under the balance of wall the Installations. Do not Install in showers. <br />4. Cementltious backer board for use in showers.. <br />Products: 1. Gypsum wallboard: ASTM C 36, of types, edge configuration and thickness indicated: <br />In maximum lengths available to minimize end -to -end butt Joints <br />a. Type: %' Type 'X' <br />b. Edges: Tapered <br />c. Thickness: As indicated, or If not otherwise Indicated, as required to comply <br />with ASTM C840 for application system and supporting spacing Indicated. <br />J. Wall/Partition Support Materials: <br />a. Studs: ASTM C645: 20 gage unless otherwise indicated. Use 16 gage steel studs <br />at shower seat supports, rolling counter service doors or where required by equipment <br />4. Celling suspension and furring materials: Steel runners and galvanized hanger <br />wire; stainless steel wire. <br />5. Accessories: Galvanized steel corner beads. casing beads, control Joints <br />6. Acoustical sealant: US Gypsum Acoustical Sealant <br />SECTION 095I0 - ACOUSTICAL CEILINGS <br />Scope: I. Provide acoustical ceilings and metal suspension system. <br />2. Fire Performance Characteristics: Provide materials that are identical to those tested for <br />the following fire performance characteristics, per ASTM test method Indicated below, <br />by UL or other testing and Inspecting organizations acceptable to authorities having <br />jurisdiction. Identify acoustical ceiling components with appropriate markings of <br />applicable testing and inspecting organizations. <br />a. Flame spread 25 or less <br />b. Smoke developed 450 or less <br />3. Install products per manufacturers recommendations. <br />Products: <br />I. Acoustical panels: As selected by Owner <br />2. Exposed grid suspension system: To match existing. <br />J. Extra materials <br />a. Provide additional panels and grid In an amount equal to 2.0 percent of each type <br />of specifled for maintenance stock. <br />SECTION 09650 - RESILIENT FLOORING <br />Scope: I. Provide resilient flooring and base <br />2. Install per manufacturers recommendations <br />3.Fire Test Performance: Provide, Class I resilient flooring which compiles with the following <br />fire test performance criteria as determined by an Independent testing laboratory <br />acceptable to authorities having Jurisdiction. <br />a. Critical Radiant Flux (CRF): Not less than the following rating per ASTM E 648. <br />0.45 watts per sq. cm. <br />b. Flame Spread: Not more than 25 per ASTM E 84. <br />c. Smoke Developed: Not more than 450 per ASTM E 84 <br />d. Smoke Density: Not more than 450 per ASTM E662 <br />Products: I. Flooring; As selected by Owner <br />2. Accessories <br />a. Wall base: 4' hlgh,%8' thick, matte finish vinyl with preformed corners. As selected by Owner. <br />J. Adhesives (Cements): Waterproof, stabilized type as recommended by flooring <br />manufacturer to suit material and substrate conditions. <br />4. Concrete slob primer: Non -staining type compatible with adhesive as recommended by <br />flooring manufacturer. <br />5. Leveling compound: Latex type compatible with adhesive as recommended by <br />flooring manufacturer. <br />6. Extra materials: <br />a. Provide additional resilient flooring for maintenance stock as <br />directed by Owner. <br />SECTION 09900 PAINTING <br />Scope: !.Provide painting and surface preparation for all Interior and exterior surfaces, as required <br />2. Prepare surface and apply per manufacturers recommendation. <br />Products: I. Premium products for all systems <br />2. Interior Point Schedule: New Surfaces: <br />a. Zinc-cooted Metal <br />I. Semi -Gloss Alkyd Enamel: 2 flnlsh coots over primer <br />b. Primed Metal <br />I. Seml-Gloss Alkyd Enamel: Two coots over existing primer <br />c. Smooth Finish Dry Wall: <br />I. Satin or Seml Gloss (Owners Option) Latex Finishes: Two coats over primer <br />d. Existing Zinc Coated or Primed Metal: <br />I. Seml Gloss Alkyd Enamel: (2) coats over prepared surface. <br />DIVISION 10 - SPECIALTIES <br />SECTION 10190 - Cubicle Curtains <br />Scope: I. Provide extruded aluminum track for cubicle curtains. <br />2. Provide cubicle curtains <br />Products: I. Provide channel track of continuous lengths and curved bends as required by plan. <br />2. Fittings to be aluminum to match finish of track. <br />J. Carriers to have nylon wheels and nickel plated brass axles. <br />4. Curtain: Class A product complying with NFPA 701 Top 20' <br />of curtain to be open mesh.Color and style to be selected by Owner <br />DIVISION 10 - SPECIAL CONSTRUCTION <br />SECTION 13090 - Radiation Protection <br />Scope: 1. Provide radiation shielding and radiation protection work. <br />for radiology and radio therapy functions and where indicated <br />on drawings including existing construction that is being relocated. <br />2. Refer to report from Certified Health Physicist for required lead thickness. <br />Products: I. Units lined and fabricated with lead; <br />a. Doors <br />b. Door frames <br />c. Gypsum drywall <br />d. Control window <br />e. Sheet lead <br />Products: I. Lead lined doors and frames where Indicated on plans. <br />2. Gypsum drywall; <br />a. ASTM 1396 %' Type 'X' with sheet lead factory bonded to one side. <br />J. Existing Control window <br />a. Size and extent as shown on drawings X-ray proof with hollow metal from <br />and leaded gloss to provide equivalent protection of adjacent partition. <br />4. Sheet lead, <br />a. Sheet lead complying with FS00-L-201 grade C. <br />Ouallty Control: <br />I. Comply with NCRP standards for Installation. <br />2. Test in place radiation shielding In accordance with NBS procedures. Testing <br />to be done by Certified Health Physicist, prior to room occupancy. <br />ca.fj. )z <br />Project No. 12010.00 <br />A2,02 <br />02012 BH/PK Architects, Inc. <br />