ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11.In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />FET <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />I-.'r-1h <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />$ <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />?4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />O <br />EXHAUST FAN <br />;Q, <br />EXHAUST FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />k[e]D <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />© <br />TELEVISION (OPTIONAL) <br />T�2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />]M <br />ELECTRIC METER <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />G J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G r J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />jI HANSON <br />BOX <br />I I <br />____ I I ti W/C <br />LAV <br />-1 1 3" SHOWER <br />3" VTR <br />JIL <br />I <br />I <br />I <br />I <br />I <br />I OPT. <br />�I LAV <br />LI JAV <br />I <br />I <br />L TUB/ <br />W/C SHOWER <br />STUDOR R. <br />VENTQ I , DBLSINK <br />t TI W/ DISP. <br />LAV I W/C <br />PLUMBING RISER <br />SCALE: NITS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />UNIT-C 1624 (1624) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1625 S.F. <br />4875 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10875 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33935 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9574 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />5200 <br />TOTAL: 31878 <br />LOAD WATTS --- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service <br />Same As Underground <br />150 Or 200 Amp Service <br />1 <br />Power Co. Feed <br />200A <br />Indoor Panel <br />Center <br />NEMA 1 <br />RMAN <br />200 AMP <br />313 <br />Cable <br />#4 Solid COPPER Ground <br />Intersystem Bonding <br />Termination Per <br />NEC 17, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />Typical 150-200 Amp Electrical Riser Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CO. <br />C.O. <br />------------------------- <br />OUTDOOR LIVING <br />INSTALL LIGHT <br />ROUGH -IN <br />FOR OPT. <br />FAN/LIGHT FI <br />i `� �' GP <br />All <br />(fl) (U)GFI <br />L� <br />1 <br />DINING <br />KITCHEN <br />1 /-- <br />F---� <br />- --- --- GFI <br />SWITCH FOR <br />DISPOSAL IN CAB <br />UNDER SINK <br />GREAT ROOM <br />/,>ROUGH -IN\ <br />`!��, `FOR OPT. <br />FAN/LIGHT' <br />r� � <br />r � <br />r <br />1 / <br />E: <br />DB & GFI TO <br />BE ALIGNED <br />VERTICALLY <br />I <br />I <br />I <br />I <br />I <br />rq-L—j <br />DISCONNECT <br />►FN$DEDICATED <br />RECEPTACLE FOR <br />WN, <br />—► iMICROWAVE <br />•10A <br />0'R� RANGE t PER <br />►W A <br />00" <br />UPSTAIRS F <br />a <br />GFI <br />@ 44" <br />` \ <br />W.H. <br />A.F.F. <br />' <br />` 0 <br />r <br />I <br />GARAGE <br />I <br />GARAGE <br />LIGHT AS <br />PER SPECS <br />GARAGE <br />DOOR <br />GFI <br />--------------- <br />I <br />I <br />UJ <br />I <br />I <br />10 Z <br />I <br />IQ d <br />I <br />I0 Q <br />I <br />I� U <br />I <br />I <br />� U <br />I <br />I <br />IUJIJ <br />W <br />I <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />1ST ELECTRICAL — UNIT—C 1624 <br />SCALE: X"=V-0" <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />I <br />2ND ELECTRICAL — UNIT—C 1624 <br />SCALE: Y"=V-0" <br />C%j <br />C%A <br />.®. <br />dLU <br />7 W <br />O t <br />C7 <br />_ R f_..) Q <br />s b c X <br />N C U- a <br />o a - <br />% <br />a, o <br />Cj <br />CU <br />xu . <br />15 <br />7 ev <br />�.�a,ev <br />t .M <br />C= <br />M <br />0 <br />CV <br />o <br />o <br />7 "0' <br />dr <br />, <br />4' <br />� 0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications <br />contained within these <br />drawings comply with the 2020 Florida <br />Building Code - <br />Residential 7th Edition. Engineer's <br />signature and seal is only <br />for <br />the structural engineering portions <br />of the drawing pages bearing <br />Engineer's signature and seal. <br />O E c C,4 <br />CD N <br />M <br />N p <br />C1 <br />J <br />- <br />to <br />Jnr <br />Q <br />Qj co V w a d <br />Z 'S 0 <br />Z� <br />r @ v 0 0 <br />j <br />r_o <br />(Q � U0 coJ m <br />Z <br />O 0 W <br />h Z U U) H <br />N <br />O U ❑❑❑ <br />Z <br />_._ W <br />fAiiiiiiiiiiiiiiiih <br />z N o <br />z o <br />z <br />d <br />J <br />r <br />M <br />Nn' <br />W <br />��r+, <br />(D O <br />a--J <br />t'6 <br />C) <br />� m <br />U <br />O <br />V) <br />w g <br />C�5 w <br />ws <br />v <br />sLU <br />e <br />V =O y <br />cC/) <br />Q 'N <br />0 <br />O' <br />ti <br />CO <br />M <br />M <br />J <br />¢ <br />0 <br />W <br />Z <br />Z <br />G <br />� <br />LL <br />Q <br />E v <br />zo <br />W O <br />z <br />Z o <br />Z <br />oa <br />d <br />< <br />w O <br />0, <br />W <br />_� <br />c c <br />m J <br />< o <br />O0< <br />U <br />`gym <br />mo <br />oa <br />Z <br />aw <br />C } <br />¢ o <br />g Z <br />Z <br />U.) <br />M <br />o <br />try <br />a Z <br />=F <br />o <br />w< <br />;o <br />M <br />A <br />" F <br />v <br />3 <br />0 O <br />;n <br />>r <br />U <br />.- <br />CU <br />N <br />0 <br />F� <br />CO <br />CIO <br />co <br />r <br />N <br />N <br />a <br />�. <br />6i <br />E <br />60 <br />n <br />U <br />r <br />N <br />ate-+ <br />It <br />F— <br />0 <br />LO <br />S] <br />M <br />Lfi <br />.� <br />CO <br />It CD <br />0 <br />Cn <br />� <br />Q T <br />M N <br />I <br />ai <br />ro <br />w I <br />CO <br />M <br />T <br />o <br />Z <br />:3 <br />E r <br />`m <br />c <br />a <br />E <br />U � <br />Q p <br />JOB <br />NO: 23-03667-03672 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />11.2 <br />'00 <br />