<br />08-8100 GLAZING
<br />1. Each piece of glass shall bare manufacturer's label showing strength, grade thickness, type and quality.
<br />2. Safety Glazing Standard: Comply with ANSI Z97.1 and testing requirements of 16 CFR Part 1201 for category II materials including
<br />temper glass, tempered safety glass, laminated safety glass, etc.
<br />3. Insulating Glass Certification Program: Provide certification label of Insulating Glass Certification Council (IGCC).
<br />4. Comply with applicable seismic and wind load requirements for impact resistance as noted in the drawings.
<br />5. Manufacturers: AFG Industries, Inc. Guardian Industries Corporation, Oldcastle Glass, Inc. Vlracon, Inc.
<br />A. Glass Type A: Vision Glass:
<br />1" Insulating Glass for Aluminum Storefront and Doors: Hermetically sealed unites made of two glass sheets
<br />separated with air space, manufactured to meet or exceed the quality standards established by SIGMA, IGCC,
<br />ASTM C1048, CPSC 16, and ANSI Z97.1.
<br />A. Inside Glass: %" clear float glass.
<br />B. Outside Glass Coating: Solar Control Low-E (Sputtered), Solarban90 by PPG coated on second surface.
<br />C. Outside Glass: %" heat treated, clear.
<br />D. Overall Summer U-Value: 0.29 or lower.
<br />E. Overall Shading Co -Efficient: 0.29 or lower.
<br />B. Glass Type B: Fritted Glass
<br />1" Insulating Tempered Glass for Aluminum Storefront and Doors: Hermetically sealed units made of two fully
<br />tempered (FT) glass sheets separated with air space, manufactured to meet or exceed the quality standards
<br />established by SIGMA, IGCC, ASTM C1036, ASTM E773, ASTM E774, and ANSI Z97.1.
<br />A. Inside Glass: %" clear tempered glass, 100% etch frit on #3 Suface.
<br />B. Outside Glass Coating: Solar Control Low-E (Sputtered), Solarban90 by PPG coated on second surface.
<br />C. Outside Glass: W clear tempered.
<br />D. Overall Summer U-Value: 0.29 or lower.
<br />E. Overall Shading Co -Efficient: 0.29 or lower.
<br />C. Glass Type C: Interior Glazing
<br />A. 1/4" clear tempered
<br />D. Glass Type D: Impact Glass
<br />9/16" Laminated Glass for Exterior Sliding entry door.
<br />A. Inside Glass: 1/4" clear HS
<br />B. Interlayer:.090 Sentryglas Plus
<br />C. Outside Glass Coating: Solarban90 #2 Surface
<br />D. Outside Glass: 1/4" clear HS
<br />7. Glazing work shall be in accordance with procedures in FGJA "Glazing Manual". Glaze in temperature above 40 degrees. Sash
<br />shall be clean and dry. Setting blocks shall be at one fourth points.
<br />8. Provide insulating glas manufacturer's 10 year written warranty which guarantees the sealed glass units from seal failure, interpane
<br />dusting or misting, internal condensation at temperatures of -20F and other evidence of hermetic seal failure. Written warranty shall
<br />also guarantee the quality of sealed glass units meets or exceeds SIGMA "Specification for Sealed Insulating Glass Units."
<br />DIVISION 9 - FINISHES
<br />09-2116 GYPSUM BOARD ASSEMBLIES
<br />1. Gypsum board: Type X, 5/8" with tapered edges. Board in wet areas (around toilet and sinks) to also be water-resistant.
<br />Manufacturers: US Gypsum, Certainteed, National Gypsum.
<br />2. Mold Resistant gypsum board: USG Sheetrock brand Type "X" Mold Tough, 5/8" thick. Use on interior of exterior walls.
<br />3. Provide all accessories required to complete in accordance with Contract Documents and UL assemblies.
<br />4. Attach all gypsum board with screw 3/8" to'/" from edges and space at no more than 8" o.c. at edges and 12" o.c. in the field. Drive
<br />screws so head rests in slight dimple without cutting face paper or fracturing core.
<br />5. At Floor Slab: Leave %" space between floor slab and bottom edge of gypsum board. Set gypsum board in continuous bed of
<br />acoustical sealant, at floor and vertical intersection of sound walls.
<br />6. At deck: Leave %" space between deck and top edge of gypsum board. Caulk top of gypsum board with continuous bead of
<br />acoustical sealant.
<br />7. Finish joints and fasteners heads and accessories following "Recommended Levels of Gypsum Board Finish (GA-214-96)"
<br />published by The Gypsum Association for the following conditions: Level 4 in areas below ceiling and on ceilings, Level 1 above
<br />ceiling and Level 5 at epoxy paint locations.
<br />8. Provide metal taping beads at all jambs, corners of openings, and other locations where gypsum board joins other materials.
<br />09-2216 NON-STRUCTURAL METAL FRAMING
<br />1. Protective Coating: Galvanize steel studs, runners (track), rigid (hat Section), furring channels, and resilient furring channels, ASTM
<br />A123, G-60 minimum.
<br />2. Interior Studs. 3 5/8" 20 gauge, 0.0329 wall thickness, Moment of inertia about major axis .414, Section Modulus .213. Cee-shaped,
<br />punched web steel studs, hot -dipped galvanized finish (ASTM A525) complying with ASTM C645.
<br />3. Slip -Type Head Joints: ASTM C 645 top runner with 2 inch deep flanges in thickness not less than indicated for studs. Installed with
<br />studs friction fit into top runner and with continuous bridging located within 12 inches of the top of studs to provide lateral bracing.
<br />4. Metal Furring Channels for Gypsum Board on Ceiling Walls: Hat -shaped, roll -formed galvanized steel, DWC-25 for screw
<br />attachment of gypsum panels, DWC-20 for longer spans and load carrying for ceiling applications.
<br />5. Manufacturers: Clark Steel Framing Industries, Dale/Incor, Dietrich Industries.
<br />6. Provide framing systems and members, lateral support bracing, hanging devices and anchors throughout the facility as required for
<br />safe support of materials, fixtures and items as indicated on drawings.
<br />7. Fasteners for Attachment to Metal or Wood: Pan -head screws as recommended by fasteners manufacturer, self -drilling, self -
<br />tapping.
<br />8. Tie Wire and Hanger Wire: Galvanized Soft Annealed Wire, ASTM A641, Class I coating, diameter as specified in ASTM C754 or
<br />ASTM C841.
<br />9. Install 2 beads of sealant equivalent to Pecora Acoustical Latex All-919 under all tracks.
<br />10. At Wall -Hung Cabinets and/or Casework: Install 20 gauge double studs at 16" o.c. for full width of cabinet work plus 12 inches on
<br />each side of cabinet work. Install wall -hung cabinets with 3//8" carriage bolts.
<br />09-2226 SUSPENSION SYSTEMS
<br />1. Pre-engineered flat drywall ceiling system equivalent to USG Flat Drywall Ceiling System manufactured from commercial quality,
<br />hot dipped galvanized, cold rolled steel.
<br />2. Install per manufacturer's recommendations
<br />3. BLOX uber modules will have equipment supports furnished. For field construction, secure hangers or rods to structural support
<br />elements only; do not attach metal deck. Loop wire -tie directly or provide inserts, clips or other anchorage devices or fasteners as
<br />required.
<br />4. Space main runner, hangers and furring according to requirements of ASTM C754, except as otherwise indicated.
<br />5. Where spacing of structural members, or width of ducts or other equipment, prevents regular spacing of hangers. Provide
<br />supplemental hangers and suspensions to members and reinforce nearest affected hangers to span extra distance.
<br />6. Extend runners to within 6 inches of walls.
<br />7. Provide 1 inch clearance between furring or runners and abutting walls and partitions. Final ceiling framing installation shall be level
<br />and flat with required openings framed and reinforced; ready to receive gypsum board ceilings.
<br />09-5133 ACOUSTICAL TILE CEILINGS
<br />1. Provide ceiling tile systems as indicated on finish drawing.
<br />2. Provide manufacturers standard panels of configuration as indicated that comply with ASTM E-84 with flame spread index <25 and
<br />smoke development <50, Class A, Class I FM Approved, ASTM-E 1264 Classifications as designated by type, pattern, acoustical
<br />rating and light reflectance, unless otherwise indicated.
<br />3. Provide manufacturers standard direct -hung metal suspension systems as indicated that comply with ASTM-C635 and ASTM
<br />C636. Tees shall be double web steel (ASTM A366) as designated by type, structural specifications and finishes, unless otherwise
<br />indicated.
<br />4. Manufacturers; Armstrong, USG, Chicago Metallic.
<br />5. Install to meet seismic criteria as required by applicable codes and noted on the Index Sheet.
<br />6. Hang grid system independent of walls, columns, ducts, pipes and conduit. Where carrying members are spliced, avoid visible
<br />displacement of face plane of adjacent members.
<br />7. Provide 5% stock of each material stock.
<br />09-6100 FLOORING
<br />1. See finish sheets for floor covering, base and transition material locations and types.
<br />2. Furnish and Install homogeneous vinyl composition tile following manufacturer's recommendations.
<br />3. Furnish and install homogeneous sheet vinyl and coved base with heat -welded seams following manufacturer's recommendation.
<br />4. Furnish miscellaneous material and accessories for proper floor covering attachment. At Structo Crete floor panels, place slip sheet
<br />underlayment as required and compatible with floor finish.
<br />5. Fill holes, cracks, low spots, and rough areas with sub -floor filler. Finish smooth.
<br />6. Before installation of flooring material, provide written documentation that floor moisture levels are acceptable to flooring
<br />manufacturers.
<br />7. Provide 5% stock of each material stock.
<br />8. Provide manufacturer's standard warranties for products.
<br />09-8100 ACOUSTICAL INSULATION
<br />1. Non -rated walls: 3 %" batt insulation, unfaced, complying with property requirements of ASTM C518; ASTM E84, NPA 220,
<br />equivalent to Owens -Coming's "Sound Attenuation" Batt Insulation.
<br />2. Rated walls: 3" batt insulation, unfaced, complying with property requirements of ASTM C665/Type I and SATM E84 with
<br />flamespread of 15 and smoke development of 0, equivalent to Thermafiber Sound Attenuation Fire Blankets.
<br />3. Do not install sound -attenuation blankets before mechanical and electrical work is complete.
<br />4. "Friction -fit" blankets between studs until wall cavities are completely filled, and without gaps and voids.
<br />09-9100 PAINTING
<br />1. Clean and prepare wall surfaces following paint manufacturer's recommendations for specific substrates condition and as specified.
<br />2. Apply paint with applicator and techniques best suited for substrates following manufacturer's recommendations.
<br />3. Do not apply paint in thinner coast than manufacturer's recommended spreading rate. Provide a total dry film thickness over the
<br />entire system as recommended.
<br />4. Stencil all firewalls above ceilings at a minimum of 10' o.c. with labels. Coordinate locations needed with Drawings.
<br />5. Paint Systems to include 1 primer and 2 finish coats and be recommended by manufacturer for substrate type
<br />DIVISION 10 - SPECIALTIES Specs for: Bumper guards, wall rails, corner guards, medical dispensers/collectors, interior/exterior
<br />signage
<br />10-2123.16 CUBICLE TRACK AND HARDWARE
<br />1. Surface -mounted tracks of heavy extruded aluminum alloy 3036-T4, 1-3/8" x W', slotted to receive roller carriers, complete with
<br />accessories and components required for complete and secure installations including splicers, end stops, and corner bends,
<br />equivalent to Imperial Fasteners' Model IFC-69.
<br />a. Carrier: Virgin nylon axle with nylon wheels, complete with nickel -plated brass bead -chain and hook assembly.
<br />2. Attach track to ceiling suspension system and NOT to ceiling panels. Space screws at spacing recommended by cubicle track
<br />manufacturer. Track systems shall be capable of supporting 200 pound dead load.
<br />10-2623.13 IMPACT RESISTANT WALL PROTECTION
<br />1. See Wall Protection Legend on drawings for Bed Bumpers, Corner Guards and Sheet Wall Protection. See drawings for locations.
<br />2. Each type of wall assembly shall be UL Classified and have been tested in accordance with UL-723 (ASTM E84) to meet a flame
<br />spread of 25 or less, and smoke developed rating of 450 or less, to meet a Class 1 rating.
<br />3. Each type of wall protector shall be complete with all accessories and attachments required to complete the assemblies.
<br />4. Install in accordance with applicable accessibility requirements.
<br />10-2813 TOILET ACCESSORIES
<br />1. Included as part of BLOX pre -manufactured toilet room modules.
<br />10-4413 FIRE PROTECTION SPECIALTIES
<br />1. Fully, recessed, fire extinguisher cabinet, white baked enamel steel box with full acrylic panel door for 10 pound extinguisher and
<br />red decal lettering, equivalent to Potter -Roemer, Inc. 7020.
<br />2. Fire extinguishers to be provided by Owner.
<br />10-5113 - METAL LOCKERS
<br />1. Standard high painted steel lockers with 24 gauge bodies, 16 gag doors, all edges shall have smooth finish, locking handle for
<br />padlock by Owner, 24 gauge sloped tops, 16 gauge zee base.
<br />a. Manufacturers: Republic Storage Systems LLC, Lyonworkspace Products, Penco Products Incorporated.
<br />b. Purse, 12" wide, 15" deep, as shown in Staff Lounge on drawings.
<br />c. Color to be selected by Architect.
<br />2. Install lockers secure, plumb, square in accordance with approved shop drawings.
<br />3. The completed locker installation shall be complete with specified accessories. Install metal end panels and filler panels to
<br />completely close off openings.
<br />10-8500 - BOLLARD SLEEVES
<br />1. Bumper post shield, 1/4" thick high -density polyethylene sleeve, 7" ID by full height of bollard.
<br />a. Manufacturers: Grainger item #GRE6.
<br />b. Installed with included foam strips.
<br />c. Color: yellow with red reflective strips.
<br />2. Molded work shall have sharply -defined profile and shall be clean and straight. Plain work shall be leveled, straight, and surfaces
<br />true and smooth. Edges, angles, and corners shall be square, clean, and sharp unless otherwise detailed.
<br />DIVISION 11 - EQUIPMENT -Not Used
<br />DIVISION 12 - FURNISHINGS -Not Used
<br />DIVISION 13 - SPECIAL CONSTRUCTION
<br />13-4900 - RADIATION PROTECTION
<br />1. Lead -Lined Gypsum Board: 5/8" thick x 4' 0" wide x height indicated, laminated with a single sheet of pure virgin lead of thickness
<br />indicated. Gypsum board shall be Fire code C (Type X) only.
<br />2. Sheet Lead: Unpierced, pure virgin lead, varying not more than 3% over entire surface complying with FS QQL-201 F, Grade #33, #
<br />35.
<br />a. Lead Discs: 1/16" thick x 1" diameter, to cover screw heads.
<br />b. Lead Strips: 2" wide x height and thickness indicated for lead lined gypsum board.
<br />c. Shields: 1/16" thick x dimensions required for shielding electrical outlets, switch boxes, utility recesses, and other
<br />penetrations of lead -lined walls.
<br />d. Hardware Shields: 1/16" thick x dimensions required to shield door hardware.
<br />e. Leaded glass, approximately %" thick; install multiple panes to provide shielding equal to lead of surrounding wall lead.
<br />3. Manufacturers: TBD
<br />4. Install viewing window glass strictly in accordance with manufacturer's printed instructions.
<br />5. Install sheet lead shield to cover wall penetrations and extend out at least 2" in all directions. Attach lead securely to retain it in
<br />place but do not penetrate lead with fasteners.
<br />6. After X-ray equipment has been installed and placed in operation, have radiation shielding tested by a health physicist who is
<br />certified by a nationally recognized agency. Owner will pay for testing. Decision of acceptability of shielding by the health physicist
<br />shall be binding.
<br />a. Method of Testing: In accordance with requirements of National Bureau of Standards Handbook H-76 "Medical X-Ray
<br />Protection up to Three Million Volts".
<br />b. Repair or replace defective work including other affected work. Do any additional testing required for the health physicist's
<br />satisfaction. Repair, replacement and retesting shall be at contractor's expense.
<br />DIVISION 31 - EARTHWORK
<br />31-3116 - TERMITE CONTROL
<br />1. Treated -zone, non -repellent soil treatment for termite control equivalent to Premise manufactured by Bayer Environmental applied
<br />by Cooks, Orkin, Terminix or other who is licensed according to regulations of authorities having jurisdiction to apply termite control
<br />treatment in jurisdiction where project is located.
<br />2. Mix soil treatment termiticide solution to a uniform consistency. Provide quantity required for application at the label volume and rate
<br />the maximum specified concentration of termiticide. According to manufacturer's EPA -Registered Label, to following so that a
<br />continuous horizontal and vertical termiticide barrier or treated zone is established around and under building construction. Distribute
<br />the treatment evenly.
<br />a. Slabs -on -Grade Slabs: Underground -supported slab construction, including footings, building slabs, and attached slabs as
<br />an overall treatment. Treat soil material before concrete footings and slabs are placed.
<br />b. Foundations: Adjacent soil including soil along entire inside perimeter of foundation walls, along both sides of interior
<br />partition walls, around plumbing pipes and electric conduit penetrating slab, and around interior column footers, piers; and
<br />along entire outside perimeter, from grade to bottom of footing. Avoid soil washout around footings.
<br />c. Penetrations: At expansion joints, control joints, and areas where slabs will be penetrated.
<br />3. Avoid disturbance of treated soil after application. Keep off treated areas until completely dry.
<br />4. After application of termiticide is complete, submit report for Owner's record information, including the following as applicable: Date
<br />and time of application, moisture content of soil before application, brand name and manufacturer of termiticide, quantity of undiluted
<br />termiticide used, dilution, methods, columns and rates of application used, areas of application, water source for application.
<br />5. Written warranty certifying that applied soil poisoning treatment will prevent infestation of subterranean termites for period of five
<br />years and, that if subterranean termite activity is discovered during warranty period. Contractor will re -treat soil and repair or replace
<br />damage caused by termite infestation.
<br />DIVISION 32 - EXTERIOR IMPROVEMENTS
<br />32-3913 MANUFACTURED METAL BOLLARDS
<br />1. Fixed steel cylindrical with round finial and rounded top, ASTM A36 with polyester powder coat over epoxy primer, 34" high and
<br />5-3/4" diameter equivalent to model R-7576 as manufactured by Reliance Foundry. Color to be selected by Architect.
<br />2. Install per manufacturer's Instructions.
<br />See Civil, Structural, Mechanical, Plumbing and Electrical drawings for additional specifications.
<br />RETAIL CLINIC
<br />ADDITION TO
<br />ZEPHYRHILLS
<br />WALMART 706
<br />GA PROJECT No: 20CE14
<br />GIATTINA AYCOCK
<br />ARCHITECTURE STUDIO INC.
<br />2625 5th Avenue North, Building C
<br />• Bessemer, AL 35020
<br />P.- 205.933.9060
<br />GASTUDIO.COM
<br />STAMP:
<br />A, OF F4o•Q
<br />co I
<br />ISSUE SCHEDULE:
<br />REVISION SCHEDULE:
<br />NUM. DESCRIPTION
<br />NOTES & LEGEND
<br />CURRENT DRAWING SET:
<br />PERMIT SET
<br />ISSUE DATE: 11/25/2020
<br />DRAWN BY: CHB
<br />SHEET:
<br />ARCHITECTURAL
<br />SPECIFICATIONS