ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />Fff <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />�?4 <br />FOUR-WAY SWITCH <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />I--O <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />lO <br />EXHAUSTFAN <br />;Q <br />EXHAUST FAN/LIGHT COMBINATION <br />nD <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />kEg <br />PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />TV <br />TELEVISION (OPTIONAL) <br />TV 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />owl <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />C`/'? <br />G J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G J <br />OPT. CEILING FAN <br />GD <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />I I <br />I I <br />I I <br />LAV `I_ <br />_I I <br />L TUB/ <br />W/C SHOWER <br />LAV <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />I <br />I OPT. <br />LAV <br />ILAV <br />I <br />I <br />ti W/C <br />SHOWER <br />W/C <br />STUDOR ~� <br />VENTT DBL SINK <br />W/ DISP. <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />UNIT-C 1624 (1624) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1625 S.F. <br />4875 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10875 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33935 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9574 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />5200 <br />TOTAL: 31878 <br />LOAD WATTS --- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />3" <br />C.O. <br />DISCONNECT <br />------------------------- <br />OUTDOOR LIVING <br />INSTALL LIGHT <br />ROUGH -IN <br />FOR OPT. <br />FAN/LIGHT i WP <br />.m <br />�� II <br />1 <br />DINING <br />KITCHEN 1 <br />1-0"FI 1 — —J <br />GFI <br />SWITCH FOR <br />DISPOSAL IN CAB <br />UNDER SINK <br />GREAT ROOM <br />^� /.^TROUGH -IN\ <br />�yf <br />FOR OPT. <br />FAN/LIGHT 1 <br />I <br />I � <br />1 / <br />`S 01 <br />• <br />NTRY <br />IGHT AS e GFI <br />ER SPECS <br />DB & GFI TO I <br />BE ALIGNED I <br />VERTICALLY <br />Optional Overhead Service <br />200A <br />/ <br />Same As Underground <br />Indoor Panel <br />1 <br />150 Or 200 Amp Service <br />Center <br />C _ <br />iLU <br />F" <br />NEMA 1 <br />200 AMP <br />Z <br />W <br />ETER MAN <br />S <br />1 0-200 A P <br />Serial Cable <br />0 <br />NEMA <br />3R <br />Power Co. Feed ---_ <br />, #4 Solid COPPER Ground <br />Intersystem Bonding 7 <br />Termination Per <br />NEC 17, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />Typical 150-200 Amp Electrical Riser Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CO. <br />I <br />I <br />I <br />I <br />I <br />I <br />C.M <br />1 UPSTAIRS r <br />GFI <br />@ 44" <br />` <br />LW. <br />A.F.F. <br />1 \ 0 <br />I \ <br />/ <br />1 <br />I <br />GARAGE <br />I I <br />GARAGE <br />LIGHT AS <br />PER SPECS <br />GARAGE <br />O <br />DOOR <br />GFI <br />r — — <br />I <br />— — — — — — — — — — — — — —r <br />I <br />I <br />I <br />J <br />I <br />I <br />IZ Z <br />I <br />IQ d <br />I <br />I0 Q <br />I <br />Ij U <br />I <br />IT W <br />h r�r <br />I <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />1ST ELECTRICAL - UNIT-C 1624 <br />SCALE: A"=V-0" <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE <br />RANGE HOOD PER <br />SPECS <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />2ND ELECTRICAL - UNIT-C 1624 <br />SCALE: Ya"=1'-0" <br />0 <br />cam+Zia <br />O <br />Cad <br />CL <br />u <br />p m X <br />N fU C7 <br />r1 N Y <br />01 <br />d <br />C1 � <br />61 C <br />E r- <br />d <br />E 1' <br />ti <br />E <br />o <br />U <br />n <br />CM <br />O <br />CV <br />m <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural <br />plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential <br />7th Edition. Engineer's signature and seal is only for <br />the structural <br />engineering portions of the drawing pages bearing <br />Engineer's <br />signature and seal. <br />N <br />r <br />0 E S N <br />N <br />0) <br />G <br />J <br />'� " u- <br />7�COi <br />M v a 2 <br />c U_ a <br />u- Z <br />z <br />0 <br />o <br />W <br />'0�`° co J m <br />W <br />rn�a'� J w <br />Z <br />LL <br />00 <br />LO 3:o <br />M Z G <br />a <br />N U <br />0 UUU <br />Z <br />Z <br />W <br />M <br />N <br />� N <br />M <br />A <br />o <br />V <br />0 <br />f6 <br />w s <br />� <br />Jim <br />0 <br />— M g <br />: <br />C) t <br />• <br />yw `) <br />r. Q <br />C <br />M <br />Jrc <br />Z <br />Q <br />U_ <br />R3 E <br />?_ <br />a O <br />E U <br />�z <br />❑a <br />r0 <br />7u <br />". <br />� <br />R <br />d <br />Z <br />xLL <br />Z�� <br />W <br />ns <br />LLSa <br />q� <br />M <br />C O <br />0 <br />.N <br />> 00 <br />~ <br />U <br />ai <br />rn <br />N <br />0 <br />Cfl <br />00 <br />CN <br />L <br />T <br />T <br />Q_ <br />E <br />�— <br />CT <br />60 <br />'vca <br />, 2 <br />U <br />co <br />C4 <br />F— <br />0 <br />M <br />L O <br />r co <br />LO <br />C <br />00 <br />M �O <br />� <br />ILO <br />r <br />C� <br />T— <br />y <br />c <br />1 <br />CV) <br />(1 <br />0 <br />Z <br />Z <br />E TT <br />y <br />c <br />cc a <br />U _j <br />Q 0 <br />JOB <br />NO: 23-05713-05718 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />11.2 <br />