THIS DETAIL ONLY REFERS TO THE DIAMOND -MESH <br />EXPANDED METAL LATH ATTACHMENT. <br />METAL LATH <br />16GAx1-1\2" LONG (3/4"-1" CROWN) <br />STAPLES @ 6" O.C. VERT BETWEEN <br />STUDS (NOTED THUS:—) - OFFSET <br />STAPLES BETWEEN STUDS AS SHOWN <br />II II II <br />III I I III <br />� II II II II <br />I MAX- 1 I I I I <br />II II II <br />WALL SHEATHING <br />DOUBLE JOIST CONSTRUCTION <br />(Not required if both loaded equally from above) <br />Filler blocking <br />1/8" gap <br />r <br />1) Support back of web during nailing to prevent damage to <br />web -flange connection. <br />2) Block solid between joists for full length of span. <br />3) Leave 1/8" gap between top of filler blocking and bottom of top flange. <br />4) Place joists together and nail from each side with 2 rows of 10d nails <br />16GAx1-1/2" LONG (3/4"-1" 2x_: CONTRACTOR TO PROVIDE 2x TO FILL THE HEIGHT at 12" o.c., clinched when possible. Stagger rows from opposite <br />CROWN) STAPLES @ 6" OF THE JOIST ASA REQUIRED LEAVING Y8" GAP @ TOP sides by 6". <br />O.C. VERT INTO STUDS <br />(NOTED THUS:—) DOUBLE JOIST CONNECTION <br />METAL LATH ATTACHMENT DETAIL <br />REV. 09.24.21 SCALE: 3/4" = V-0" <br />*DETAIL EXCEEDS THE REQUIREMENTS FOR FBCR 703.7.1 LATH* <br />**ONLY APPLIES TO LENNAR TPA/JAX** <br />10'-0" <br />TANK -LESS W/H <br />CORNER OF L I <br />HOME H C G <br />GARAGE SIDE O O O <br />5'" Q <br />-0- <br />10 <br />c� <br />STUB -OUT FOR O 1'-0" = o <br />GAS METER ' <br />� o <br />• MEASUREMENTS ARE FROM FINISHED FLOOR <br />• ROUGH -IN GAS TO RIGHT (ALWAYS) - 12" OFF -CENTER <br />• ROUGH -IN ELECTRIC TO LEFT (ALWAYS) - 12" OFF -CENTER <br />GAS CONNECTION DETAIL <br />**ONLY APPLIES TO HILLSBOROUGH AND PASCO COUNTY** <br />RAFTER SPAN TABLE <br />MEMBER SIZE AND SPACING <br />MAXIMUM LENGTH <br />MEMBER CONNECTIONS* <br />2" X 4" @ 16" O.C. <br />7-5" <br />(2)16d TOENAILS <br />2" X 6" @ 16" O.C. <br />10'-8" <br />(2)16d TOENAILS <br />2" X 8" @ 16" O.C. <br />13'-9" <br />(3) 16d TOENAILS <br />2" X 10" @ 16" O.C. <br />16'-5" <br />(1) SIMPSON HTS20 OR 3 16d TOENAILS <br />2" X 12" @ 16" O.C. <br />19'-3" <br />(1) SIMPSON HTS20 OR (4)16d TOENAILS <br />2" X 4" @ 24" O.C. <br />6'-1" <br />(2)16d TOENAILS <br />2" X 6" @ 24" O.C. <br />F-T <br />(2)16d TOENAILS <br />2" X 8" @ 24" O.C. <br />11'-0" <br />(2)16d TOENAILS <br />Ti X 10" @ 24" O.C. <br />13'-0" <br />(3)16d TOENAILS <br />2" X 12" @ 24" O.C. <br />15'4" <br />(1) SIMPSON HTS20 OR (3)16d TOENAILS <br />* TOENAIL CONNECTIONS DESIGNED FOR SHEAR ONLY (i.e. RAFTER TO RIDGEBEAM). <br />** SOUTHERN YELLOW PINE, 55 PSF LOADING <br />Backer and Filler Block Dimensions <br />BCI®Joist <br />Backer Block <br />Series <br />Thickness <br />Filler Block Thickness <br />3/4" orp <br />5000s 1.811.7 <br />nel <br />wood panels <br />Two 3/4" wood panels or 2 x <br />1-1/8" or two 1/2" <br />6000s 1.8/1.7 <br />,,wood panels <br />2 x _ + 5/8" or 3/4" wood panel <br />1-1/8" or two 1/2" <br />6500s 1.8/1.7 <br />wood panels <br />2 x _ + 5/8" or 3/4" wood panel <br />1-1/8" or two 1/2" <br />602.0 <br />wood panels <br />2 x -_ + 5/8" or 3/4" wood panel <br />902.0 <br />2 x _ lumber <br />Double 2 x _ lumber <br />N.T.S <br />SQUASH BLOCKS AT INTERIOR Boise Joist Blocking <br />BEARING Use 3" (10d) nails at 6" o.c. <br />Vertical load transfer =1900 plf max along load bearing wall. Load bearing walls <br />Load bearing wall must stack <br />Non -stacking walls over squash=20 blocks and I -) <br />require additional wall or beam below.* <br />consideration. Check <br />local building <br />code for appropriate 1116" <br />: <br />details in -One 10d box �i <br />areas=20 of high or=20 sinker 1' <br />lateral load. nail each side <br />at bearing. <br />Provide t o de adequate a bearing <br />for each lapped joist. <br />Squash block 10d nails (2x4 minimum) @ <br />SECTION INT. BRG. WALL <br />- <br />Bearing wall, Versa -Lam LVL or N.T.S. <br />Glulam Beam - <br />NO HOLES (EXCEPT MINIMUM SPACING = 2x GREATEST <br />KNOCKOUTS) ALLOWED DIMENSION OF LARGEST HOLE <br />IN BEARING ZONES D (KNOCKOUT EXEMPTS) <br />(see table below) D <br />(see table below) <br />DO NOT cut, notch <br />or drill flanges <br />FILL CELL <br />rn <br />w <br />CONT. #5 STD. 900 <br />BAR HOOK <br />STD. 90' HOOK <br />BOND BEAM <br />SIMPSON MGT <br />w/ (22)10d <br />NAILS TYP. GIRDER TRUSS <br />CONT. #5 <br />— BAR 2X TOP PLATE <br />5/8"0 <br />#5 CONT. THRU <br />FROM BOLT <br />FOUNDATION <br />TO HIGHEST <br />BOND BEAM STEP <br />I BOND BEAM <br />SCALE: N.T.S. <br />2nd FLOOR <br />INTERIOR/EXT WALL SEE <br />PLAN FOR MORE INFO <br />BEARING COLUMN <br />CONT. BASE PLATE <br />SEE PLAN FOR REQ'D <br />COLUMN AND <br />1 ", ' .;,,--PLYWOOD FLOOR <br />SHEATHING PER PLAN <br />CONNECTION <br />TJI TO BE CUT TO ALLOW <br />FOR BLOCKING/TJI <br />`MASONRY WALL OR <br />I <br />INTERIOR BRG. WALL <br />TJI PER PLAN <br />OTHERWISE SOLID <br />BLOCKING TO MATCH <br />i <br /># OF 2nd FLOOR <br />Solid block all posts from STUDS <br />above to bearing below. <br />SECTION @ INT. BRG. WALL <br />N.T.S. <br />1/8" min. ) Small gap <br />2" min. <br />2" max. <br />4" max. - - - <br />Web Stiffener Fastener Schedule <br />- <br />Joist Bearing Location <br />lr + <br />li Series 1 Depth End Intermediate 1 <br />f % <br />2-8d <br />2-8d <br />BCI 5000s� 11-7/8" 2-8d <br />3-8d <br />it 14" 2-8d ; <br />5-8d <br />Clinch nailsg_1/2" <br />/� <br />R 2_8d <br />0 <br />2-8d - - <br />when <br />r' <br />11 7/8" 2 8d <br />��14 <br />3-8d <br />possible <br />^iBCI <br />BCI 6500s2 8d <br />5-8d <br />_ <br />� � 12 8d <br />�_ <br />6-8d <br />117/8" 2-8d <br />- BCI 60s� 14" _2-8d <br />3-8d <br />5-8d - <br />Tight fit <br />r 1 16' 2-8d j <br />6-8d <br />11 73-16d '1 <br />3-16d <br />2x4/PI ood/OSB web stiffener <br />2" min. ® 14" 5-16d <br />BCI 90s <br />5-16d <br />required when indicated or <br />4" max. 16" 1 6-16d <br />6-16d <br />Hangers with side nailing. <br />- - - <br />Hangers with sides not containing <br />WEB STIFFENER <br />top flange of joist. <br />- Birdsmouth cuts. <br />N.T.S. <br />Under 2nd floor column w/ loads <br />higher than 15001b. <br />BLOCKING PANEL, INTERIOR <br />Vertical load transfer =1900 plf max. along bearing wall <br />Required on interior walls : - for vertical load transfer <br />when load bearing - for lateral support when joists <br />meet over wall, or wall stacks directly over wall or <br />beam below Load bearing wall must stack over <br />/ blocking and wall or beam below.* <br />When joists meet over wall, provide <br />_1 3/4" minimum bearing for each. <br />Use 10dx3" nails at 6"o.c. for all joist <br />blocking panel *Non -stacking walls <br />require additional consideration. — <br />1 16" A 1%2' ROUND HOLE MAY q6" 6" <br />BE CUT ANYWHERE IN CANTILEVER <br />THE WEB. PROVIDE AT <br />LEAST 3" OF CLEARANCE <br />FROM OTHER HOLES <br />MINIMUM DISTANCE FROM SUPPORT, LISTED BELOW, IS REQUIRED FOR ALL HOLED GREATER THAN 1Y2" <br />DO NOT CUT HOLES <br />LARGER THAN 1y2' <br />ROUND IN <br />CANTILEVERS. <br />R�xtrnd Wile C>flarnelt n <br />2 <br />4 <br />a. <br />6 <br />7 <br />8 <br />$48 <br />10 <br />11 <br />12 <br />13 , _ <br />m <br />� .: <br />2 <br />3 ; <br />5 ' <br />6 <br />$ <br />1 <br />Any 16" joist <br />Span (ft) <br />8 <br />V-0" <br />V-1" <br />V-2" <br />V-2" <br />V-3" <br />V-3" <br />V-7' <br />1'-11" <br />2'4" <br />2-9" <br />32' <br />3-7' <br />12 <br />1'-0" <br />V-1" <br />V-2" <br />V-2" <br />V-3" <br />V-9" <br />24" <br />2-11" <br />3-7' <br />4'-2' <br />4'-9" <br />6 4" <br />16 <br />1'-0" <br />V-1" <br />1' 2" <br />V-2" <br />V-7" <br />2-5- <br />3'-2 <br />3-10" <br />4'-9 <br />5-7" <br />64" <br />7 2" <br />20 <br />1 V-0" <br />V-1" <br />1 V-2" <br />V-2" <br />2-0" <br />3-0" <br />4'-0" <br />4'-10" <br />6-11" <br />6-11" <br />7'-11" <br />8'-11" <br />24 <br />1,-0" <br />I 1'-1" <br />11'-2' <br />V-3" <br />2-9 <br />3-7 <br />4'-9 <br />6-10" <br />I T-2' <br />1 8'4" <br />97-0" <br />10'-9 <br />NOTES: <br />1. JOISTS MUST BE PROPERLY DESIGNED TO MEET BUILDING CODE REQUIREMENTS. <br />2. TABLE IS FOR UNIFORMLY LOADED MAXIMUM LOADS OF 40 PSL(LIVE) AND 15 PSF (DEAD) ON SIMPLE SPAN APPLICATIONS ONLY. <br />3. REFER TO JOIST SPECIFIER GUIDE FOR INSTALLATION AND OTHER INFO. <br />4. SELECT A TABLE ROW BASED ON JOIST DEPTH AND THE ACTUAL JOIST SPAN ROUNDED UP TO THE NEAREST TABLE SPAN. SCAN ACROSS <br />THE ROW TO THE COLUMN HEADED BY THE APPROPRIATE ROUND HOLE DIAMETER OR RECTANGULAR HOLE SIDE. USE THE LONGEST SIDE OF <br />A RECTANGULAR HOLE. THE TABLE VALUES IS THE CLOSEST THAT THE CENTERLINE OF THE NEAREST SUPPORT. <br />5. THE ENTIRE WEB MAY BE CUT OUT. DO NOT CUT THE FLANGES. HOLES APPLY TO EITHER SINGLE OR MULTIPLE JOISTS IN REPETITIVE <br />MEMBER CONDITIONS. <br />6. FOR MULTIPLE HOLES, THE AMOUNT OF UNCUT WEB BETWEEN HOLES MUST EQUAL AT LEAST TWICE THE DIAMETER (OR LONGEST SIDE) OF <br />THE LARGEST HOLE. <br />7. 1Y2" ROUND KNOCKOUTS IN THE WEB MAY BE REMOVED BY USING A SHORT PIECE OF METAL PIPE AND HAMMER. <br />8. HOLES MAY BE POSITIONED VERTICALLY ANYWHERE IN THE WEB. THE JOIST MAY BE SET WITH THE %" KNOCKOUT HOLES TURNED WITHER <br />UP OR DOWN. <br />9. THIS TABLE WAS DESIGNED TO APPLY TO THE DESIGN TO APPLY TO THE DESIGN CONDITIONS COVERED BY TABLES ELSEWHERE IN HIS <br />PUBLICATION. USE THE BC CALC SOFTWARE TO CHECK OTHER HOLE SIZES OR HOLES UNDER OTHER DESIGN CONDITIONS. IT MAY BE <br />POSSIBLE TO EXCEED THE LIMITATIONS OF THIS TABLE BY ANALYZING A SPECIFIC APPLICATION WITH THE BC CALC SOFTWARE. <br />HOLE CUTTING CHART <br />N.T.S. <br />Plumbing <br />Joist <br />I -Joist can be offset <br />up to 3" to avoid <br />vertical plumbing <br />3" max <br />JOISTS OFFSET <br />N.T.S. <br />1/4"-2" gap — <br />Backer Block <br />"Top Mount" "Face Mount" <br />Backer block shall be tight Backer block shall be tight <br />to bottom of top flange with to top of bottom flange with <br />1/4"-2" gap at top of bottom 1/4"-2" gap at bottom of top <br />flange. flange. <br />Web stiffner as <br />Web stiffeners are not required when top required if hanger <br />flange is laterally supported by joist hanger. doesn't meet <br />height <br />requirements <br />0.6 X Joist <br />D " ' depth <br />I -JOISTS BUCKETS <br />N.T.S. <br />IN <br />SIMPSC <br />w/(22)' <br />NAILS 1 <br />TYPICAL SIMPSON MGT TO <br />BUILT-UP COLUMN DETAIL <br />TYPICAL SIMPSON LUS/HUS/HUC <br />INSTALLATION <br />AIN. EMBEDMENT <br />SCHEDULE FOR <br />AND QUANTITY <br />)F FASTENERS <br />TYPICAL SIMPSON META12 / <br />META12 TSS INSTALLATION <br />A/C CHASE 4" PVC <br />SLEEVE THRU STEM <br />WALL <br />. 8 °° <br />FINISH GRADE <br />SLEEVE THRU STEM--` <br />SEE PLAN FOR •• d . • , . • <br />FOUNDATION INFO ` a. a <br />STEM FOUNDATION <br />GRADE REINF. SEE PLAN <br />d 4 d <br />rVV UmAot 4 YVI, <br />SLEEVE THRU FOOTING <br />MONO FOUNDATION <br />TYP. FND. PENETRATIONS <br />SCALE: N.T.S. <br />SIMPSON META12 / META12 TSS <br />INSTALLATION @ MID SPAN <br />NOTE: <br />UPLIFT VALUE <br />IS BASED ON <br />S.P.F. <br />LOCATION OF <br />SECOND H10A <br />• •` (WHEN <br />SIMPSON H10A • REQUIRED) <br />w/ (18) 10d x 1 1/2" <br />NAILS <br />- <br />UPLIFT = 1015# <br />TYPICAL SIMPSON H10A <br />INSTALLATION <br />TYPICAL SIMPSON MTS <br />/ HTS INSTALLATION <br />PLUMBING LINE <br />TOP (2) #5's x 4'-0" <br />CENTERED @ PIPE PVC OR SCH40 SLEEVE <br />PENETRATION <br />I ° ° <br />d ° a <br />II=1I1= • • III —II' <br />--12" BELOW <br />GRADE <br />SEE FND. PLN. <br />SIZE & REINF. <br />PIPE VERTICAL THRU FND. <br />TOP (2) #5's x 4'-0" PVC OR SCH40 SLEEVE <br />CENTERED @ PIPE PLUMBING LINE <br />PENETRATION <br />d d / <br />--- - - ° - - _I • ° d e <br />Z ° • <br />c.>a � <br />SEE FND. PLN. <br />SIZE & REINF. <br />PIPE PERPENDICULAR TO FND. <br />TOP (2) #5's x 4'-0" PVC OR SCH40 SLEEVE <br />CENTERED @ PIPE <br />PENETRATION PLUMBING LINE <br />° d <br />d -I _ 1-1 11 1 1 r <br />° <br />SEE FND. PLN. <br />SIZE & REINF. <br />N <br />N <br />m <br />0 <br />m <br />CX_ <br />W <br />w f7 O <br />V7 y O f0 <br />.Q N JL: <br />d N <br />d t= L G <br />y O -d <br />a u. <br />i CM <br />6 <br />ti y C l� <br />C E <br />1 u <br />0 <br />J' <br />CIV <br />Ly <br />W <br />JA <br />y.o <br />Sri <br />To the best of the Engineers knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential 7th Edition. Engineers signature and seal is only for <br />the structural <br />engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />rA <br />W <br />Q <br />E p S N <br />O M N Co <br />C <br />J J <br />M <br />M <br />Cn ^ 0 LL W <br />0 <br />a <br />Q <br />13 <br />4j cNi � u, <br />toLL (L Y U'- <br />Z <br />o <br />�rn o <br />"m�O <br />Lu <br />W°�O1 <br />nz�Z <br />z <br />LL <br />Oz H <br />N <br />o0 ❑W <br />z <br />W <br />z N M <br />0 <br />iz- <br />- N <br />F~ 8 <br />�� <br />CV <br />LL <br />4-1 <br />� <br />Ou <br />pp <br />C.) M <br />w <br />� <br />° 8 <br />I <br />S L w <br />U � gt <br />C <br />Q 0 <br />• <br />Q <br />J <br />n <br />w <br />E E <br />n E <br />E v <br />s <br />z® <br />rw 2 <br />'1' ra <br />a2 <br />x <br />LL <br />ra <br />H <br />Luj <br />N <br />ZMc <br />m _J <br />WU5�= <br />o� <br />NZ <br />wig <br />t <br />0 CD <br />>00 <br />N <br />U <br />y <br />rn <br />U <br />CO <br />('(D <br />L <br />L <br />DO <br />M <br />CID <br />ll <br />CF) <br />CL <br />E <br />Cr <br />00 <br />w m <br />c <br />C) <br />T <br />F-- <br />0 <br />0 <br />CN <br />LO <br />M M <br />1.o <br />E <br />� <br />'0 00 <br />r` N <br />M <br />O <br />� <br />04 <br />Cfl <br />T <br />M <br />r— <br />y <br />•v; In <br />o <br />z <br />cc <br />z <br />E T <br />N <br />6 <br />m <br />c <br />d <br />E2 <br />U J <br />Q p <br />J <br />JOB <br />NO: 23-05713-05718 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />SN 1 <br />