a <br />ELECTRICAL SPECIFICATIONS: <br />GENERAL PROVISIONS <br />A. PROVIDE ALL LABOR, MATERIALS AND EQUIPMENT FOR A COMPLETE AND PROPERLY OPERATING <br />ELECTRICAL SYSTEM. INCLUDE NECESSARY FEES AND PERMITS WITHIN BASE BID. <br />B. CODES AND STANDARDS <br />1. ALL WORK SHALL BE PROVIDED IN ACCORDANCE WITH ALLGOVERNING AUTHORITIES LAWS, ORDINANCES, <br />CODES, RULES AND REGULATIONS WHICH GOVERN THE WORK. <br />2. THE APPLICABLE GOVERNING AUTHORITIES LAWS, ORDINANCES, CODES, RULES AND REGULATIONS SHALL <br />CONSIST BASICALLY OF, BUT NOT LIMITED TO, THE FOLLOWING (LATEST EDITIONS): <br />3. NFPA-1 UNIFORM FIRE CODE,2012 <br />4. CHAPTER 59A-3, 2010 FLORIDA ADMINISTRATIVE CODE <br />5. 69A-53, F.A.C., STATE FIRE PREVENTION CODE 5TH EDITION. <br />6. NFPA-70-201 1, NATIONAL ELECTRICAL CODE. <br />7. NFPA-72-2010, NATIONAL FIRE ALARM CODE. <br />8. NFPA-99-2012, STANDARD FOR HEALTH CARE FACILITIES <br />9. NFPA-101 (2012), LIFE SAFETY CODE W/FLORIDA AMENDMENTS. <br />10. NFPA-1 10 (2010), STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS. <br />11. NFPA 241 (2009), STANDARD FOR SAFEGUARDING BUILDING CONSTRUCTION AND DEMOLITION OPERATIONS. <br />12. CHAPTER 395, FLORIDA STATUTES <br />13. CHAPTER 780, LIGHTNING PROTECTION CODE (2011). <br />14. FLORIDA FIRE PREVENTION CODE 5TH EDITION AND THE CURRENT ADOPTED CODES AND STANDARDS BY THE <br />STATE OF FLORIDA. <br />15. 2010GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTHCARE FACILITIES. <br />16. FLORIDA BUILDING CODE 5TH EDITION (2014) CHAPTER 449. <br />17. FLORIDA AMERICANS WITH DISABILITIES, 2007AS DESCRIBED IN ACCESSIBILITY REQUIREMENTS MANUAL, <br />DEPARTMENT OF COMMUNITY AFFAIRS. <br />18. LATEST EDITION OF ALLOTHER NFPA ARTICLES NOT LISTED, AS ADOPTED BY THE STATE FIRE MARSHALL. <br />19. REQUIREMENTS OF THE FLORIDA BUILDING CODE 5TH EDITION (2014). <br />20. AMERICANS WITH DISABILITY ACT, JANUARY 26,1992. <br />21. ALL WORK SHALL BE PROVIDED IN ACCORDANCE WITH ALL ANSI STANDARDS ADOPTED BY THE GOVERNING <br />AUTHORITY. THIS INCLUDES BUT IS NOT LIMITED TO SPECIAL REQUIREMENTS FOR FIRE ALARM, ELEVATORS <br />AND HANDICAP PERSONS. <br />22. IT IS THE INTENT OF THE CONTRACT DOCUMENTS TO COMPLY WITH ALL APPLICABLE GOVERNING <br />AUTHORITIES, LAWS, ORDINANCES, CODES, RULES, REGULATIONS AND STANDARDS. WHERE DISCREPANCIES <br />OCCUR, NOTIFY THE ARCHITECT/ENGINEER, IN WRITING, AND ASK FOR INTERPRETATION A MINIMUMOF TEN <br />DAYS PRIOR TO THE BID OF THE CONTRACT DOCUMENTS. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED <br />AS EVIDENCE THAT THE CONTRACTOR SHALL MEET THIS INTENT. NO ADDITIONAL COMPENSATION SHALL BE <br />PROVIDED FOR WORK REQUIRED FROM INTERPRETATIONS OF DISCREPANCIES AFTER THE BID. <br />23. REQUIREMENT OF THE CITY OF ZEPHYRHILLS <br />C. PERMITS AND INSPECTIONS: OBTAIN AND MAKE ALL PAYMENTS FOR PERMITS AND INSPECTIONS <br />REQUIRED. AT THE COMPLETION OF THE PROJECT AND BEFORE FINAL ACCEPTANCE OF THE ELECTRICAL <br />WORK, PROVIDE EVIDENCE OF FINAL INSPECTION AND APPROVAL BY THE AUTHORITIES HAVING <br />JURISDICTION. <br />D. CONTRACTOR SHALLTHOROUGHLY INVESTIGATE SITE BEFORE BIDDING. NO CHANGES WILL BE ALLOWED <br />IN CONTRACT PRICE FOR WORK REQUIRED TO COMPLY WITH EXISTING CONDITIONS. <br />E. ALL ELECTRICAL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER. <br />F. PROVIDE PHENOLIC NAMEPLATES ON ALL PANELBOARDS, SWITCHBOARDS, DISCONNECTS, <br />TRANSFORMERS, ETC, INDICATING DESIGNATION, CIRCUIT NUMBER(S), VOLTAGE AND WHERE UNIT IS FED <br />FROM. SECURE NAMEPLATES WITH AT LEAST TWO SCREWS OR RIVETS. CEMENTING AND ADHESIVE <br />INSTALLATION IS NOT ACCEPTABLE. <br />G. ELECTRICAL CONTRACTOR SHALL EXAMINE ARCHITECTURAL, MECHANICAL, PLUMBING AND FIRE <br />PROTECTION DRAWINGS FOR ESTIMATING AND CONSTRUCTION OF THIS PROJECT. SUBMISSION OF A <br />PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER <br />CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED FOR CONNECTING AND ENERGIZING <br />EQUIPMENT SHOWN ON THOSE DRAWINGS WILL NOT BE RECOGNIZED. <br />ELECTRICAL CONTRACTOR SHALL COMMUNICATE DISCREPANCIES TO ENGINEER PRIOR TO SUBMITTING A <br />BID. <br />H. PROVIDE TEMPORARY POWER AND LIGHTING. INCLUDE PERMITS AND UTILITY COMPANY FEES FOR <br />TEMPORARY SERVICES WITHIN BASE BID. <br />I. CONTRACTOR SHALL SCHEDULE ALL DOWN -TIME WITH THE OWNER PRIOR TO BEGINNING THE WORK. <br />PREMILIWOVERTIME RATES MAYBE REQUIRED AND MUST BE INCLUDED IN BASE BID. <br />J. CONTRACTOR SHALLTHOROUGHLY REVIEW CONSTRUCTION DOCUMENTS. WHEN CONFLICTS ARISE WITHIN <br />CONSTRUCTION DOCUMENTS, CONTRACTOR SHALL NOTIFY ENGINEER PRIOR TO SUBMITTING A BID. <br />SUBMISSION OF A BID SHALL INDICATE THAT CONTRACTOR THOROUGHLY REVIEWED CONSTRUCTION <br />DOCUMENTS. <br />N AVAILABLE R TIME ES NOT PERMIT CONTRACTOR SHALL INCLUDE THE MOST <br />K. WHEN ENGINEER IS NOT ,0 0 , <br />STRINGENT (COSTLY) REQUIREMENTS WITHIN BASE BID. <br />L. CONTRACTOR S HALLCOORDINATE WITH UTILITY COMPANY AND TELECOMMUNICATION COMPANY FOR <br />LOCATIONS AND REQUIREMENTS PRIOR TO COMMENCEMENT OF WORK. <br />M. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING MANUFACTURERS, SUB <br />CONTRACTORS, VENDORS, AND SUPPLIERS, WITH A COPY OF THESE SPECIFICATIONS. <br />N. GUARANTEE ALL ELECTRICAL SYSTEM MATERIALS AND WORKMANSHIP TO BE FREE FROM DEFECTS FOR A <br />PERIOD OF ONE (1) YEAR FROM THE DATE OF FINALACCEPTANCE AND PROPERLY CORRECT LATENT <br />DEFECTS ARISING WITHIN THIS PERIOD UPON NOTIFICATION BY THE OWNER'S REPRESENTATIVE WITHOUT <br />ADDITIONAL COMPENSATION. <br />0. DAILY REMOVE REFUSE AND DEBRIS ACCUMULATING FROM ELECTRICAL CONSTRUCTION AND PRIOR TO <br />ACCEPTANCE OF THIS WORK, LEAVE THE PREMISES "BROOM CLEAN" INSOFAR AS AFFECTED BY <br />ELECTRICAL WORK. <br />P. EQUIPMENT AND DESIGN OF SYSTEMS INDICATED ON THE DESIGN DRAWINGS AND WITHIN THESE <br />SPECIFICATIONS SHALL BE CONSIDERED AS "SPECIFIED STANDARD" OF QUALITY. NO SUBSTITUTIONS <br />SHALL <br />BE MADE WITHOUT WRITTEN APPROVAL OF THE ENGINEER AT LEAST 10 DAYS PRIOR TO BID DATE. <br />Q. ALL EMERGENCY EGRESS LIGHTING SHALL BE HARDPIPED. NO EXCEPTIONS. NO FLEXIBLE CONDUIT OR <br />WHIPS IS ALLOWED. <br />ANY DEVIATION FROM SPECIFIED EQUIPMENT THAT AFFECT THE INSTALLATION, OPERATION, <br />PERFORMANCE, QUALITY OR LONGEVITY OF THE ELECTRICAL SYSTEMS AS DEFINED HEREIN, SHALL BE <br />REPLACED BY THE ELECTRICAL CONTRACTOR WITH NO ADDITIONALCOST TO THE CLIENT, IN ADDITION, <br />ELECTRICAL CONTRACTOR SHALL PROVIDE THE ENGINEERING WITH PHOTOMETRIC FLOOR PLANS FOR ANY <br />LIGHTING FIXTURES CHANGES FOR APPROVAL AT LEAST 10 DAYS PRIOR TO BID DATE. <br />BASIC MATERIALS AND METHODS <br />A. RACEWAYS AND FITTINGS: ALL RACEWAYS AND FITTINGS SHALL BE GALVANIZED RIGID STEEL OR <br />INTERMEDIATE METAL CONDUIT WITH LOCKNUTS AND BUSHINGS, WITH THE EXCEPTION THAT <br />WHERE SPECIFICALLY ALLOWED BY THE NATIONAL ELECTRICAL CODE AND APPLICABLE LOCAL CODES. <br />ELECTRICAL METALLIC TUBING (E.M.T) MAY BE USED FOR ALL INTERIOR EXPOSED AND CONCEALED WORK <br />WHERE IT IS NOT SUBJECT TO PHYSICAL DAMAGE OR CORROSION. FITTINGS SHALL BE STEEL SET SCREW <br />TYPE. NO PVC, BX OR MC CABLE ALLOWED. INSTALL EXPANSION FITTINGS IN RACEWAYS EVERY 200, LINEAR <br />RUN OR WHEREVER STRUCTURAL EXPANSION JOINTS ARE CROSSED. <br />Al. FOR MEDICAL, DENTAL AND SIMILAR OFFICES AS DEFINED NEC ARTICLE 517 NO NON-METALIC <br />RACEWAYS SHALL BE USED ANYWHERE AND ONLY MC CABLE LISTED FOR HEALTHCARE USE MAY BE <br />USED FOR NORMAL POWER RECEPTACLE CIRCUITS, FIXED EQUIPMENT CIRCUITS, SWITCH LEGS AND <br />LIGHT FIXTURE WHIPS. <br />B. CONDUCTORS: FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE (412 UNLESS OTHERWISE NOTED) <br />THWN COPPER. NO ALUMINUM SHALL BE PERMITTED UNLESS SPECIFICALLY" NOTED OTHERWISE, INSTALL ALL <br />WIRING IN CONDUIT OR APPROVED RACEWAYS UNLESS OTHERWISE INDICATED. PROVIDE 410AWG FOR <br />BRANCH CIRCUITS OVER 100 FEET IN LENGTH TO ACCOUNT FOR VOLTAGE DROP. PROVIDE #10 GROUND TO <br />CORRESPOND. ALL BRANCH CIRCUITS SHALL CARRY A GROUNDING EQUIPMENT CONDUCTOR, AND BE WIRED <br />WITH COLOR -CODED WIRE WITH THE SAME COLOR USED FOR A PHASE THROUGHOUT. COLOR -CODE SHALL <br />BE AS FOLLOWS: <br />120/240 VOLT 10: PHASE A - BLACK: PHASE B - RED; <br />NEUTRAL - WHITE; GROUND -GREEN. <br />120/208 VOLT 30: PHASE A - BLACK: PHASE B - RED; PHASE C - BLUE; <br />NEUTRAL - WHITE; GROUND - GREEN. <br />277/480 VOLT 30: PHASE A - BROWN; PHASE B - ORANGE; PHASE C - YELLOW; <br />NEUTRAL - LIGHT GREY; GROUND - GREEN. <br />A DEDICATED NEUTRAL CONDUCTOR SHALL BE INSTALLED FOR ALL CIRCUITS DEDICATED OR NOT. NO <br />SHARING OF THE NEUTRAL SHALL BE PERMITTED. <br />C. FINAL CONNECTIONS TO MOTORS OR EQUIPMENT SUBJECT TO VIBRATION SHALL BE MADE UP WITH <br />GREENFIELD IN DRY LOCATIONS AND WITH JACKETED, LIQUID -TIGHT, FLEXIBLE, GALVANIZED STEEL <br />CONDUIT IN WET OR DAMP LOCATIONS. LOCATE ALL DEVICES AND EQUIPMENT WHERE SHOWN ON <br />DRAWINGS. ALL DIMENSIONS SHOWN ON THE DRAWINGS ARE FROM FINISHED FLOOR TO THE CENTER OF <br />THE DEVICE UNLESS OTHERWISE INDICATED. STANDARD MOUNTING HEIGHTS ARE AS FOLLOWS: <br />DEVICES HEIGHT AFF AT DEVICE CENTER (NOTE 1) <br />1. ELECTRICAL OUTLETS 18" <br />2. ELECTRICAL OUTLETS ABOVE COUNTER 42" <br />3. TELEPHONE 18" <br />4. WALLTELEPHONE 54" <br />5. LIGHT SWITCHES 46" <br />6. THERMOSTATS SEE MECH SPECS <br />7. FIRE ALARM DEVICES 80" TO BOTTOM OF GLASS/& PER LATEST ADA REGULATIONS <br />8. DISCONNECT SWITCHES 60" TO TOP <br />9. PANELBOARDS 72" TO TOP <br />10. EXITSIGNS AS NECESSARY <br />11. SPECIAL DEVICES AS NECESSARY <br />NOTE 1: IN SPACES SUCH AS, BUT NOT LIMITED TO DENTAL LABS, MEDICAL LABS, SCHOOL LABS, CHIP <br />PLANTS, ETC. WHERE VENDORS ARE SUPPLYING MILLWORK THE ABOVE REFERENCED HEIGHTS <br />ARE NOT APPLICABLE. REFER TO THE MILLWORK ELEVATION PLANS TO DETERMINE AN <br />APPROPRIATE MOUNTING HEIGHT. <br />D. DISCONNECT SWITCHES: HEAVY DUTY, FUSED OR NON -FUSED AS CALLED FOR ON PLAN DRAWINGS. PROVIDE <br />SOLID NEUTRAL CONNECTION WHERE REQUIRED. USE.NEMA-1 INDOORS AND NE MA-3R OUTDOORS. ALL <br />DISCONNECT SWITCHES SHALL BE PROVIDED WITH GROUND KIT. <br />E. PROVIDE PANELBOARDS OF THE DEAD FRONT TYPE, NO LESS THAN 20 INCHES WIDE AND 5 3/4 INCHES DEEP <br />WITH QUANTITY OF BRANCH CIRCUITS/CIRCUIT BREAKERS AS INDICATED ON THE PANELBOARD SCHEDULE <br />WITH THE VOLTAGE. PHASE AND AMPERE RATING AS REQUIRED. ALL PANELBOARDS SHALL HAVE PHASE <br />SEQUENCE CIRCUITS AND BOLT -ON CIRCUIT BREAKERS. MAIN BREAKERS SHALL BE MOLDED CASE, CIRCUIT <br />BREAKERS FEEDING HVAC LOADS SHALL BE HACK TYPE. TYPEWRITTEN PANEL DIRECTORIES SHALL BE <br />PROVIDED AT COMPLETION OF THE PROJECT. <br />F. ELECTRICAL CONTRACTOR SHALL REVIEW ONE LINE POWER RISER DIAGRAM IN CONJUNCTION WITH <br />SWITCHGEAR MANUFACTURER REPRESENTATIVE TO CROSS REFERENCE POWER RISER WITH PANEL <br />SCHEDULES AND VERIFY VOLTAGES, AMPS, LUGS SIZES/ NUMBER AND CABINETS DIMENSIONS PRIOR TO <br />SUBMITTING A BID. <br />G. EXERCISE CARE IN CONNECTING THE VARIOUS ELECTRICAL LOADS TO THE PANELS IN ORDER TO ARRIVE AT A <br />REASONABLE BALANCE BETWEEN LOADS IN EACH PHASE AT EACH PANEL. MAKE TESTS AND ADJUST LOADS <br />AT EACH PANEL TO RESULT IN REASONABLY BALANCED LOAD CONDITION. SATISFACTORY TO THE UTILITY <br />COMPANY. ENGINEER, OWNER AND INSPECTION AGENCIES DOCUMENT ALL SAID LOAD ADJUSTMENTS. <br />H. MANUFACTURERS:BASE OF DESIGN IS SQUARE D. <br />I. MATERIALS SHALL BE NEW AND UNUSED AND THE CATALOGUED PRODUCTS OF MANUFACTURERS <br />REGULARLY ENGAGED IN THE PRODUCTION OF SUCH MATERIALS. THE MATERIALS SHALL BE OF THE <br />MANUFACTURER'S LATEST STANDARD DESIGN THAT COMPLIES WITH THE SPECIFICATION REQUIREMENTS. <br />J. LIGHTING FIXTURES SHALL BE AS SHOWN ON THE DRAWING AND SHALL BE FURNISHED WITH LAMPS <br />INSTALLED. CLEAN, RELAMP AND REFURBISH AS REQUIRED FOR LIGHT FIXTURES THAT ARE ETR OR NL. <br />K. ALL GROUNDING SHALL CONFORM TO ARTICLE 250OF THE NEC REQUIREMENTS. IN ADDITION THERETO AS <br />IMPOSED BY THE DRAWINGS AND THE LOCAL CODE ENFORCEMENT AUTHORITIES HAVING JURISDICTION. <br />WHEN THE WATER MAIN METAL PIPE IS USED AS A SUPPLEMENTAL ELECTRODE, CONNECTION SHALL BE MADE <br />WITHIN 5 FT. OF POINT OF ENTRANCE OF PIPE INTO THE BUILDING. CONNECTIONS OF CONDUCTORS TO <br />GROUND RODS SHALL BE MADE BY MEANS OF EXOTHERMIC WELD. <br />L. FIREPROOF ALLOPENINGS ON FIRE RATED WALLS BY AN UL APPROVED SYSTEM. <br />M. PROVIDE 4" SQUARE BOX AND 3/4" CONDUIT STUB -UP TO ACCESSIBLE CEILING FOR TELEPHONE, TV AND DATA <br />OU <br />TLETS, PROVIDE INSULATING BUSHINGS AT BOTH ENDS AND PULL STRING. <br />N. SUBMITTALS: SUBMIT ELECTRONIC SUBMITTALS VIA E-MAIL FORMATTED AS PDF FILE, <br />LL BE SEALED USING AN UL APPROVED <br />0, CONDUIT PENETRATIONS RATIONS THROUGH FIRE RATED PARTITIONS SHALL <br />SYSTEM. REFER TO ARCHITECTURAL FLOOR PLAN FOR LOCATION OF FIRE RATED PARTITIONS. PROVIDE <br />ACOUSTICAL FOAM SEALANT AT ALL DEVICES ON DEMISING PARTITIONS. IF PARTITION IS FIRE RATED, <br />PROVIDE FIREPROOF COMPOUND ON BACK AND SIDES OF THE BOX. WHERE TELEPHONE AND ELECTRICAL <br />OUTLETS APPEAR ON PLANS AS BACK TO BACK, OUTLETS SHALL BE STAGGERED TO REDUCE NOISE <br />TRANSMISSION. WHERE WALLS AND PARTITIONS ARE REQUIRED TO HAVE A MINIMUM OF 1-HOUR <br />FIRE -RESISTANCE RATING, BOXES SHALL BE SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES <br />OR PROTECTED WITH UL LISTED PUTTY PADS. <br />P. CABLES NOT ENCLOSED IN CONDUITS WITHIN CEILING SPACES SHALL BE AIR PLENUM RETURN FIRE RATED <br />AND MEET THE REQUIREMENTS OF SECTION 602OF F.M.C. <br />Q. PROVIDE DISK FILE ON CAD 2013 RELEASE WITH "AS BUILT" ELECTRICAL DRAWINGS AT THE COMPLETION OF <br />THE PROJECT. <br />R. CONTRACTOR REPRESENTS THAT HIS BID IS BASED UPON THE MANUFACTURER'S MATERIALS AND <br />EQUIPMENT DESCRIBED IN THE CONTRACT DOCUMENTS. <br />S. ELECTRICAL CONTRACTOR SHALL REVIEW THE ARCHITECTURAL DRAWINGS FOR DEVICES EXACT LOCATIONS, <br />MOUNTING HEIGHTS AND QUANTITIES PRIOR TO BID AND PRIOR TO ROUGH -IN. NOTIFY THE ENGINEER <br />IMMEDIATELY IF ANY DISCREPANCIES ARE FOUND. <br />T. FINAL QUANTITY OF EXIT AND EMERGENCY LIGHTS TO BE DETERMINED BY FIRE MARSHALL. INCLUDE <br />CONTINGENCY FOR 2 ADDITIONAL EXIT LIGHTS AND 2 ADDITIONAL EMERGENCY, <br />U. PROVIDE SWITCHBOARDS WITH THE VOLTAGE AND AMPERE RATINGS FOR THE MAIN BREAKER, THE MAIN BUS <br />AND THE FEEDER BREAKERS AS INDICATED ON THE ONE -LINE POWER RISER DIAGRAM. <br />1. BUS BARS OF SILVER-PLATED COPPER OR TIN-PLATED ALUMINUM. <br />2. MOLDED CASE BREAKERS FOR THE MAIN AND FEEDERS, <br />3. BUS BARS OF SILVER-PLATED COPPER OR TIN-PLATED ALUMINUM. <br />4. PROVISIONS FOR PADLOCKING THE CIRCUIT BREAKER HANDLES ON THE "ON" AND "OFF" <br />POSITION. <br />5, PROVIDE RUBBER INSULATION FLOOR MAT IN FRONT OF SWITCHBOARD FOR ENTIRE LENGTH OF <br />CENTER AND 4 FEET WIDE. <br />V. SWITCHBOARDS, MOTOR CONTROLCENTERS AND TRANSFORMERS SHALL BE MOUNTED ON 4" THICK <br />CONCRETE HOUSEKEEPING PADS. HOUSEKEEPING PADS SHALL EXTEND AT LEAST 2" BEYOND ALL SIDES, <br />FRONT AND BACK OF THE EQUIPMENT EXCEPT WHERE EQUIP. EXTENDS TO WALLS. EXTENSIONS BEYOND <br />SIDES OF THE EQUIPMENT SHALL BE BEVELED. <br />W. ELECTRICAL CONTRACTOR MAY COMBINE CIRCUITS IN A COMMON RACEWAY AS LONG AS CONDUCTORS ARE <br />DEBATED AS PER NEC. SHARED NEUTRAL SHALL NOT BE ALLOWED UNLESS OTHERWISE INDICATED. <br />X. ELECTRICAL CONTRACTOR SHALL INCLUDE TRENCHING AND BACKFILLING, CORE DRILLING, CUTTING AND <br />PATCHING FOR THE INSTALLATION OF HIS/HER WORK WITHIN BASE BID. <br />Y. CLEAN ALL LIGHT FIXTURES, LAMPS AND LENSES AND PANELBOARD INTERIORS PRIOR TO FINAL <br />ACCEPTANCE. <br />Z. SERVICE LATERALS THAT ARE NOT ENCASED IN CONCRETE AND THAT ARE BURIED 18 IN. (457 MM) OR MORE <br />BELOW GRADE SHALL HAVE THEIR LOCATION IDENTIFIED BY A WARNING RIBBON THAT IS PLACED IN THE <br />TRENCH AT LEAST 12 IN. (305 MM) ABOVE THE UNDERGROUND INSTALLATION. <br />AA. REVIEW AND COORDINATE WITH MECHANICAL DRAWINGS FOR EQUIPMENT, CONDUIT, DEVICES, ETC., <br />REQUIRED FOR A COMPLETE AND OPERATING HVAC SYSTEM. <br />BB. PROVIDE BACK BOXES AND RACEWAY FOR DOOR ACCESS CARD READERS AND ELECTRIC STRIKES AS PER <br />SECURITY CONTRACTOR DIRECTIONS. PROVIDE 120VAC TO EACH ELECTRIC STRIKE DOOR LOCATION AND TO <br />ACCESS CONTROL SYSTEM PANEL. ACCESS CONTROL SYSTEM MUST DEACTIVATE OR OPEN ANY DOOR <br />LOCKING MECHANISM AND REMAIN IN FAIL SAFE POSITION WHENEVER FIRE ALARM SYSTEM IS ACTIVATED OR <br />BUILDING POWER FAILS. PROVIDE "PUSH -TO -EXIT' PUSHBUTTON AND MOTION DETECTOR AT EACH ACCESS <br />DOOR LOCATION. INTERLOCK WITH FIRE ALARM SYSTEM. <br />CC. CONTRACTOR REPRESENTS THAT HIS BID IS BASED UPON THE MANUFACTURER'S MATERIALS AND <br />EQUIPMENT DESCRIBED IN THE CONTRACT DOCUMENTS. <br />DD. E LECTRICAL CONTRACTOR SHALLFILL UTILITY SERVICE INFORMATION FORMS AND BUILDING DEPARTMENT <br />ELECTRICAL PERMIT FORMS. <br />EE. PROVIDE AND INSTALL PHASE LOSS PROTECTORS WITH AUTO RESET FOR ALL 10 AND 30 EQUIPMENT SHOWN <br />ON MECHANICAL PLANS THAT HAVE AT LEAST 2 HOT CONDUCTORS. SEE DIAGRAMS, THIS SHEET. <br />FF. ALL UNDERGROUND CONDUITS SHALL BE PROVIDED WITH PULL STRING AND BOTH ENDS SHALL BE <br />PROPERLY IDENTIFIED AND MARKED. PROVIDE CAPS TO AVOID MATERIAL INTRUSION. <br />WHERE AN UNDERGROUND RACEWAY ENTERS A BUILDING OR STRUCTURE, IT SHALL BE SEALED AS PER <br />NEC ARTICLES 230.8 AND 300.5(G). <br />CONDUITS STUB -UPS WITHIN BUILDING SHALL BE MADE WITH GALVANIZED RIGID CONDUIT. NO <br />NON-METALLIC RACEWAY ALLOWED WITHIN BUILDING (ASSEMBLY OCCUPANCY, NEC ARTICLE 518). <br />GG. THE CEILING SPACE OF THIS PROJECT IS A RETURN AIR PLENUM. ALL MATERIALS IN THIS AREA MUST BE <br />PLENUM RATED AND MEET THE REQUIREMENTS OF SECTION 602 OF THE F.M.C. <br />HH. COORDINATE WITH MECHANICAL CONTRACTOR FOR INSTALLATION OF MOTOR STARTERS AND VFD'S <br />FURNISHED BY MECHANICAL. <br />II. PRIOR TO TRENCHING IN ANY AREA, THE CONTRACTOR SHALLCONTACT ELECTRICAL. COMMUNICATION/DATA, <br />CABLE TV, GAS, STORM, CHILL WATER, SANITARY AND WATER UTILITY PROVIDERS. HAVE ALL THE UTILITIES IN <br />THE AREA IDENTIFIED. IN ADDITION, THE CONTRACTOR SHALL OBTAIN THE SERVICES OF A SUBCONTRACTOR <br />SPECIALIZING IN THE LOCATION OF UNDERGROUND STRUCTURES, MEMBRANES, ETC. TO IDENTIFIED ANY <br />OBSTACLES IN THE PATH OF TRENCHING PRIOR TO COMMENCING WORK. DAMAGE TO ANY UNDERGROUND <br />STRUCTURES SHALL BE REPAIRED BY THE CONTRACTOR AT NO ADDITIONALCOST TO THE PROJECT. <br />JJ. ELECTRICALCONTRACTOR SHALL INSTRUCT OWNER REPRESENTATIVE REGARDING EQUIPMENT OPERATION <br />AND MAINTENANCE AT COMPLETION OF WORK. PROVIDE OWNER WITH ALL MANUALS PERTAINING TO THE <br />PROJECT. <br />KK, LOW VOLTAGE CABLES FOR SECURITY SYSTEM, AV SYSTEM, TELEPHONE SYSTEM AND DATA SYSTEM ARE <br />NOT PART OF THIS ENGINEER'S SCOPE OF WORK. <br />ILL. MINIMUM EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A PERIOD OF 1 1/2 HOURS IN THE EVENT OF <br />FAILURE OR NORMAL LIGHTING, WITHIN THE WORK AREAS. EMERGENCY LIGHTING FACILITIES SHALL BE <br />ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS AT LEAST AN AVERAGE OF 1 FOOTCANDLE (10 LUX) AND <br />A MINIMUM AT ANY POINT OF 0.1 FOOTCANDLE (1 LUX) MEASURED ALONG THE PATH OF EGRESS AT FLOOR <br />LEVEL. <br />MM. REVIEW AND COORDINATE WITH MECHANICAL DRAWINGS FOR EQUIPMENT, CONDUIT, DEVICES, ETC. <br />REQUIRED FOR ACOMPLETE AND OPERATING HVAC SYSTEM. LOW VOLTAGE CONTROL WIRING FURNISHED <br />AND INSTALLED BY MECHANICAL. CHECK ALL MOTORS AND ROTATING EQUIPMENT FOR PROPER ROTATION, <br />NN. PROVIDE LIGHTNING PROTECTION TO ALL ROOF MOUNTED EQUIPMENT PROVIDED WITHIN THIS SCOPE OF <br />WORK. INTERCONNECT TO EXISTING LIGHTNING PROTECTION SYSTEM. <br />NURSE CALL <br />F_---- <br />- <br />SYMBOL <br />i <br />DESCRIPTION <br />(NBMS <br />NURSE CALL MASTER STATION <br />NCTC <br />NURSE CALL TERMINATION CABINET <br />CB <br />CODE BLUE STATION <br />i B <br />SHOWER STATION <br />FB <br />DUTY STATION <br />{S) <br />I- - <br />STAFF STATION <br />D D <br />CORRIDOR DOME LIGHT <br />t-- <br />II _ B <br />CORRIDOR ZONE LIGHT CEILINGAVALL <br />j F ] - <br />SINGLE PATIENTSTATION(W/2-WAY AUDIO) <br />I [I- <br />TOILET PULLCORD STATION <br />B�-- <br />BATH PULL CORD STATION <br />DP� <br />DUAL PATIENT STATION (W/2-WAY AUDIO) <br />BB <br />f <br />STAFF EMERGENCY AUDIBLENISUAL INDICATING APPLIANCE <br />37) <br />L_ <br />37 PIN BED CONNECTOR <br />PER AHCA REGULATIONS/MANUFACTURERS SPECIFICATIONS PULL CORD STATION IN SHOWER <br />MUST BE MOUNTED ABOVE THE SHOWER HEAD AND ON THE SAME WALLAS THE SHOWER HEAD. <br />1. PROVIDE A WATER RESISTANT GASKET KIT. INSTALLON SHOWER WALL WITH SHOWER HEAD. <br />2. STATIONS SHALL BE LOCATED WITHIN 12" OF THE FRONT OF THE TOILET BOWL AND T TO 4' <br />ABOVE THE FLOOR PER FGI GUIDELINES 2.1-8.3.7.3(3), <br />3. STATIONS IN SHOWER AND TUBS SHALL BE LOCATED 570 6' ABOVE THE FLOOR, WITHIN <br />NORMAL VIEW OF THE USER AND WITHIN REACH OF THE STAFF WITHOUT THE NEED TO STEP INTO <br />THE STALL OR TUB PER FGI GUIDELINES. FIELD VERIFY EXACT LOCATIONS. ALL ROOMS SHALL <br />HAVE CONSISTENT LOCATIONS. <br />EQUIPMENT LISTING NOTES: <br />ALL EQUIPMENT IN THIS PROJECT SHALL BE UL LISTED (OR US EQUIVALENT) <br />PER THE F.B.C. IF ANY EQUIPMENT IS NOT LISTED A FIELD LISTING BY AN OSHA <br />APPROVED THIRD PARTY WILL BE REQUIRED AS FOLLOWS: <br />1. EQUIPMENT SUPPLIERNENDOR SHALL SUPPLY DOCUMENTATION, OSHA <br />APPROVED THIRD PARTY LISTINGS, AND E-FILES FOR ALL EQUIPMENT, WIRING, <br />TRANSFORMERS, LIGHTS, ETC. IN THIS PROJECT TO AN ENGINEER WITH <br />PENINSULA ENGINEERING SEVEN (7) WORKING DAYS PRIOR TO INSPECTION <br />FOR REVIEW AND APPROVAL <br />2. DEVICES THAT DO NOT MEET OSHA APPROVED THIRD PARTY LISTINGS OR <br />ARE NOT LISTED SHALL BE FIELD LISTED BY A QUALIFIED AGENCY PRIOR TO <br />INSPECTION AND DOCUMENTATION SHALL BE PROVIDED. THIS SHALL BE THE <br />RESPONSIBILITY OF THE EQUIPMENT MANUFACTURER. <br />3. ALL EQUIPMENT SHALL BE UL 60601 COMPLIANT. <br />ELECTRICAL SYMBOL LEGEND: <br />NOTE: NOT ALL SYMBOLS USED IN THIS PROJECT <br />2x4 AND 2x2 RECESSED FLUORESCENT LIGHT FIXTURE TO NORMALCIRCUIT <br />FLUORESCENT FIXTURE CONNECTED TO CRITICAL CIRCUIT <br />FLUORESCENT FIXTURE CONNECTED TO EMERGENCY CIRCUIT <br />-. <br />FLUORESCENT FIXTURE CONNECTEDTO LIFE SAFETYCIRCUIT <br />N - L t N ' <br />FLUORESCENT FIXTURE CONNECTED TO UNSWITCHED CIRCUIT <br />I-4--� <br />STRIP FLUORESCENT LIGHT FIXTURE -CEILING, WALL MOUNTED <br />O (2 INCANDESCENT, HID OR COMPACT FLUORESCENT FIXTURE - CEILING MOUNTED, WALL MOUNTED <br />SITE LIGHTING FIXTURE <br />® T EXIT SIGN FIXTURE, SHADED QUADRANT INDICATES FACE, WITH ARROWS AS SHOWN ON PLAN - CEILING <br />MOUNTED, WALL MOUNTED <br />B EMERGENCY LIGHTING FIXTURE <br />S S 2$ 3$ 4 1-POLE, 2-POLE, 3-WAY, 4-WAY SWITCH <br />MS MOTION SENSOR LIGHT SWITCH <br />Mi FM 2OCCUPANCY SENSORS. REFER TO LIGHTING PLAN <br />PP POWER PACK. REFER TO LIGHTING PLAN <br />$ K KEYSWITCH <br />D INCANDESCENT DIMMER SWITCH, 1-POLE, 3-WAY, 4-WAY SWITCH <br />M MP MANUAL MOTOR STARTER TOGGLE SWITCH AS NOTED; "P" INDICATES PILOT LIGHT; "WP" INDICATES <br />wP <br />WEATHERPROOF <br />0 W o (o DUPLEX RECEPTACLE AT 18"!AS NOTED, ABOVE COUNTER AT <br />C G 42"/AS NOTED, CEILING MOUNTED, GROUND FAULT TYPE, ISOLATED GROUND <br />B TYPE, WEATHERPROOF TYPE,(REFER TO NOTE 10 BELOW) SIMPLEX (AS NOTED) <br />IG WP <br />(2) DUPLEX RECEPTACLES IN SINGLE OUTLET BOX WITH <br />B_ SINGLE COVER PLATE AT 18"/AS NOTED, ABOVE COUNTER AT 42"/AS NOTED 1 <br />$C or 1-POLE SWITCH CONNECTED TO CRITICAL CIRCUIT (RED DEVICE) -QUIET TYPE <br />DUPLEX RECEPTACLE (RED DEVICE) AT 18"/AS NOTED, ABOVE COUNTER AT 42"/AS NOTED CONNECTED TO <br />CRITICALCIRCUIT <br />(2) DUPLEX RECEPTACLE (RED DEVICES) IN SINGLE OUTLET BOX WITH <br />SINGLE COVER PLATE AT 167AS NOTED, ABOVE COUNTER AT 42VAS NOTED CONNECTED TO CRITICAL <br />CIRCUIT <br />0 0 ❑ SPECIAL MOUNTED RECEPTACLE AS NOTED, PUSHBUTTON AS NOTED, TELE-POWER POLE <br />\ [(] FINALCONNECTION TO EQUIPMENT <br />B B�FT] JUNCTION BOXES, MOTOR, TRANSFORMER <br />E::]= FUSED DISCONNECT SWITCH, NON FUSED DISCONNECT, MOTOR STARTER OR CONTACTOR, COMBINATION <br />®lSTARTER/DISCONNECT, ENCLOSED CIRCUIT BREAKER <br />llllllll� 120/208OR 120/240V PANELBOARD <br />277/480V PANELBOARD <br />lira_] SYSTEMS CABINET -FLUSH MOUNTED, SURFACE MOUNTED (AS NOTED) <br />TELEPHONE TERMINALS TELEPHONE SYSTEM RACEWAY <br />BOARD, <br />CONNECTION TO GROUND <br />W P TELEPHONE OUTLET AT 18", WALL TELEPHONE OUTLET AT 54%ABOVE COUNTER, PAY TELEPHONE OUTLET. <br />V V V V PROVIDE 4'SO. MASONRY (DEEP) BOX AND 1" CONDUIT (WITH INSULATING BUSHING) TO ACCESSIBLE CEILING <br />COMPUTER OUTLET, COMPUTER OUTLET 48 , PHONE/DATA PROVIDE 4" SQUARE MASONRY BOX AND r CONDUIT <br />17 17 v (WITH INSULATING BUSHING) TO ACCESSIBLE CEILING <br />TV OUTLET, PROVIDE 4" SQUARE BOX AND 3/4" CONDUIT TO ACCESSIBLE CEILING. MOUNT @ IT TO THE <br />TV CENTER UNLESS OTHERWISE NOTED. <br />SMOKE DETECTOR, SMOKE DUCT DETECTOR <br />WAP WIRELESS ACCESS POINT <br />O VOLUME CONTROL <br />SO SPEAKER <br />B HEAT DETECTOR <br />B DUCT/SMOKE DETECTOR REMOTE INDICATOR LIGHT W/KEYED TEST SWITCH <br />SHUTDOWN RELAY, 24V DC <br />B LOCK BOX <br />MANUAL PULL STATION, FLUSH <br />HORN AND STROBE LIGHT, FLUSH MOUNTED <br />C <br />Bi WALIJCEILING MOUNT STROBE <br />VE VOICE EVAC SPEAKER <br />VE VOICE EVAC SPEAKER AND STROBE LIGHT, FLUSH MOUNTED <br />H+ DOOR HOLDER <br />TC TIMECLOCK <br />ITS] TAMPER SWITCH <br />FS FLOWSWITCH <br />CM FIRE ALARM CONTROL MODULE "C" INDICATES CEILING MOUNTED <br />BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR IN WALL, SLASH MARKS INDICATE NUMBER OF <br />CONDUCTORS, LONGER SLASH IS NEUTRAL, (GROUND WIRE NOT SHOWN). 2 #12,1 #12 GROUND IN A 3/4" <br />CONDUIT MINIMUM (UNLESS OTHERWISE NOTED OR MARKED). QUANTITY OF ARROWS INDICATE QUANTITY <br />OF HOMERUNS TO PANELBOARD. PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN ALL BRANCH CIRCUITS. <br />BRANCH CIRCUIT CONDUIT CONCEALED BELOW SLAB OR UNDERGROUND. <br />ELECTRICAL SYMBOL LEGEND NOTES: <br />1. AN OUTLET BOX OF THE APPROPRIATE SIZE AND TYPE SHALL BE PROVIDED FOR ALL DEVICES, LIGHTING <br />FIXTURES, SWITCHES, RECEPTACLES, ETC. <br />2. A DEDICATED NEUTRAL CONDUCTOR SHALL BE INSTALLED FOR ALLCIRCUITS DEDICATED OR NOT. NO <br />SHARING OF THE NEUTRAL SHALL BE PERMITTED. <br />3. SWITCHES AND RECEPTACLES SHALL BE SPECIFICATION GRADE 20A MINIMUM. ALL RECEPTACLES IN <br />PATIENT CARE AREAS SHALL BE HOSPITAL GRADE 20A MINIMUM UNLESS OTHERWISE NOTED. ALL NORMAL <br />DEVICES TO BE IVORY (COORDINATE COLOR WITH ARCHITECT PRIOR TO ORDER) AND ALL CRITICAL <br />DEVICES TO BE RED. <br />4. ELECTRICAL CONTRACTOR MAY COMBINE SAME CIRCUIT TYPES IN A COMMON RACEWAY AS LONG AS <br />CONDUCTORS ARE DEBATED AS PER NEC. SHARED NEUTRALS SHALL NOT BE ALLOWED. A DEDICATED <br />NEUTRAL SHALL BE PROVIDED FOR EACH CIRCUIT PER 2008 NEC. <br />5. COORDINATE ALL LOCATIONS, HEIGHTS AND COLORS WITH ARCHITECTURAL DRAWINGS/DIAGRAMS PRIOR <br />TO ROUGH IN. <br />6. ALL NEW AND EXISTING COVER PLATES IN THE PROJECT AREA SHALL BE ENGRAVED WITH PANEL AND <br />CIRCUIT INFORMATION. METAL PLATES SHALL BE RED LETERING FOR CRITICAL CIRCUITS AND <br />BLACK LETTERING FOR NORMALCIRCUITS. PHENOLIC PLATES SHALLBE A RED PLATE WITH WHITE <br />LETTERING FOR CRITICAL CIRCUITS AND IVORY/WHITE/MATCH EXISTING PLATES WITH BLACK LETTERING <br />FOR NORMAL CIRCUITS. <br />7. PROVIDE A PULL STRING IN ALL EMPTY CONDUITS. <br />8. ALLJUNCTION BOX COVERS SHALL BE MARKED WITH PANEL, CIRCUIT NUMBER AND VOLTAGE WITH <br />PERMANENT BLACK MARKER. <br />9. JUNCTION BOXES SHALL NOT BE MOUNTED TO THE PARTITION TOP PLATE. <br />10. SECTION 406.8 OF THE 2008 NEC CODE MANDATES ALL NON -LOCKING 15A AND 20A RECEPTACLES IN DAMP <br />OR WET LOCATIONS SHOULD BE LISTED WEATHER RESISTANT. <br />11. PROVIDE ACOUSTICAL FOAM AND SEALANT AT ALL DEVICES ON DEMISING PARTITIONS. IF PARTITION IS <br />FIRE <br />RATED, PROVIDE FIREPROOF COMPOUND ON BACK AND SIDES OF THE BOX OR 5 SIDED WITH APPROVED <br />MATERIALAS REQUIRED. <br />12. WHERE TELEPHONE AND El ECTRICALOUTLETS APPEAR ON PLANS AS BACK TO BACK, OUTLETS SHALL BE <br />STAGGERED TO REDUCE NOISE TRANSMISSION. WHERE WALLS AND PARTITIONS ARE REQUIRED TO HAVE <br />A <br />MINIMUM OF 1-HOUR FIRE -RESISTANCE RATING, BOXES SHALL BE SEPARATED BY A MINIMUM HORIZONTAL <br />DISTANCE OF 24" INCHES OR PROTECTED WITH UL LISTED PUTTY PADS. <br />13. THE ELECTRICAL CONTRACTOR SHALL COORDINATE EXACT MOUNTING AND INSTALLATION REQUIREMENTS <br />FOR PAY TELEPHONE OUTLET. <br />14. THE ELECTRICAL CONTRACTOR SHALLCOORDINATE EXACT MOUNTING OF RECEPTACLES SERVING <br />ELECTRIC WATER COOLERS TO ENSURE THAT THE POWER CORD IS FULLY CONCEALED. <br />15. PROVIDE LABELS ON POWER POLES INDICATING PANELAND CIRCUIT NUMBER. <br />16, WHEN PRICING FLOOR BOXES OF POKE-THRU DEVICES, ELECTRICAL CONTRACTOR SHALL INCLUDE X-RAY <br />OF SLAB, CORE DRILLING, FIREPROOFING, AND PROTECTION OF FLOOR BELOW. <br />IT PROVIDE 4" SQUARE BOX AND 1" CONDUIT STUB -UP TO ACCESSIBLE CEILING FOR TELEPHONE AND DATA <br />OUTLETS. TERMINATE CONDUITS T ABOVE CEILING IN ACCESSIBLE SPACE WITH 90' BEND INSULATED <br />BUSHINGS AND PULL STRING. COORDINATE WITH TENANTS DATA(TELEPHONE CONTRACTOR FOR FUR <br />FURTHER ELECTRICAL AND RACEWAYS REQUIREMENTS. CABLING BY OTHERS. <br />18. GROUNDING OF RECEPTACLES AND FIXED EQUIPMENT IN PATIENT CARE AREAS SHALL COMPLY WITH NEC <br />ARTICLE 517,13 (A) AND (B). <br />19. RECEPTACLES LOCATED WITHIN THE EXAM ROOMS, BATHROOMS, PLAYROOMS, WAITING, ACTIVITY ROOMS <br />AND PATIENT CARE AREAS OF PEDIATRIC WARDS AND CHILD CARE FACILITIES SHALL BE LISTED TAMPER <br />RESISTANT. <br />HOSPITAL SPECIAL REQUIREMENTS: <br />1. NOTIFY PROJECT COORDINATOR WHEN PROJECT IS TO COMMENCE & PROVIDE PROPOSED PROJECT <br />SCHEDULE. <br />2. MEET WITH AND REVIEW PROGRESS OF CONSTRUCTION & AS -BUILT RECORD DRAWINGS WITH (&AT A FREQUENCY <br />SET BY) PROJECT COORDINATOR. <br />3. PROVIDE WRITTEN NOTIFICATION TO PROJECT COORDINATOR OF TIMES & DATES FOR BUILDING <br />INSPECTIONS OR REVIEW OF CONSTRUCTION BY AUTHORITIES HAVING JURISDICTION. <br />4. PROVIDE COMPLETED FACILITY ENGINEERING DEPARTMENT EQUIPMENT REGISTRATION FORMS FOR ADDITION, <br />DELETION, RELOCATION OR PROVISION OF NEW ELECTRIC CIRCUITS, ELECTRICAL PANELS, VALVES OR OTHER <br />EQUIPMENT. BLANK FORMS ARE AVAILABLE FROM HOSPITAL ENGINEERING DEPARTMENT. <br />5. COMPLY WITH FACILITY ENGINEERING DEPARTMENT STANDARDS FOR EQUIPMENT / POWER PANEL/SYSTEM PANEL/ <br />DISCONNECT NAMEPLATING, PIPE LABELING, &VALVE TAGGING. <br />6. MAKE CONNECTIONS TO EXISTING SYSTEMS AT APPROVED TIMES MINIMIZING DURATION OF INTERRUPTION TO <br />EXISTING SERVICES. OBTAIN WRITTEN APPROVAL FOR TIME & DURATION OF A SCHEDULED SHUTDOWN FROM <br />FACILITY ENGINEERING DEPARTMENT. <br />7. COMPLY WITH FACILITY POLICIES AND PROTOCOLS FOR CONSTRUCTION AND INFECTIOUS CONTROL. COORDINATE <br />WITH FACILITY. <br />8. FACILITY SHALL SUBMIT COPIES OF THEIR CONSTRUCTION STANDARDS AND INFECTIOUS CONTROL RISK <br />ASSESSMENT TO AHCA FOR REVIEW. <br />9. FIRE ALARM AND SMOKE DETECTION SYSTEMS SHALL ALWAYS BE ACTIVE. HEADS MAY BE COVERED DURING HOURS <br />OF CONSTRUCTION BUT THE COVERS SHALL BE REMOVED AT THE END DAY. IF THIS IS IMPOSSIBLE, THEN INSTALLA <br />FIRE WATCH TILL THESE SYSTEMS ARE ACTIVE. <br />10. IF THE FIRE ALARM OR SPRINKLER SYSTEMS IS OUT OF SERVICE FOR ANY EXTENDED PERIOD OF TIME (I.E. GREATER <br />THAN FOUR HOURS) THEN A FIRE WATCH SHALL BE INSTALLED. SEE NFPA 101 ITEM 9.6.1.8 AND 9.7.6. <br />11. DOCUMENT THE TYPE OF FIREPROOFING METHOD BEING UTILIZED ON THE STRUCTURAL FRAME FOR THESE AREAS <br />UNDER RENOVATION, (I.E. SELF PROTECTING, SPRAY -ON FIRE PROOFING, OR MEMBRANE). <br />A. SELECT THE FIRE RATING FOR THE SPRAY -ON FIREPROOFING FOR TYPICAL ULASSEMBLY (I.E. COLUMNS AND <br />BEAMS) IN CASE PATCHING IS REQUIRED. <br />B. IF A FIRE RATED MEMBRANE IS BEING EMPLOYED, DOCUMENT ITS UL LISTED ASSEMBLY. <br />12, NO ITEMS OR MATERIALS SHALL BE STORED IN THE EXIT DISCHARGE OR PATH TO THE PUBLIC WAY. <br />13. THE EXIT ACCESS CORRIDOR SHALL REMAIN OPEN AND ACCESSIBLE AT ALL TIMES. <br />14. ANY DAMAGE FOUND TO EXISTING WALLS, SHALL BE REPAIRED TO THEIR ORIGINAL FIRE RESISTANT CONDITION. <br />California I Florida I Nevada <br />Peninsula Engineering, INC. <br />MEP&FP <br />PENINSULA <br />ENGINEERING <br />INC. <br />2016 ALDEN ROAD <br />ORLANDO, FL 32803 <br />CA 3089 <br />VOICE: (407) 246.1688 <br />FAX: (407) 246-1664 <br />http://Www.peifla.com <br />Email to: pei0eifla.com <br />JOB #: 15384 <br />Copyright - All ideas, designs, <br />methods and plans indicated or <br />represented by this drawing are <br />owned by and the property of <br />Peninsula Engineering, Inc. and <br />were created, evolved and <br />developed for use on and in <br />connection with the specified <br />project. None of the ideas, <br />designs, arrangements, methods <br />or plans shall be used by or <br />disclosed to any person, firm or <br />corporation for any purpose <br />whatsoever without the written <br />permission of Peninsula <br />Engineering, Inc. <br />©opyright <br />2015 <br />ARCHISPEC, INC <br />ARCHITECTURAL SPECIFICATIONS <br />653 Mallory Hill Drive Lady Lake., FL 32162 <br />P: 352.430.0987 <br />REVISIONS: <br />3 1 03/03/17 REVISION #2 <br />PROJECT TITLE: <br />ZEPHYRHILLS HEALTH & REHAB <br />CENTER <br />SKILLED NURSING -10 BED <br />CONVERSION <br />PROJECT ADDRESS: <br />7350 DAIRY RD. ZEPHYRHILLS, ;FL. 33540 <br />PROJECT NUMBER: <br />FLTSP15008 <br />SHEET TITLE: <br />SPECIFICATIONS AND LEGEND - <br />ELECTRICAL <br />C:\Users\kinae\Documents\15384 ZEPHYRHILLS HEALTH & REHAB CENTER kinaena neifla.com.rvt <br />PROJECT NORTH TRUE NORTH <br />rN <br />E001 <br />© 2015 Studio+ <br />