'q <br />d 01o+ <br />GENERAL NURSE CALL NOTES: <br />1. NEW NURSECALL SYSTEM IS RAULAND-BORG RESPONDER 5. <br />2. ELECTRICAL CONTRACTOR SHALL PROVIDE AND COORDINATE CONDUIT <br />ROUTING AND J-BOX LOCATIONS WITH NURSE CALL CONTRACTOR. <br />SUPPORT PER NEC. REFER TO VENDOR DRAWINGS FOR MORE INFO. <br />3. ALL CABLING TO BE FIELD TERMINATED BY INSTALLING CONTRACTOR. <br />4. DEVICE LOCATIONS ARE FOR ILLUSTRATION ONLY. FIELD DETERMINE <br />ACTUAL PLACEMENT. <br />5. PROVIDE INSULATING GROMMETS WITH STRAIN RELIEF AT ALL REQUIRED <br />LOCATIONS. <br />6. FOR CIRCUITING/WIRING COORDINATE WITH NURSE CALL CONTRACTOR <br />DRAWINGS AND DIAGRAMS. CABLING IS ANTICIPATED TO BE FREE WIRED <br />& SUPPORTED WITH J-HOOKS PER THE NEC. <br />7. ONCE NURSE CALL IS INSTALLED, STAFF IN EACH DEPT. SHALL BE <br />TRAINED/INFORMED OF CALLS & PROCEDURES. HOSPITAL NEEDS TO <br />PROVIDE A WRITTEN PROCEDURE FOR THE STAFF & HOW THEY SHOULD <br />RESPOND FOR AHCA & PRESENT AT THE AHCA INSPECTION. <br />8. ALL NEW NURSE CALL EQUIPMENT SHALL BE CONNECTED TO THE NEW <br />RAULAND-BORG NURSE CALL SYSTEM. <br />9. PROVIDE PROGRAMMING OF ALL NECESSARY EQUIPMENT FOR PROPER <br />OPERATION. <br />10. ALL PRODUCTS SHALL BE U.L. LISTED. <br />11. LOCA11ON OF ROUGH -IN FOR ALL BED INTERFACE UNITS MUST AVOID <br />INTERFERENCE OR DAMAGE FROM PATIENT BED. <br />12. NEW CODE BLUE DEVICES SHALL BE CONNECTED TO THE NURSE CALL <br />SYSTEM. CODE BLUE TO REPORT TO PBX & NURSE STATION. PROVIDE <br />TYPED UPDATED DIRECTORIES. <br />13. STAFF ASSIST SHALL BE INSTALLED & FUNCTION PER THE 2010 EDITION <br />OF THE FGI GUIDELINES IN AREAS INDICATED. <br />14. EXISTING TV'S MUST BE LISTED FOR USE IN HEALTHCARE FACILITIES PER <br />THE LISTING REQUIREMENTS OF THE NURSE CALL SYSTEM. PROVIDE <br />DOCUMENTATION ON UL LISTING. INSTALLING CONTRACTOR TO PULL <br />TV/LIGHTING/ ENTERTAINMENT CABLE TO BED INTERFACE. <br />15. WALL MOUNTED OVER -BED LIGHT WILL BE CONTROLLED VIA THE PILLW <br />SPEAKER. RAULAND-BORG SHALL PROVIDE A CURBELL RELAY FOR <br />CONTROL. REFER TO DETAIL. <br />KEYED NOTES: <br />O1 TV CONTROL CABLE FROM THE NURSE —CALL PATIENT STATION TO <br />THE TV OUTLET AND TV PATCH CABLES FROM THE TELEVISION TO <br />THE TV PLATE — ONE (1) COAX AND ONE (1) 1/4" TO 1/4" DATA <br />CABLE. (TYPICAL) <br />KEY PLAN (N.T.S.): <br />THIS DRAWING ADDED IN ITS ENTIRETY <br />California I Florida <br />2211 E. 7TH Ave, Suite A, Tampa, Florida 33605 <br />P:239.357.4983 AA26002372 <br />Peninsula Engineering, INC. <br />MEP&FP <br />2016 Alden Road <br />Orlando, FL 32803 <br />P: 407.246.1688 <br />F: 407.246.1664 <br />LBA Interiors <br />INTERIOR DESIGNER <br />5650 DTC Parkway, Suite 100 <br />Englewood, CO 80111 <br />P:303.773.0436 <br />F:303.773.0053 <br />2018 ALDEN ROAD <br />ORLANDID-W 32803 <br />YIW W28W FAX W P LIM <br />E—Ma1 to pe�Nfla.com <br />JOB # 16318 <br />Copyright — All Ideas, designs, methods and <br />plane Indicated or represented by this drawing <br />ore owned by and the property of Peninsula <br />Engineering, Inc. and were created, evolved <br />and developed for use on and in connection <br />with`the apedNed project None of the Ideas, <br />designs, arrangements, methods or plans shdl <br />be used by or disclosed to my person, fIrm <br />or corporation for my wpm whatsoever <br />without the written permission of Peninsula <br />UgIne" , Ina. <br />REVISIONS: <br />1 07/29/ 16 AHCA COMMENTS' <br />2 11/23116 REVISION #1 <br />3 03/10/17 REVISION #2 <br />7 <br />a <br />PROJECT TITLE: <br />ZEPHYRHILLS HEALTH & <br />REHAB CENTER <br />FINISH UPGRADE - SKILLED <br />NURSING FACILITY <br />PROJECT ADDRESS: <br />7350 DAIRY RD. ZEPHYRHILLS, FL 33540 <br />PROJECT NUMBER: <br />FLTSP16000 <br />ISSUED DATE: <br />12/16/2016 <br />FIRST FLOOR RENOVATION PLAN <br />PHASE 2 - NURSECALL <br />PROJECT NORTH TRUE NORTH <br />FIRST FLOOR RENOVATION PLAN - PHASE 2 - NURSECALL 1 1 <br />1 /8" = 1'-Orr <br />----------F— ,!I;Tr I: 1" I I leT,, i.. F--7 is I , —T-- 1� <br />E305 <br />© 2016 Studio+l <br />