DRAWING NOTES HANGER NOTES • No • • m ~ • off " m <br />2. SPRINKLERS SHALLIBE(SPACED PER THEIR LISTING. 2. MAXIGN MUMESPACNG FOR2STEEL PIPE IS AS FOLLOWS SCALE. g"=1'-011 <br />3. SPRINKLERS ARE NOT REQUIRED IN THE NON 1" AND 1i" - 12'-0" <br />COMBUSTIBLE ATTIC PER 9.2.1. 1 j" AND ABOVE - 15'-0". <br />4. ALL PIPING TO BE INSTALLED WITHIN THE HEATED 3. A HANGER IS REQUIRED WITHIN 3'-0" OF THE END <br />ENVELOP AND PROTECTED FROM FREEZING BY OF A BRANCH LINE. SCALE: 1 /8"=1'-O" <br />OTHERS. <br />5. SYSTEM DESIGN PER THE DENSITY/AREA METHOD 4. ARMOVERS GREATER THAN 2'-0" REQUIRES A 8' O' 4' 8' 16' <br />PER 19.3.3.2. AREA REDUCTION WAS NOT USED. HANGER. <br />6. QUICK RESPONSE SPRINKLERS ARE TO BE USED 5. PIPES GREATER THAN 6 -0 IN LENGTH REQUIRES <br />THROUGHOUT THE BUILDING ADDITION. A HANGER. <br />7. PIPING TO BE BLACK STEEL SCHEDULE 40 PIPE <br />8. DIMENSIONS ON PIPE INDICATE CUT LENGTHS <br />SYM <br />CNT <br />POSITION <br />FINISH <br />TEMP <br />K <br />NPT <br />SIN <br />MFG <br />ESCUTCHEON <br />0 <br />63 <br />PEND <br />WHITE <br />155 <br />5.60 <br />15,60 <br />1 1/2" <br />V3802 <br />VICTAULIC <br />CONCEALED <br />QO <br />4 <br />UPR <br />BRASS <br />155 <br />1/2" <br />V2804 <br />VICTAULIC <br />EXPOSED <br />FITTINGS, WELDS AND/OR END OF PIPE. <br />67 TOTAL SPRINKLERS9. HILLER SYSTEMS TO BEGIN AT POINT AS INDICATED <br />ON DRAWING. D 66073 10-FP-JD20,35 <br />