Laserfiche WebLink
.P <br />POWER PLAN <br />U�J SCALE: 1/8"=1'-0" <br />G_ i <br />JHVAC EQUIPMENT SCHEDULE <br />UNIT <br />DESIGNATION <br />WIRE AND CONDUIT <br />DISCONNECTING <br />MEANS <br />FEEDER <br />' BRANCH <br />RTU-1 <br />11-1/4-C WITH 3 #1, 1 /8 EG, <br />11-1/4% WITH 3 #3, 1 /8 EG.I <br />100/3/NP/NEMA 3R <br />RTU-2 <br />�1-1/4"C WITH 3 #1, 1 18 EG, <br />I <br />I1-1/4"C WITH 3 #3, 1 #8 EG.� <br />100/3/NP/NEMA 3R <br />GENERAL NOTES: <br />(1) EC IS ADVISED THAT FUSE REDUCER MAY BE REQUIRED. <br />NOTES O <br />1. JUNCTION BOX MOUNTED BEHIND FASCIA IN SOFFIT AREA FOR FUTURE TENANT <br />SIGN (VERIFY EXACT LOCATION WITH GENERAL CONTRACTOR). ROUTE HOMERUN <br />THRU TENANT TIME CLOCK. <br />2. REFER TO "HVAC EQUIPMENT SCHEDULE" ON THIS SHEET, <br />3. DUPLEX RECEPTACLE FOR SHOW WINDOW LIGHTING MOUNTED FLUSH IN CEILING, <br />4. 3/4"X3'X3' PLYWOOD, FIRE -RETARDANT PAINTED, FOR TELECOMMUNICATIONS, <br />5. EXTEND (2) 2-1/2" CONDUITS TO BENEATH DISCONNECT AS SHOWN ON POWER <br />RISER DIAGRAM. REFER TO CORRESPONDING DIAMOND NOTE FOR STUB -UP <br />LOCATION. EXTEND 1" EMPTY CONDUIT WITH PULLSTRING TO TELEPHONE <br />TERMINAL CABINET, STUB -UP AND CAP AT BOTH ENDS. <br />6. EXTEND (1) 2" EMPTY CONDUIT WITH PULLSTRING TO MAIN TELEPHONE CABINET <br />FOR TELEPHONE CONDUCTORS, <br />7. PROVIDE CONNECTION TO EWH. 30AMP 2-POLE TOGGLE SWITCH. EXTEND <br />1/2"C WITH 2 #10, 1 #10 EG TO PANEL SHOWN. <br />8. EXHAUST FAN IS TO BE CONTROLLED WITH LIGHTING THIS ROOM. <br />9. 1" EMPTY CONDUIT WITH PULLSTRING EXTENDED FROM UNDER SALES DESK TO <br />BELOW TELEPHONE BOARD FOR FUTURE TELEPHONE CONDUCTORS, STUB -UP <br />AT BOTH ENDS. <br />10, EC SHALL COORDINATE STUB -UP LOCATIONS FOR POWER AND DATA WITH <br />TENANT ARCHITECT AND OWNER PRIOR TO ROUGH -IN. EC TO COORDINATE <br />OUTLETS SHOWN IN MILLWORK WITH TENANT ARCHITECT AND OWNER PRIOR TO <br />ROUGH -IN, <br />11, JUNCTION BOX MOUNTED BEHIND FASCIA IN SOFFIT AREA FOR FUTURE TENANT <br />SIGN (VERIFY EXACT LOCATION WITH GENERAL CONTRACTOR). EXTEND 3/4" <br />EMPTY CONDUIT WITH PULL STRINGS TO LOCATION ABOVE FUTURE CEILING IN <br />TENANT SPACE. <br />12. PROVIDE CONCEALED OUTLET FOR EWC, VERIFY REQUIREMENTS PRIOR TO <br />ROUGH -IN, PROVIDE GFI RECEPTACLE FOR ELECTRIC WATER COOLER, IF <br />RECEPTACLE IS CONCEALED WITHIN WATER COOLER, PROVIDE GFI CIRCUIT <br />BREAKER. VERIFY REQUIREMENTS PRIOR TO ROUGH -IN. <br />13, RTU CIRCUITING, OVERCURRENT PROTECTION, AND WP/GFI RECEPTACLE TO BE <br />PROVIDED DURING TENANT BUILD -OUT. TENANT BUILDING DOCUMENTS TO BE <br />SUBMITTED SEPARATELY, <br />GENERAL NOTES <br />1. ALL EXPOSED CONDUIT SHALL BE LOCATED WITHIN JOIST SPACE AREA OR <br />ATTACHED DIRECTLY TO THE JOIST. CONDUIT SHALL NOT BE SUSPENDED FROM <br />STRUCTURE. <br />Job Number: 65173 <br />' Colwill Engineering <br />Aw om Consulting Engineers, Inc. <br />Engineering Business No. 9021 <br />4750 East Adamo Drive Tampa, Florida 33606 <br />%�'*= I Tel: 813-241-2525 Fax: 813-241-2424 <br />© 2013 ALL RIGHTS RESERVED <br />�S = Tec <br />Associates, Inc. AA26001933 <br />Architecture • Planning Interior Design <br />14125 N.W. 80th Ave. Suite 303 <br />Miami Lakes, FI. 33016 <br />T. 786-235-9097 <br />F. 305-362-4420 <br />dtiinfo@dtiarchitect.com <br />www.dtiarchitect.com <br />L CO <br />; �C,ENS' '4 <br />16 <br />O F 4U • <br />Phillip L. Cochran, <br />P.E. No.50716 <br />Revisions: <br />Date Description <br />10-21-13 OWNER CHANGES <br />L7 <br />O M <br />W <br />wQ <br />� <br />O <br />W <br />U <br />/W <br />V--I <br />W <br />Z <br />4 <br />H � <br />v a <br />a <br />Q <br />O <br />Z <br />►� <br />W <br />v <br />0 <br />� <br />z <br />M <br />M <br />Q <br />� <br />H <br />� <br />a <br />� <br />O <br />0 <br />n <br />0 <br />a <br />x <br />w <br />Job Number: <br />12049.01 <br />File name: <br />Issued Date: <br />07,17.13 <br />Drawn by: <br />AS/PK <br />Checked by: <br />DAS <br />SHEET NAME <br />POWER PLAN <br />SHEET NUMBER <br />E-291 <br />.P <br />