<br />ELECTRICAL SPECIFICATIONS:
<br />GENERAL PROVISIONS
<br />A. PROVIDE ALL LABOR, MATERIALS AND EQUIPMENT FOR A COMPLETE AND PROPERLY OPERATING
<br />ELECTRICAL SYSTEM. INCLUDE NECESSARY FEES AND PERMITS WITHIN BASE BID.
<br />B. CODES AND STANDARDS
<br />1. ALL WORK SHALL BE PROVIDED IN ACCORDANCE WITH ALLGOVERNING AUTHORITIES LAWS, ORDINANCES,
<br />CODES, RULES AND REGULATIONS WHICH GOVERN THE WORK.
<br />2. THE APPLICABLE GOVERNING AUTHORITIES LAWS, ORDINANCES, CODES, RULES AND REGULATIONS SHALL
<br />CONSIST BASICALLY OF, BUT NOT LIMITED TO, THE FOLLOWING (LATEST EDITIONS):
<br />3. NFPA-1 UNIFORM FIRE CODE,2012
<br />4. CHAPTER 59A-3, 2010 FLORIDA ADMINISTRATIVE CODE
<br />5. 69A-53, F.A.C., STATE FIRE PREVENTION CODE 5TH EDITION.
<br />6. NFPA-70-201 1, NATIONAL ELECTRICAL CODE.
<br />7. NFPA-72-2010, NATIONAL FIRE ALARM CODE.
<br />8. NFPA-99-2012, STANDARD FOR HEALTH CARE FACILITIES
<br />9. NFPA-101 (2012), LIFE SAFETY CODE W/FLORIDA AMENDMENTS.
<br />10. NFPA-1 10 (2010), STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS.
<br />11. NFPA 241 (2009), STANDARD FOR SAFEGUARDING BUILDING CONSTRUCTION AND DEMOLITION OPERATIONS.
<br />12. CHAPTER 395, FLORIDA STATUTES
<br />13. CHAPTER 780, LIGHTNING PROTECTION CODE (2011).
<br />14. FLORIDA FIRE PREVENTION CODE 5TH EDITION AND THE CURRENT ADOPTED CODES AND STANDARDS BY THE
<br />STATE OF FLORIDA.
<br />15. 2010GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTHCARE FACILITIES.
<br />16. FLORIDA BUILDING CODE 5TH EDITION (2014) CHAPTER 449.
<br />17. FLORIDA AMERICANS WITH DISABILITIES, 2007AS DESCRIBED IN ACCESSIBILITY REQUIREMENTS MANUAL,
<br />DEPARTMENT OF COMMUNITY AFFAIRS.
<br />18. LATEST EDITION OF ALLOTHER NFPA ARTICLES NOT LISTED, AS ADOPTED BY THE STATE FIRE MARSHALL.
<br />19. REQUIREMENTS OF THE FLORIDA BUILDING CODE 5TH EDITION (2014).
<br />20. AMERICANS WITH DISABILITY ACT, JANUARY 26,1992.
<br />21. ALL WORK SHALL BE PROVIDED IN ACCORDANCE WITH ALL ANSI STANDARDS ADOPTED BY THE GOVERNING
<br />AUTHORITY. THIS INCLUDES BUT IS NOT LIMITED TO SPECIAL REQUIREMENTS FOR FIRE ALARM, ELEVATORS
<br />AND HANDICAP PERSONS.
<br />22. IT IS THE INTENT OF THE CONTRACT DOCUMENTS TO COMPLY WITH ALL APPLICABLE GOVERNING
<br />AUTHORITIES, LAWS, ORDINANCES, CODES, RULES, REGULATIONS AND STANDARDS. WHERE DISCREPANCIES
<br />OCCUR, NOTIFY THE ARCHITECT/ENGINEER, IN WRITING, AND ASK FOR INTERPRETATION A MINIMUMOF TEN
<br />DAYS PRIOR TO THE BID OF THE CONTRACT DOCUMENTS. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED
<br />AS EVIDENCE THAT THE CONTRACTOR SHALL MEET THIS INTENT. NO ADDITIONAL COMPENSATION SHALL BE
<br />PROVIDED FOR WORK REQUIRED FROM INTERPRETATIONS OF DISCREPANCIES AFTER THE BID.
<br />23. REQUIREMENT OF THE CITY OF ZEPHYRHILLS
<br />C. PERMITS AND INSPECTIONS: OBTAIN AND MAKE ALL PAYMENTS FOR PERMITS AND INSPECTIONS
<br />REQUIRED. AT THE COMPLETION OF THE PROJECT AND BEFORE FINAL ACCEPTANCE OF THE ELECTRICAL
<br />WORK, PROVIDE EVIDENCE OF FINAL INSPECTION AND APPROVAL BY THE AUTHORITIES HAVING
<br />JURISDICTION.
<br />D. CONTRACTOR SHALLTHOROUGHLY INVESTIGATE SITE BEFORE BIDDING. NO CHANGES WILL BE ALLOWED
<br />IN CONTRACT PRICE FOR WORK REQUIRED TO COMPLY WITH EXISTING CONDITIONS.
<br />E. ALL ELECTRICAL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER.
<br />F. PROVIDE PHENOLIC NAMEPLATES ON ALL PANELBOARDS, SWITCHBOARDS, DISCONNECTS,
<br />TRANSFORMERS, ETC, INDICATING DESIGNATION, CIRCUIT NUMBER(S), VOLTAGE AND WHERE UNIT IS FED
<br />FROM. SECURE NAMEPLATES WITH AT LEAST TWO SCREWS OR RIVETS. CEMENTING AND ADHESIVE
<br />INSTALLATION IS NOT ACCEPTABLE.
<br />G. ELECTRICAL CONTRACTOR SHALL EXAMINE ARCHITECTURAL, MECHANICAL, PLUMBING AND FIRE
<br />PROTECTION DRAWINGS FOR ESTIMATING AND CONSTRUCTION OF THIS PROJECT. SUBMISSION OF A
<br />PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER
<br />CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED FOR CONNECTING AND ENERGIZING
<br />EQUIPMENT SHOWN ON THOSE DRAWINGS WILL NOT BE RECOGNIZED.
<br />ELECTRICAL CONTRACTOR SHALL COMMUNICATE DISCREPANCIES TO ENGINEER PRIOR TO SUBMITTING A
<br />BID.
<br />H. PROVIDE TEMPORARY POWER AND LIGHTING. INCLUDE PERMITS AND UTILITY COMPANY FEES FOR
<br />TEMPORARY SERVICES WITHIN BASE BID.
<br />I. CONTRACTOR SHALL SCHEDULE ALL DOWN -TIME WITH THE OWNER PRIOR TO BEGINNING THE WORK.
<br />PREMILIWOVERTIME RATES MAYBE REQUIRED AND MUST BE INCLUDED IN BASE BID.
<br />J. CONTRACTOR SHALLTHOROUGHLY REVIEW CONSTRUCTION DOCUMENTS. WHEN CONFLICTS ARISE WITHIN
<br />CONSTRUCTION DOCUMENTS, CONTRACTOR SHALL NOTIFY ENGINEER PRIOR TO SUBMITTING A BID.
<br />SUBMISSION OF A BID SHALL INDICATE THAT CONTRACTOR THOROUGHLY REVIEWED CONSTRUCTION
<br />DOCUMENTS.
<br />N AVAILABLE R TIME ES NOT PERMIT CONTRACTOR SHALL INCLUDE THE MOST
<br />K. WHEN ENGINEER IS NOT ,0 0 ,
<br />STRINGENT (COSTLY) REQUIREMENTS WITHIN BASE BID.
<br />L. CONTRACTOR S HALLCOORDINATE WITH UTILITY COMPANY AND TELECOMMUNICATION COMPANY FOR
<br />LOCATIONS AND REQUIREMENTS PRIOR TO COMMENCEMENT OF WORK.
<br />M. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING MANUFACTURERS, SUB
<br />CONTRACTORS, VENDORS, AND SUPPLIERS, WITH A COPY OF THESE SPECIFICATIONS.
<br />N. GUARANTEE ALL ELECTRICAL SYSTEM MATERIALS AND WORKMANSHIP TO BE FREE FROM DEFECTS FOR A
<br />PERIOD OF ONE (1) YEAR FROM THE DATE OF FINALACCEPTANCE AND PROPERLY CORRECT LATENT
<br />DEFECTS ARISING WITHIN THIS PERIOD UPON NOTIFICATION BY THE OWNER'S REPRESENTATIVE WITHOUT
<br />ADDITIONAL COMPENSATION.
<br />0. DAILY REMOVE REFUSE AND DEBRIS ACCUMULATING FROM ELECTRICAL CONSTRUCTION AND PRIOR TO
<br />ACCEPTANCE OF THIS WORK, LEAVE THE PREMISES "BROOM CLEAN" INSOFAR AS AFFECTED BY
<br />ELECTRICAL WORK.
<br />P. EQUIPMENT AND DESIGN OF SYSTEMS INDICATED ON THE DESIGN DRAWINGS AND WITHIN THESE
<br />SPECIFICATIONS SHALL BE CONSIDERED AS "SPECIFIED STANDARD" OF QUALITY. NO SUBSTITUTIONS
<br />SHALL
<br />BE MADE WITHOUT WRITTEN APPROVAL OF THE ENGINEER AT LEAST 10 DAYS PRIOR TO BID DATE.
<br />Q. ALL EMERGENCY EGRESS LIGHTING SHALL BE HARDPIPED. NO EXCEPTIONS. NO FLEXIBLE CONDUIT OR
<br />WHIPS IS ALLOWED.
<br />ANY DEVIATION FROM SPECIFIED EQUIPMENT THAT AFFECT THE INSTALLATION, OPERATION,
<br />PERFORMANCE, QUALITY OR LONGEVITY OF THE ELECTRICAL SYSTEMS AS DEFINED HEREIN, SHALL BE
<br />REPLACED BY THE ELECTRICAL CONTRACTOR WITH NO ADDITIONALCOST TO THE CLIENT, IN ADDITION,
<br />ELECTRICAL CONTRACTOR SHALL PROVIDE THE ENGINEERING WITH PHOTOMETRIC FLOOR PLANS FOR ANY
<br />LIGHTING FIXTURES CHANGES FOR APPROVAL AT LEAST 10 DAYS PRIOR TO BID DATE.
<br />BASIC MATERIALS AND METHODS
<br />A. RACEWAYS AND FITTINGS: ALL RACEWAYS AND FITTINGS SHALL BE GALVANIZED RIGID STEEL OR
<br />INTERMEDIATE METAL CONDUIT WITH LOCKNUTS AND BUSHINGS, WITH THE EXCEPTION THAT
<br />WHERE SPECIFICALLY ALLOWED BY THE NATIONAL ELECTRICAL CODE AND APPLICABLE LOCAL CODES.
<br />ELECTRICAL METALLIC TUBING (E.M.T) MAY BE USED FOR ALL INTERIOR EXPOSED AND CONCEALED WORK
<br />WHERE IT IS NOT SUBJECT TO PHYSICAL DAMAGE OR CORROSION. FITTINGS SHALL BE STEEL SET SCREW
<br />TYPE. NO PVC, BX OR MC CABLE ALLOWED. INSTALL EXPANSION FITTINGS IN RACEWAYS EVERY 200, LINEAR
<br />RUN OR WHEREVER STRUCTURAL EXPANSION JOINTS ARE CROSSED.
<br />Al. FOR MEDICAL, DENTAL AND SIMILAR OFFICES AS DEFINED NEC ARTICLE 517 NO NON-METALIC
<br />RACEWAYS SHALL BE USED ANYWHERE AND ONLY MC CABLE LISTED FOR HEALTHCARE USE MAY BE
<br />USED FOR NORMAL POWER RECEPTACLE CIRCUITS, FIXED EQUIPMENT CIRCUITS, SWITCH LEGS AND
<br />LIGHT FIXTURE WHIPS.
<br />B. CONDUCTORS: FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE (412 UNLESS OTHERWISE NOTED)
<br />THWN COPPER. NO ALUMINUM SHALL BE PERMITTED UNLESS SPECIFICALLY" NOTED OTHERWISE, INSTALL ALL
<br />WIRING IN CONDUIT OR APPROVED RACEWAYS UNLESS OTHERWISE INDICATED. PROVIDE 410AWG FOR
<br />BRANCH CIRCUITS OVER 100 FEET IN LENGTH TO ACCOUNT FOR VOLTAGE DROP. PROVIDE #10 GROUND TO
<br />CORRESPOND. ALL BRANCH CIRCUITS SHALL CARRY A GROUNDING EQUIPMENT CONDUCTOR, AND BE WIRED
<br />WITH COLOR -CODED WIRE WITH THE SAME COLOR USED FOR A PHASE THROUGHOUT. COLOR -CODE SHALL
<br />BE AS FOLLOWS:
<br />120/240 VOLT 10: PHASE A - BLACK: PHASE B - RED;
<br />NEUTRAL - WHITE; GROUND -GREEN.
<br />120/208 VOLT 30: PHASE A - BLACK: PHASE B - RED; PHASE C - BLUE;
<br />NEUTRAL - WHITE; GROUND - GREEN.
<br />277/480 VOLT 30: PHASE A - BROWN; PHASE B - ORANGE; PHASE C - YELLOW;
<br />NEUTRAL - LIGHT GREY; GROUND - GREEN.
<br />A DEDICATED NEUTRAL CONDUCTOR SHALL BE INSTALLED FOR ALL CIRCUITS DEDICATED OR NOT. NO
<br />SHARING OF THE NEUTRAL SHALL BE PERMITTED.
<br />C. FINAL CONNECTIONS TO MOTORS OR EQUIPMENT SUBJECT TO VIBRATION SHALL BE MADE UP WITH
<br />GREENFIELD IN DRY LOCATIONS AND WITH JACKETED, LIQUID -TIGHT, FLEXIBLE, GALVANIZED STEEL
<br />CONDUIT IN WET OR DAMP LOCATIONS. LOCATE ALL DEVICES AND EQUIPMENT WHERE SHOWN ON
<br />DRAWINGS. ALL DIMENSIONS SHOWN ON THE DRAWINGS ARE FROM FINISHED FLOOR TO THE CENTER OF
<br />THE DEVICE UNLESS OTHERWISE INDICATED. STANDARD MOUNTING HEIGHTS ARE AS FOLLOWS:
<br />DEVICES HEIGHT AFF AT DEVICE CENTER (NOTE 1)
<br />1. ELECTRICAL OUTLETS 18"
<br />2. ELECTRICAL OUTLETS ABOVE COUNTER 42"
<br />3. TELEPHONE 18"
<br />4. WALLTELEPHONE 54"
<br />5. LIGHT SWITCHES 46"
<br />6. THERMOSTATS SEE MECH SPECS
<br />7. FIRE ALARM DEVICES 80" TO BOTTOM OF GLASS/& PER LATEST ADA REGULATIONS
<br />8. DISCONNECT SWITCHES 60" TO TOP
<br />9. PANELBOARDS 72" TO TOP
<br />10. EXITSIGNS AS NECESSARY
<br />11. SPECIAL DEVICES AS NECESSARY
<br />NOTE 1: IN SPACES SUCH AS, BUT NOT LIMITED TO DENTAL LABS, MEDICAL LABS, SCHOOL LABS, CHIP
<br />PLANTS, ETC. WHERE VENDORS ARE SUPPLYING MILLWORK THE ABOVE REFERENCED HEIGHTS
<br />ARE NOT APPLICABLE. REFER TO THE MILLWORK ELEVATION PLANS TO DETERMINE AN
<br />APPROPRIATE MOUNTING HEIGHT.
<br />D. DISCONNECT SWITCHES: HEAVY DUTY, FUSED OR NON -FUSED AS CALLED FOR ON PLAN DRAWINGS. PROVIDE
<br />SOLID NEUTRAL CONNECTION WHERE REQUIRED. USE.NEMA-1 INDOORS AND NE MA-3R OUTDOORS. ALL
<br />DISCONNECT SWITCHES SHALL BE PROVIDED WITH GROUND KIT.
<br />E. PROVIDE PANELBOARDS OF THE DEAD FRONT TYPE, NO LESS THAN 20 INCHES WIDE AND 5 3/4 INCHES DEEP
<br />WITH QUANTITY OF BRANCH CIRCUITS/CIRCUIT BREAKERS AS INDICATED ON THE PANELBOARD SCHEDULE
<br />WITH THE VOLTAGE. PHASE AND AMPERE RATING AS REQUIRED. ALL PANELBOARDS SHALL HAVE PHASE
<br />SEQUENCE CIRCUITS AND BOLT -ON CIRCUIT BREAKERS. MAIN BREAKERS SHALL BE MOLDED CASE, CIRCUIT
<br />BREAKERS FEEDING HVAC LOADS SHALL BE HACK TYPE. TYPEWRITTEN PANEL DIRECTORIES SHALL BE
<br />PROVIDED AT COMPLETION OF THE PROJECT.
<br />F. ELECTRICAL CONTRACTOR SHALL REVIEW ONE LINE POWER RISER DIAGRAM IN CONJUNCTION WITH
<br />SWITCHGEAR MANUFACTURER REPRESENTATIVE TO CROSS REFERENCE POWER RISER WITH PANEL
<br />SCHEDULES AND VERIFY VOLTAGES, AMPS, LUGS SIZES/ NUMBER AND CABINETS DIMENSIONS PRIOR TO
<br />SUBMITTING A BID.
<br />G. EXERCISE CARE IN CONNECTING THE VARIOUS ELECTRICAL LOADS TO THE PANELS IN ORDER TO ARRIVE AT A
<br />REASONABLE BALANCE BETWEEN LOADS IN EACH PHASE AT EACH PANEL. MAKE TESTS AND ADJUST LOADS
<br />AT EACH PANEL TO RESULT IN REASONABLY BALANCED LOAD CONDITION. SATISFACTORY TO THE UTILITY
<br />COMPANY. ENGINEER, OWNER AND INSPECTION AGENCIES DOCUMENT ALL SAID LOAD ADJUSTMENTS.
<br />H. MANUFACTURERS:BASE OF DESIGN IS SQUARE D.
<br />I. MATERIALS SHALL BE NEW AND UNUSED AND THE CATALOGUED PRODUCTS OF MANUFACTURERS
<br />REGULARLY ENGAGED IN THE PRODUCTION OF SUCH MATERIALS. THE MATERIALS SHALL BE OF THE
<br />MANUFACTURER'S LATEST STANDARD DESIGN THAT COMPLIES WITH THE SPECIFICATION REQUIREMENTS.
<br />J. LIGHTING FIXTURES SHALL BE AS SHOWN ON THE DRAWING AND SHALL BE FURNISHED WITH LAMPS
<br />INSTALLED. CLEAN, RELAMP AND REFURBISH AS REQUIRED FOR LIGHT FIXTURES THAT ARE ETR OR NL.
<br />K. ALL GROUNDING SHALL CONFORM TO ARTICLE 250OF THE NEC REQUIREMENTS. IN ADDITION THERETO AS
<br />IMPOSED BY THE DRAWINGS AND THE LOCAL CODE ENFORCEMENT AUTHORITIES HAVING JURISDICTION.
<br />WHEN THE WATER MAIN METAL PIPE IS USED AS A SUPPLEMENTAL ELECTRODE, CONNECTION SHALL BE MADE
<br />WITHIN 5 FT. OF POINT OF ENTRANCE OF PIPE INTO THE BUILDING. CONNECTIONS OF CONDUCTORS TO
<br />GROUND RODS SHALL BE MADE BY MEANS OF EXOTHERMIC WELD.
<br />L. FIREPROOF ALLOPENINGS ON FIRE RATED WALLS BY AN UL APPROVED SYSTEM.
<br />M. PROVIDE 4" SQUARE BOX AND 3/4" CONDUIT STUB -UP TO ACCESSIBLE CEILING FOR TELEPHONE, TV AND DATA
<br />OU
<br />TLETS, PROVIDE INSULATING BUSHINGS AT BOTH ENDS AND PULL STRING.
<br />N. SUBMITTALS: SUBMIT ELECTRONIC SUBMITTALS VIA E-MAIL FORMATTED AS PDF FILE,
<br />LL BE SEALED USING AN UL APPROVED
<br />0, CONDUIT PENETRATIONS RATIONS THROUGH FIRE RATED PARTITIONS SHALL
<br />SYSTEM. REFER TO ARCHITECTURAL FLOOR PLAN FOR LOCATION OF FIRE RATED PARTITIONS. PROVIDE
<br />ACOUSTICAL FOAM SEALANT AT ALL DEVICES ON DEMISING PARTITIONS. IF PARTITION IS FIRE RATED,
<br />PROVIDE FIREPROOF COMPOUND ON BACK AND SIDES OF THE BOX. WHERE TELEPHONE AND ELECTRICAL
<br />OUTLETS APPEAR ON PLANS AS BACK TO BACK, OUTLETS SHALL BE STAGGERED TO REDUCE NOISE
<br />TRANSMISSION. WHERE WALLS AND PARTITIONS ARE REQUIRED TO HAVE A MINIMUM OF 1-HOUR
<br />FIRE -RESISTANCE RATING, BOXES SHALL BE SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES
<br />OR PROTECTED WITH UL LISTED PUTTY PADS.
<br />P. CABLES NOT ENCLOSED IN CONDUITS WITHIN CEILING SPACES SHALL BE AIR PLENUM RETURN FIRE RATED
<br />AND MEET THE REQUIREMENTS OF SECTION 602OF F.M.C.
<br />Q. PROVIDE DISK FILE ON CAD 2013 RELEASE WITH "AS BUILT" ELECTRICAL DRAWINGS AT THE COMPLETION OF
<br />THE PROJECT.
<br />R. CONTRACTOR REPRESENTS THAT HIS BID IS BASED UPON THE MANUFACTURER'S MATERIALS AND
<br />EQUIPMENT DESCRIBED IN THE CONTRACT DOCUMENTS.
<br />S. ELECTRICAL CONTRACTOR SHALL REVIEW THE ARCHITECTURAL DRAWINGS FOR DEVICES EXACT LOCATIONS,
<br />MOUNTING HEIGHTS AND QUANTITIES PRIOR TO BID AND PRIOR TO ROUGH -IN. NOTIFY THE ENGINEER
<br />IMMEDIATELY IF ANY DISCREPANCIES ARE FOUND.
<br />T. FINAL QUANTITY OF EXIT AND EMERGENCY LIGHTS TO BE DETERMINED BY FIRE MARSHALL. INCLUDE
<br />CONTINGENCY FOR 2 ADDITIONAL EXIT LIGHTS AND 2 ADDITIONAL EMERGENCY,
<br />U. PROVIDE SWITCHBOARDS WITH THE VOLTAGE AND AMPERE RATINGS FOR THE MAIN BREAKER, THE MAIN BUS
<br />AND THE FEEDER BREAKERS AS INDICATED ON THE ONE -LINE POWER RISER DIAGRAM.
<br />1. BUS BARS OF SILVER-PLATED COPPER OR TIN-PLATED ALUMINUM.
<br />2. MOLDED CASE BREAKERS FOR THE MAIN AND FEEDERS,
<br />3. BUS BARS OF SILVER-PLATED COPPER OR TIN-PLATED ALUMINUM.
<br />4. PROVISIONS FOR PADLOCKING THE CIRCUIT BREAKER HANDLES ON THE "ON" AND "OFF"
<br />POSITION.
<br />5, PROVIDE RUBBER INSULATION FLOOR MAT IN FRONT OF SWITCHBOARD FOR ENTIRE LENGTH OF
<br />CENTER AND 4 FEET WIDE.
<br />V. SWITCHBOARDS, MOTOR CONTROLCENTERS AND TRANSFORMERS SHALL BE MOUNTED ON 4" THICK
<br />CONCRETE HOUSEKEEPING PADS. HOUSEKEEPING PADS SHALL EXTEND AT LEAST 2" BEYOND ALL SIDES,
<br />FRONT AND BACK OF THE EQUIPMENT EXCEPT WHERE EQUIP. EXTENDS TO WALLS. EXTENSIONS BEYOND
<br />SIDES OF THE EQUIPMENT SHALL BE BEVELED.
<br />W. ELECTRICAL CONTRACTOR MAY COMBINE CIRCUITS IN A COMMON RACEWAY AS LONG AS CONDUCTORS ARE
<br />DEBATED AS PER NEC. SHARED NEUTRAL SHALL NOT BE ALLOWED UNLESS OTHERWISE INDICATED.
<br />X. ELECTRICAL CONTRACTOR SHALL INCLUDE TRENCHING AND BACKFILLING, CORE DRILLING, CUTTING AND
<br />PATCHING FOR THE INSTALLATION OF HIS/HER WORK WITHIN BASE BID.
<br />Y. CLEAN ALL LIGHT FIXTURES, LAMPS AND LENSES AND PANELBOARD INTERIORS PRIOR TO FINAL
<br />ACCEPTANCE.
<br />Z. SERVICE LATERALS THAT ARE NOT ENCASED IN CONCRETE AND THAT ARE BURIED 18 IN. (457 MM) OR MORE
<br />BELOW GRADE SHALL HAVE THEIR LOCATION IDENTIFIED BY A WARNING RIBBON THAT IS PLACED IN THE
<br />TRENCH AT LEAST 12 IN. (305 MM) ABOVE THE UNDERGROUND INSTALLATION.
<br />AA. REVIEW AND COORDINATE WITH MECHANICAL DRAWINGS FOR EQUIPMENT, CONDUIT, DEVICES, ETC.,
<br />REQUIRED FOR A COMPLETE AND OPERATING HVAC SYSTEM.
<br />BB. PROVIDE BACK BOXES AND RACEWAY FOR DOOR ACCESS CARD READERS AND ELECTRIC STRIKES AS PER
<br />SECURITY CONTRACTOR DIRECTIONS. PROVIDE 120VAC TO EACH ELECTRIC STRIKE DOOR LOCATION AND TO
<br />ACCESS CONTROL SYSTEM PANEL. ACCESS CONTROL SYSTEM MUST DEACTIVATE OR OPEN ANY DOOR
<br />LOCKING MECHANISM AND REMAIN IN FAIL SAFE POSITION WHENEVER FIRE ALARM SYSTEM IS ACTIVATED OR
<br />BUILDING POWER FAILS. PROVIDE "PUSH -TO -EXIT' PUSHBUTTON AND MOTION DETECTOR AT EACH ACCESS
<br />DOOR LOCATION. INTERLOCK WITH FIRE ALARM SYSTEM.
<br />CC. CONTRACTOR REPRESENTS THAT HIS BID IS BASED UPON THE MANUFACTURER'S MATERIALS AND
<br />EQUIPMENT DESCRIBED IN THE CONTRACT DOCUMENTS.
<br />DD. E LECTRICAL CONTRACTOR SHALLFILL UTILITY SERVICE INFORMATION FORMS AND BUILDING DEPARTMENT
<br />ELECTRICAL PERMIT FORMS.
<br />EE. PROVIDE AND INSTALL PHASE LOSS PROTECTORS WITH AUTO RESET FOR ALL 10 AND 30 EQUIPMENT SHOWN
<br />ON MECHANICAL PLANS THAT HAVE AT LEAST 2 HOT CONDUCTORS. SEE DIAGRAMS, THIS SHEET.
<br />FF. ALL UNDERGROUND CONDUITS SHALL BE PROVIDED WITH PULL STRING AND BOTH ENDS SHALL BE
<br />PROPERLY IDENTIFIED AND MARKED. PROVIDE CAPS TO AVOID MATERIAL INTRUSION.
<br />WHERE AN UNDERGROUND RACEWAY ENTERS A BUILDING OR STRUCTURE, IT SHALL BE SEALED AS PER
<br />NEC ARTICLES 230.8 AND 300.5(G).
<br />CONDUITS STUB -UPS WITHIN BUILDING SHALL BE MADE WITH GALVANIZED RIGID CONDUIT. NO
<br />NON-METALLIC RACEWAY ALLOWED WITHIN BUILDING (ASSEMBLY OCCUPANCY, NEC ARTICLE 518).
<br />GG. THE CEILING SPACE OF THIS PROJECT IS A RETURN AIR PLENUM. ALL MATERIALS IN THIS AREA MUST BE
<br />PLENUM RATED AND MEET THE REQUIREMENTS OF SECTION 602 OF THE F.M.C.
<br />HH. COORDINATE WITH MECHANICAL CONTRACTOR FOR INSTALLATION OF MOTOR STARTERS AND VFD'S
<br />FURNISHED BY MECHANICAL.
<br />II. PRIOR TO TRENCHING IN ANY AREA, THE CONTRACTOR SHALLCONTACT ELECTRICAL. COMMUNICATION/DATA,
<br />CABLE TV, GAS, STORM, CHILL WATER, SANITARY AND WATER UTILITY PROVIDERS. HAVE ALL THE UTILITIES IN
<br />THE AREA IDENTIFIED. IN ADDITION, THE CONTRACTOR SHALL OBTAIN THE SERVICES OF A SUBCONTRACTOR
<br />SPECIALIZING IN THE LOCATION OF UNDERGROUND STRUCTURES, MEMBRANES, ETC. TO IDENTIFIED ANY
<br />OBSTACLES IN THE PATH OF TRENCHING PRIOR TO COMMENCING WORK. DAMAGE TO ANY UNDERGROUND
<br />STRUCTURES SHALL BE REPAIRED BY THE CONTRACTOR AT NO ADDITIONALCOST TO THE PROJECT.
<br />JJ. ELECTRICALCONTRACTOR SHALL INSTRUCT OWNER REPRESENTATIVE REGARDING EQUIPMENT OPERATION
<br />AND MAINTENANCE AT COMPLETION OF WORK. PROVIDE OWNER WITH ALL MANUALS PERTAINING TO THE
<br />PROJECT.
<br />KK, LOW VOLTAGE CABLES FOR SECURITY SYSTEM, AV SYSTEM, TELEPHONE SYSTEM AND DATA SYSTEM ARE
<br />NOT PART OF THIS ENGINEER'S SCOPE OF WORK.
<br />ILL. MINIMUM EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A PERIOD OF 1 1/2 HOURS IN THE EVENT OF
<br />FAILURE OR NORMAL LIGHTING, WITHIN THE WORK AREAS. EMERGENCY LIGHTING FACILITIES SHALL BE
<br />ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS AT LEAST AN AVERAGE OF 1 FOOTCANDLE (10 LUX) AND
<br />A MINIMUM AT ANY POINT OF 0.1 FOOTCANDLE (1 LUX) MEASURED ALONG THE PATH OF EGRESS AT FLOOR
<br />LEVEL.
<br />MM. REVIEW AND COORDINATE WITH MECHANICAL DRAWINGS FOR EQUIPMENT, CONDUIT, DEVICES, ETC.
<br />REQUIRED FOR ACOMPLETE AND OPERATING HVAC SYSTEM. LOW VOLTAGE CONTROL WIRING FURNISHED
<br />AND INSTALLED BY MECHANICAL. CHECK ALL MOTORS AND ROTATING EQUIPMENT FOR PROPER ROTATION,
<br />NN. PROVIDE LIGHTNING PROTECTION TO ALL ROOF MOUNTED EQUIPMENT PROVIDED WITHIN THIS SCOPE OF
<br />WORK. INTERCONNECT TO EXISTING LIGHTNING PROTECTION SYSTEM.
<br />NURSE CALL
<br />F_----
<br />-
<br />SYMBOL
<br />i
<br />DESCRIPTION
<br />(NBMS
<br />NURSE CALL MASTER STATION
<br />NCTC
<br />NURSE CALL TERMINATION CABINET
<br />CB
<br />CODE BLUE STATION
<br />i B
<br />SHOWER STATION
<br />FB
<br />DUTY STATION
<br />{S)
<br />I- -
<br />STAFF STATION
<br />D D
<br />CORRIDOR DOME LIGHT
<br />t--
<br />II _ B
<br />CORRIDOR ZONE LIGHT CEILINGAVALL
<br />j F ] -
<br />SINGLE PATIENTSTATION(W/2-WAY AUDIO)
<br />I [I-
<br />TOILET PULLCORD STATION
<br />B�--
<br />BATH PULL CORD STATION
<br />DP�
<br />DUAL PATIENT STATION (W/2-WAY AUDIO)
<br />BB
<br />f
<br />STAFF EMERGENCY AUDIBLENISUAL INDICATING APPLIANCE
<br />37)
<br />L_
<br />37 PIN BED CONNECTOR
<br />PER AHCA REGULATIONS/MANUFACTURERS SPECIFICATIONS PULL CORD STATION IN SHOWER
<br />MUST BE MOUNTED ABOVE THE SHOWER HEAD AND ON THE SAME WALLAS THE SHOWER HEAD.
<br />1. PROVIDE A WATER RESISTANT GASKET KIT. INSTALLON SHOWER WALL WITH SHOWER HEAD.
<br />2. STATIONS SHALL BE LOCATED WITHIN 12" OF THE FRONT OF THE TOILET BOWL AND T TO 4'
<br />ABOVE THE FLOOR PER FGI GUIDELINES 2.1-8.3.7.3(3),
<br />3. STATIONS IN SHOWER AND TUBS SHALL BE LOCATED 570 6' ABOVE THE FLOOR, WITHIN
<br />NORMAL VIEW OF THE USER AND WITHIN REACH OF THE STAFF WITHOUT THE NEED TO STEP INTO
<br />THE STALL OR TUB PER FGI GUIDELINES. FIELD VERIFY EXACT LOCATIONS. ALL ROOMS SHALL
<br />HAVE CONSISTENT LOCATIONS.
<br />EQUIPMENT LISTING NOTES:
<br />ALL EQUIPMENT IN THIS PROJECT SHALL BE UL LISTED (OR US EQUIVALENT)
<br />PER THE F.B.C. IF ANY EQUIPMENT IS NOT LISTED A FIELD LISTING BY AN OSHA
<br />APPROVED THIRD PARTY WILL BE REQUIRED AS FOLLOWS:
<br />1. EQUIPMENT SUPPLIERNENDOR SHALL SUPPLY DOCUMENTATION, OSHA
<br />APPROVED THIRD PARTY LISTINGS, AND E-FILES FOR ALL EQUIPMENT, WIRING,
<br />TRANSFORMERS, LIGHTS, ETC. IN THIS PROJECT TO AN ENGINEER WITH
<br />PENINSULA ENGINEERING SEVEN (7) WORKING DAYS PRIOR TO INSPECTION
<br />FOR REVIEW AND APPROVAL
<br />2. DEVICES THAT DO NOT MEET OSHA APPROVED THIRD PARTY LISTINGS OR
<br />ARE NOT LISTED SHALL BE FIELD LISTED BY A QUALIFIED AGENCY PRIOR TO
<br />INSPECTION AND DOCUMENTATION SHALL BE PROVIDED. THIS SHALL BE THE
<br />RESPONSIBILITY OF THE EQUIPMENT MANUFACTURER.
<br />3. ALL EQUIPMENT SHALL BE UL 60601 COMPLIANT.
<br />ELECTRICAL SYMBOL LEGEND:
<br />NOTE: NOT ALL SYMBOLS USED IN THIS PROJECT
<br />2x4 AND 2x2 RECESSED FLUORESCENT LIGHT FIXTURE TO NORMALCIRCUIT
<br />FLUORESCENT FIXTURE CONNECTED TO CRITICAL CIRCUIT
<br />FLUORESCENT FIXTURE CONNECTED TO EMERGENCY CIRCUIT
<br />-.
<br />FLUORESCENT FIXTURE CONNECTEDTO LIFE SAFETYCIRCUIT
<br />N - L t N '
<br />FLUORESCENT FIXTURE CONNECTED TO UNSWITCHED CIRCUIT
<br />I-4--�
<br />STRIP FLUORESCENT LIGHT FIXTURE -CEILING, WALL MOUNTED
<br />O (2 INCANDESCENT, HID OR COMPACT FLUORESCENT FIXTURE - CEILING MOUNTED, WALL MOUNTED
<br />SITE LIGHTING FIXTURE
<br />® T EXIT SIGN FIXTURE, SHADED QUADRANT INDICATES FACE, WITH ARROWS AS SHOWN ON PLAN - CEILING
<br />MOUNTED, WALL MOUNTED
<br />B EMERGENCY LIGHTING FIXTURE
<br />S S 2$ 3$ 4 1-POLE, 2-POLE, 3-WAY, 4-WAY SWITCH
<br />MS MOTION SENSOR LIGHT SWITCH
<br />Mi FM 2OCCUPANCY SENSORS. REFER TO LIGHTING PLAN
<br />PP POWER PACK. REFER TO LIGHTING PLAN
<br />$ K KEYSWITCH
<br />D INCANDESCENT DIMMER SWITCH, 1-POLE, 3-WAY, 4-WAY SWITCH
<br />M MP MANUAL MOTOR STARTER TOGGLE SWITCH AS NOTED; "P" INDICATES PILOT LIGHT; "WP" INDICATES
<br />wP
<br />WEATHERPROOF
<br />0 W o (o DUPLEX RECEPTACLE AT 18"!AS NOTED, ABOVE COUNTER AT
<br />C G 42"/AS NOTED, CEILING MOUNTED, GROUND FAULT TYPE, ISOLATED GROUND
<br />B TYPE, WEATHERPROOF TYPE,(REFER TO NOTE 10 BELOW) SIMPLEX (AS NOTED)
<br />IG WP
<br />(2) DUPLEX RECEPTACLES IN SINGLE OUTLET BOX WITH
<br />B_ SINGLE COVER PLATE AT 18"/AS NOTED, ABOVE COUNTER AT 42"/AS NOTED 1
<br />$C or 1-POLE SWITCH CONNECTED TO CRITICAL CIRCUIT (RED DEVICE) -QUIET TYPE
<br />DUPLEX RECEPTACLE (RED DEVICE) AT 18"/AS NOTED, ABOVE COUNTER AT 42"/AS NOTED CONNECTED TO
<br />CRITICALCIRCUIT
<br />(2) DUPLEX RECEPTACLE (RED DEVICES) IN SINGLE OUTLET BOX WITH
<br />SINGLE COVER PLATE AT 167AS NOTED, ABOVE COUNTER AT 42VAS NOTED CONNECTED TO CRITICAL
<br />CIRCUIT
<br />0 0 ❑ SPECIAL MOUNTED RECEPTACLE AS NOTED, PUSHBUTTON AS NOTED, TELE-POWER POLE
<br />\ [(] FINALCONNECTION TO EQUIPMENT
<br />B B�FT] JUNCTION BOXES, MOTOR, TRANSFORMER
<br />E::]= FUSED DISCONNECT SWITCH, NON FUSED DISCONNECT, MOTOR STARTER OR CONTACTOR, COMBINATION
<br />®lSTARTER/DISCONNECT, ENCLOSED CIRCUIT BREAKER
<br />llllllll� 120/208OR 120/240V PANELBOARD
<br />277/480V PANELBOARD
<br />lira_] SYSTEMS CABINET -FLUSH MOUNTED, SURFACE MOUNTED (AS NOTED)
<br />TELEPHONE TERMINALS TELEPHONE SYSTEM RACEWAY
<br />BOARD,
<br />CONNECTION TO GROUND
<br />W P TELEPHONE OUTLET AT 18", WALL TELEPHONE OUTLET AT 54%ABOVE COUNTER, PAY TELEPHONE OUTLET.
<br />V V V V PROVIDE 4'SO. MASONRY (DEEP) BOX AND 1" CONDUIT (WITH INSULATING BUSHING) TO ACCESSIBLE CEILING
<br />COMPUTER OUTLET, COMPUTER OUTLET 48 , PHONE/DATA PROVIDE 4" SQUARE MASONRY BOX AND r CONDUIT
<br />17 17 v (WITH INSULATING BUSHING) TO ACCESSIBLE CEILING
<br />TV OUTLET, PROVIDE 4" SQUARE BOX AND 3/4" CONDUIT TO ACCESSIBLE CEILING. MOUNT @ IT TO THE
<br />TV CENTER UNLESS OTHERWISE NOTED.
<br />SMOKE DETECTOR, SMOKE DUCT DETECTOR
<br />WAP WIRELESS ACCESS POINT
<br />O VOLUME CONTROL
<br />SO SPEAKER
<br />B HEAT DETECTOR
<br />B DUCT/SMOKE DETECTOR REMOTE INDICATOR LIGHT W/KEYED TEST SWITCH
<br />SHUTDOWN RELAY, 24V DC
<br />B LOCK BOX
<br />MANUAL PULL STATION, FLUSH
<br />HORN AND STROBE LIGHT, FLUSH MOUNTED
<br />C
<br />Bi WALIJCEILING MOUNT STROBE
<br />VE VOICE EVAC SPEAKER
<br />VE VOICE EVAC SPEAKER AND STROBE LIGHT, FLUSH MOUNTED
<br />H+ DOOR HOLDER
<br />TC TIMECLOCK
<br />ITS] TAMPER SWITCH
<br />FS FLOWSWITCH
<br />CM FIRE ALARM CONTROL MODULE "C" INDICATES CEILING MOUNTED
<br />BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR IN WALL, SLASH MARKS INDICATE NUMBER OF
<br />CONDUCTORS, LONGER SLASH IS NEUTRAL, (GROUND WIRE NOT SHOWN). 2 #12,1 #12 GROUND IN A 3/4"
<br />CONDUIT MINIMUM (UNLESS OTHERWISE NOTED OR MARKED). QUANTITY OF ARROWS INDICATE QUANTITY
<br />OF HOMERUNS TO PANELBOARD. PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN ALL BRANCH CIRCUITS.
<br />BRANCH CIRCUIT CONDUIT CONCEALED BELOW SLAB OR UNDERGROUND.
<br />ELECTRICAL SYMBOL LEGEND NOTES:
<br />1. AN OUTLET BOX OF THE APPROPRIATE SIZE AND TYPE SHALL BE PROVIDED FOR ALL DEVICES, LIGHTING
<br />FIXTURES, SWITCHES, RECEPTACLES, ETC.
<br />2. A DEDICATED NEUTRAL CONDUCTOR SHALL BE INSTALLED FOR ALLCIRCUITS DEDICATED OR NOT. NO
<br />SHARING OF THE NEUTRAL SHALL BE PERMITTED.
<br />3. SWITCHES AND RECEPTACLES SHALL BE SPECIFICATION GRADE 20A MINIMUM. ALL RECEPTACLES IN
<br />PATIENT CARE AREAS SHALL BE HOSPITAL GRADE 20A MINIMUM UNLESS OTHERWISE NOTED. ALL NORMAL
<br />DEVICES TO BE IVORY (COORDINATE COLOR WITH ARCHITECT PRIOR TO ORDER) AND ALL CRITICAL
<br />DEVICES TO BE RED.
<br />4. ELECTRICAL CONTRACTOR MAY COMBINE SAME CIRCUIT TYPES IN A COMMON RACEWAY AS LONG AS
<br />CONDUCTORS ARE DEBATED AS PER NEC. SHARED NEUTRALS SHALL NOT BE ALLOWED. A DEDICATED
<br />NEUTRAL SHALL BE PROVIDED FOR EACH CIRCUIT PER 2008 NEC.
<br />5. COORDINATE ALL LOCATIONS, HEIGHTS AND COLORS WITH ARCHITECTURAL DRAWINGS/DIAGRAMS PRIOR
<br />TO ROUGH IN.
<br />6. ALL NEW AND EXISTING COVER PLATES IN THE PROJECT AREA SHALL BE ENGRAVED WITH PANEL AND
<br />CIRCUIT INFORMATION. METAL PLATES SHALL BE RED LETERING FOR CRITICAL CIRCUITS AND
<br />BLACK LETTERING FOR NORMALCIRCUITS. PHENOLIC PLATES SHALLBE A RED PLATE WITH WHITE
<br />LETTERING FOR CRITICAL CIRCUITS AND IVORY/WHITE/MATCH EXISTING PLATES WITH BLACK LETTERING
<br />FOR NORMAL CIRCUITS.
<br />7. PROVIDE A PULL STRING IN ALL EMPTY CONDUITS.
<br />8. ALLJUNCTION BOX COVERS SHALL BE MARKED WITH PANEL, CIRCUIT NUMBER AND VOLTAGE WITH
<br />PERMANENT BLACK MARKER.
<br />9. JUNCTION BOXES SHALL NOT BE MOUNTED TO THE PARTITION TOP PLATE.
<br />10. SECTION 406.8 OF THE 2008 NEC CODE MANDATES ALL NON -LOCKING 15A AND 20A RECEPTACLES IN DAMP
<br />OR WET LOCATIONS SHOULD BE LISTED WEATHER RESISTANT.
<br />11. PROVIDE ACOUSTICAL FOAM AND SEALANT AT ALL DEVICES ON DEMISING PARTITIONS. IF PARTITION IS
<br />FIRE
<br />RATED, PROVIDE FIREPROOF COMPOUND ON BACK AND SIDES OF THE BOX OR 5 SIDED WITH APPROVED
<br />MATERIALAS REQUIRED.
<br />12. WHERE TELEPHONE AND El ECTRICALOUTLETS APPEAR ON PLANS AS BACK TO BACK, OUTLETS SHALL BE
<br />STAGGERED TO REDUCE NOISE TRANSMISSION. WHERE WALLS AND PARTITIONS ARE REQUIRED TO HAVE
<br />A
<br />MINIMUM OF 1-HOUR FIRE -RESISTANCE RATING, BOXES SHALL BE SEPARATED BY A MINIMUM HORIZONTAL
<br />DISTANCE OF 24" INCHES OR PROTECTED WITH UL LISTED PUTTY PADS.
<br />13. THE ELECTRICAL CONTRACTOR SHALL COORDINATE EXACT MOUNTING AND INSTALLATION REQUIREMENTS
<br />FOR PAY TELEPHONE OUTLET.
<br />14. THE ELECTRICAL CONTRACTOR SHALLCOORDINATE EXACT MOUNTING OF RECEPTACLES SERVING
<br />ELECTRIC WATER COOLERS TO ENSURE THAT THE POWER CORD IS FULLY CONCEALED.
<br />15. PROVIDE LABELS ON POWER POLES INDICATING PANELAND CIRCUIT NUMBER.
<br />16, WHEN PRICING FLOOR BOXES OF POKE-THRU DEVICES, ELECTRICAL CONTRACTOR SHALL INCLUDE X-RAY
<br />OF SLAB, CORE DRILLING, FIREPROOFING, AND PROTECTION OF FLOOR BELOW.
<br />IT PROVIDE 4" SQUARE BOX AND 1" CONDUIT STUB -UP TO ACCESSIBLE CEILING FOR TELEPHONE AND DATA
<br />OUTLETS. TERMINATE CONDUITS T ABOVE CEILING IN ACCESSIBLE SPACE WITH 90' BEND INSULATED
<br />BUSHINGS AND PULL STRING. COORDINATE WITH TENANTS DATA(TELEPHONE CONTRACTOR FOR FUR
<br />FURTHER ELECTRICAL AND RACEWAYS REQUIREMENTS. CABLING BY OTHERS.
<br />18. GROUNDING OF RECEPTACLES AND FIXED EQUIPMENT IN PATIENT CARE AREAS SHALL COMPLY WITH NEC
<br />ARTICLE 517,13 (A) AND (B).
<br />19. RECEPTACLES LOCATED WITHIN THE EXAM ROOMS, BATHROOMS, PLAYROOMS, WAITING, ACTIVITY ROOMS
<br />AND PATIENT CARE AREAS OF PEDIATRIC WARDS AND CHILD CARE FACILITIES SHALL BE LISTED TAMPER
<br />RESISTANT.
<br />HOSPITAL SPECIAL REQUIREMENTS:
<br />1. NOTIFY PROJECT COORDINATOR WHEN PROJECT IS TO COMMENCE & PROVIDE PROPOSED PROJECT
<br />SCHEDULE.
<br />2. MEET WITH AND REVIEW PROGRESS OF CONSTRUCTION & AS -BUILT RECORD DRAWINGS WITH (&AT A FREQUENCY
<br />SET BY) PROJECT COORDINATOR.
<br />3. PROVIDE WRITTEN NOTIFICATION TO PROJECT COORDINATOR OF TIMES & DATES FOR BUILDING
<br />INSPECTIONS OR REVIEW OF CONSTRUCTION BY AUTHORITIES HAVING JURISDICTION.
<br />4. PROVIDE COMPLETED FACILITY ENGINEERING DEPARTMENT EQUIPMENT REGISTRATION FORMS FOR ADDITION,
<br />DELETION, RELOCATION OR PROVISION OF NEW ELECTRIC CIRCUITS, ELECTRICAL PANELS, VALVES OR OTHER
<br />EQUIPMENT. BLANK FORMS ARE AVAILABLE FROM HOSPITAL ENGINEERING DEPARTMENT.
<br />5. COMPLY WITH FACILITY ENGINEERING DEPARTMENT STANDARDS FOR EQUIPMENT / POWER PANEL/SYSTEM PANEL/
<br />DISCONNECT NAMEPLATING, PIPE LABELING, &VALVE TAGGING.
<br />6. MAKE CONNECTIONS TO EXISTING SYSTEMS AT APPROVED TIMES MINIMIZING DURATION OF INTERRUPTION TO
<br />EXISTING SERVICES. OBTAIN WRITTEN APPROVAL FOR TIME & DURATION OF A SCHEDULED SHUTDOWN FROM
<br />FACILITY ENGINEERING DEPARTMENT.
<br />7. COMPLY WITH FACILITY POLICIES AND PROTOCOLS FOR CONSTRUCTION AND INFECTIOUS CONTROL. COORDINATE
<br />WITH FACILITY.
<br />8. FACILITY SHALL SUBMIT COPIES OF THEIR CONSTRUCTION STANDARDS AND INFECTIOUS CONTROL RISK
<br />ASSESSMENT TO AHCA FOR REVIEW.
<br />9. FIRE ALARM AND SMOKE DETECTION SYSTEMS SHALL ALWAYS BE ACTIVE. HEADS MAY BE COVERED DURING HOURS
<br />OF CONSTRUCTION BUT THE COVERS SHALL BE REMOVED AT THE END DAY. IF THIS IS IMPOSSIBLE, THEN INSTALLA
<br />FIRE WATCH TILL THESE SYSTEMS ARE ACTIVE.
<br />10. IF THE FIRE ALARM OR SPRINKLER SYSTEMS IS OUT OF SERVICE FOR ANY EXTENDED PERIOD OF TIME (I.E. GREATER
<br />THAN FOUR HOURS) THEN A FIRE WATCH SHALL BE INSTALLED. SEE NFPA 101 ITEM 9.6.1.8 AND 9.7.6.
<br />11. DOCUMENT THE TYPE OF FIREPROOFING METHOD BEING UTILIZED ON THE STRUCTURAL FRAME FOR THESE AREAS
<br />UNDER RENOVATION, (I.E. SELF PROTECTING, SPRAY -ON FIRE PROOFING, OR MEMBRANE).
<br />A. SELECT THE FIRE RATING FOR THE SPRAY -ON FIREPROOFING FOR TYPICAL ULASSEMBLY (I.E. COLUMNS AND
<br />BEAMS) IN CASE PATCHING IS REQUIRED.
<br />B. IF A FIRE RATED MEMBRANE IS BEING EMPLOYED, DOCUMENT ITS UL LISTED ASSEMBLY.
<br />12, NO ITEMS OR MATERIALS SHALL BE STORED IN THE EXIT DISCHARGE OR PATH TO THE PUBLIC WAY.
<br />13. THE EXIT ACCESS CORRIDOR SHALL REMAIN OPEN AND ACCESSIBLE AT ALL TIMES.
<br />14. ANY DAMAGE FOUND TO EXISTING WALLS, SHALL BE REPAIRED TO THEIR ORIGINAL FIRE RESISTANT CONDITION.
<br />California I Florida I Nevada
<br />Peninsula Engineering, INC.
<br />MEP&FP
<br />PENINSULA
<br />ENGINEERING
<br />INC.
<br />2016 ALDEN ROAD
<br />ORLANDO, FL 32803
<br />CA 3089
<br />VOICE: (407) 246.1688
<br />FAX: (407) 246-1664
<br />http://Www.peifla.com
<br />Email to: pei0eifla.com
<br />JOB #: 15384
<br />Copyright - All ideas, designs,
<br />methods and plans indicated or
<br />represented by this drawing are
<br />owned by and the property of
<br />Peninsula Engineering, Inc. and
<br />were created, evolved and
<br />developed for use on and in
<br />connection with the specified
<br />project. None of the ideas,
<br />designs, arrangements, methods
<br />or plans shall be used by or
<br />disclosed to any person, firm or
<br />corporation for any purpose
<br />whatsoever without the written
<br />permission of Peninsula
<br />Engineering, Inc.
<br />©opyright
<br />2015
<br />ARCHISPEC, INC
<br />ARCHITECTURAL SPECIFICATIONS
<br />653 Mallory Hill Drive Lady Lake., FL 32162
<br />P: 352.430.0987
<br />REVISIONS:
<br />3 1 03/03/17 REVISION #2
<br />PROJECT TITLE:
<br />ZEPHYRHILLS HEALTH & REHAB
<br />CENTER
<br />SKILLED NURSING -10 BED
<br />CONVERSION
<br />PROJECT ADDRESS:
<br />7350 DAIRY RD. ZEPHYRHILLS, ;FL. 33540
<br />PROJECT NUMBER:
<br />FLTSP15008
<br />SHEET TITLE:
<br />SPECIFICATIONS AND LEGEND -
<br />ELECTRICAL
<br />C:\Users\kinae\Documents\15384 ZEPHYRHILLS HEALTH & REHAB CENTER kinaena neifla.com.rvt
<br />PROJECT NORTH TRUE NORTH
<br />rN
<br />E001
<br />© 2015 Studio+
<br />
|