<br />5PECINCATION5
<br />GENERAL
<br />CONTRACTOR SHALL REfER TO ALL RELATED DOCUMENTS, ARCHITECTURAL, STRUCTURAL,
<br />CIVIL AND MEP DRAWINGS, AND f ULLY UNDERSTAND THE SCOPE Of WORK AND CONDITION
<br />Of CONSTRUCTION.
<br />THE WORK UNDER TH15 SPECIf ICATION5 AND DRAWINGS SHALL INCLUDE ALL LABOR.
<br />ALL INSTALLATION Of DEVICES AND CONNECTION Of CONDUCTORS SHALL BE PERfORMED
<br />13Y LICENSED AND SKILLED ELECTRICIAN OR JOURNEYMAN.
<br />ALL WORK SHALL 13E COMPLETED TO THE 5AT15fACTION Of THE OWNER. If ANY PORTION Of
<br />THE WORK 15 fOUND LINSATISfACTORY BY THE OWNER, IT SHALL BE REMOVED AND
<br />REINSTALLED WITHOUT DELAY AT NO C05T TO THE OWNER.
<br />THE WORK INCLUDES, BUT NOT LIMITED TO:
<br />THE COMPLETE ELECTRICAL DISTRIBUTION SYSTEM.
<br />ROUGH -IN AND NNAL CONNECTIONS TO ALL DEVICES REQUIRING ELECTRICAL POWER,
<br />INCLUDING OWNER PROVIDED EQUIPMENT.
<br />LIGHTING CONTROL
<br />LIGHTING fIXTURES
<br />EACH CONTRACTOR SHALL 013TAIN ALL PERMITS AND INSPECTIONS REQUIRED BY THE
<br />REGULATORYAUTHORITIE5. ALL fEE5 RELATED TO 013TAINING PERMITS AND INSPECTION
<br />SHALL BE PAID fOR BY EACH CONTRACTOR IN H15 TRADE.
<br />ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH LOCAL, COUNTY, STATE, AND
<br />NATIONAL ELECTRICAL CODE 2017, 5PECIf ICATIONS, UTILITY COMPANY REQUIREMENTS AND
<br />ALL INDUSTRY STANDARDS.
<br />ANY DIffERENCE5 IN AE30VE MENTIONED REQUIREMENTS, THE M05T STERN SHALL
<br />OVERRULE ALL OTHERS.
<br />IN ADDITION TO A13OVE MENTIONED CODES AND 5PECIf [CATIONS, THE fOLLOWING
<br />INDUSTRY STANDARDS SHALL 13E COMPLIED If THEY ARE MORE STRINGENT.
<br />IEEE
<br />IE5
<br />IECC 2009
<br />A5HRAE 90.1
<br />NfPA
<br />NEMA
<br />UL
<br />ADA
<br />THE MANUfACTURER5 PUBLISHED DIRECTIONS SHALL BE fOLLOWED IN THE DELIVERY,
<br />STORAGE, PROTECTION, INSTALLATION AND WIRING Of ALL EQUIPMENT AND MATERIAL.
<br />THE DRAWINGS SHOW DIAGRAMMATICALLY THE LOCATIONS Of THE VARIOUS LINES,
<br />CONDUITS, fIXTURES, AND EQUIPMENT AND THE METHOD Of CONNECTING AND
<br />CONTROLLING THEM. IT 15 NOT INTENDED TO SHOW EVERY CONNECTION IN DETAIL AND ALL
<br />fITTINGS REQUIRED fOR A COMPLETE SYSTEM. THE SYSTEMS SHALL INCLUDE BUT ARE NOT
<br />LIMITED TO THE ITEMS SHOWN ON THE DRAWINGS. EXACT LOCATIONS Of THESE ITEMS
<br />SHALL BE DETERMINED 13Y UfERENCE TO THE GENERAL PLANS AND MEASUREMENTS AT THE
<br />BUILDING AND IN COOPERATION WITH THE OTHER SUBCONTRACTORS, AND IN ALL CASES,
<br />SHALL BE SUBJECT TO THE APPROVAL Of THE OWNER. THE OWNER RESERVES THE RIGHT
<br />TO MAKE ANY REA50NABLE CHANGE IN THE LOCATION Of ANY PART Of THIS WORK WITHOUT
<br />ADDITIONAL C05T TO THE OWNER.
<br />CONTRACTOR SHALL SEEK APPROVAL f ROM THE OWNER fOR ANY CHANGES TO THE
<br />SPECIfICATION5 OR CONTRACT DOCUMENTS.
<br />ANY EXCEPTIONS, INCONSISTENCIES AND CONfLICT5 IN CONTRACT DOCUMENTS,
<br />5PECIf ICATION5 AND CONTRACT DOCUMENTS BY OTHER TRADE SHALL BE BROUGHT TO
<br />ATTENTION TO THE OWNER PRIOR TO BID.
<br />CONTRACTOR SHALL COORDINATE AND VERIfY THE WORK WITH EX15TING CONDITIONS AND
<br />THE WORK Of OTHER TRADE PRIOR TO ANY fABRICATION5 OR INSTALLATION. If THE LAYOUT
<br />Of THE DEVICES ON DRAWINGS ARE IMPRACTICAL TO THE CONDITION IN ff IELD,
<br />CONTRACTOR SHALL NOTIfY THE OWNER IMMEDIATELY PRIOR TO ANY fABRICATION OR
<br />INSTALLATION.
<br />ELECTRICAL DEVICES ARE INDICATED ON DRAWINGS AT APPROXIMATE LOCATIONS. THE
<br />OWNER RESERVE THE RIGHT TO MAKE REASONABLE CHANGES IN LOCATIONS WITHOUT
<br />ADDITIONAL COSTS.
<br />THE LINES INDICATING BRANCH CIRCUITS DO NOT REPRESENT THE ROUTING Of ELECTRICAL
<br />CONDUITS. THEY INDICATE THE LAYOUT AND CONTROL Of CIRCUITS.
<br />PRODUCTS AND WORK
<br />MATERIALS fURN15HED SHALL BE NEW AND 13Y STANDARD MANUFACTURERS AND MUST
<br />CONfORM TO THE NATIONAL BOARD Of f IRE UNDERWRITERS REQUIREMENTS AND BEAR THE
<br />UNDEKWRITER5 LABORATORI ES' SEAL Of APPROVAL.
<br />L15TED MANUfACTURER5, MODELS, OR CATALOGUE NUMBERS IN PART OR ALL SHALL ENTAIL
<br />TO INCLUDE THE PUBL15HED MANUfACTURER!S DESCRIPTION AND 5PECIfICATION.
<br />CONTRACTOR SMALL NOT INTERPRET THAT THE L15TED MANUfACTURER5 IN 5PECIfICATION5
<br />OR DRAWINGS TO EXCLUDE ALL OTHER MANUfACTURERS
<br />CONTRACTOR SHALL MAKE CERTAIN THAT ALL EQUIPMENT f IT IN THE SPACE DESIGNATED
<br />AND DESIGNEE) fOR THE SURROUNDINGS IT OCCUPIES.
<br />COMPLETE CATALOGUE ILLUSTRATION AND DE5CRIFTION5 Of ALL EQUIPMENT SHALL BE
<br />SUBMITTED TO THE OWNER PRIOR TO ORDERING ANY EQUIPMENT.
<br />ALL HORIZONTAL RUNS Of CONDUITS SHALL BE SUPPORTED 13Y MEANS Of APPROVE[)
<br />HANGER fROM THE STRUCTURAL CEILING.
<br />COORDINATE THE WORK UNDER THIS SECTION WITH ALL OTHER TRADES.
<br />CONDUITS AND RACEWAYS:
<br />MANUfACTUREP,5: SQUARE D, B-LINE, ALLIED TU13E * CONDUIT, HOfffMAN, CARLON
<br />ELECTRICAL, WIRE MOLD.
<br />OUTDOORS EXP05ED: RIGID STEEL.
<br />OUTDOORS CONCEALED ABOVE GROUND: RIGID STEEL.
<br />OUTDOORS UNDERGROUND: TYPE EFC-40-PVC
<br />OUTDOOR5 CONNECTION TO VIBRATING EQUIPMENT (INCLUDING TRANSFORMERS AND
<br />MOTOR DRIVEN EQUIPMENT): LfMC,
<br />BOXES AND ENCLOSURES ABOVE GROUND: NEMA 3R UNLE55 NOTED OTHERWISE ON PLANS.
<br />INDOORS EXPOSED NOT SUBJECT TO PHY51CAL DAMAGE: EMT.
<br />INDOORS EXPOSED NOT SUBJECT TO SEVERE PHY51CAL DAMAGE: EMT.
<br />INDOORS EXPOSED SUBJECT TO SEVERE PHY51CAL DAMAGE: RIGID STEEL CONDUIT.
<br />INDOORS CONCEALED IN CEILINGS AND INTERIOR WALLS AND PARTITIONS: EMT.
<br />INDOORS CONNECTION TO VIBRATING EQUIPMENT: fMC, EXCEPT USE LFMC IN DAMP OR
<br />WET LOCATIONS.
<br />INDOORS DAMP OR WET LOCATIONS: IMC.
<br />INDOORS LOW -VOLTAGE CABLES: EMT.
<br />5PECINCATION5
<br />CONDUCTORS:
<br />COPPER CONDUCTORS # 10 AND SMALLER:
<br />LABELED PER UL 83, TYPE THHN/THWN, SOLID COPPER GOO VOLT IN5ULATION, UNIfORM
<br />COLOR CODED JACKET WITH JACKET DATA.
<br />METAL CLAD (TYPE MC) CABLE WHERE INSTALLED IN ACCORDANCE WITH NEC ARTICLE 330.
<br />COPPER CONDUCTORS #8 OR LARGER:
<br />LABELED PEP, UL 83, TYPE THHN/THWN, STRANDED COPPER, GOOVOLT INSULATION, UNIfORM
<br />COLOR CODED JACKET WITH JACKET DATA.
<br />ACCEPTABLE MANUfACTURER5 Of CONDUCTORS:
<br />PIRELLIE
<br />5OUTHWIRE
<br />AETNA
<br />REPUBLIC
<br />AfC
<br />ENCORE WIRE
<br />KEKITE
<br />CONTRACTOR MAY USE ALUMINUM CONDUCTORS fOR #4 AWG OR LARGER IN THE PLACE Of
<br />COPPER CONDUCTORS. CONTRACTOR SHALL REfER TO NEC TABLE 3 10- 1 G fOp,
<br />EQUIVALENT AMPACITY AND SHALL COMPENSATE fOR VOLTAGE DROP.
<br />MOLDED CASE CIRCUIT BREAKER:
<br />INCLUDE SCHEDULE Of ALL fU5F_5, RATINGS, TIME COORDINATION DATA, MANUfACTURER!5
<br />STANDARD DATA AND TIME -CURRENT CURVES. ALL DATA SHALL 13E BASED ON TEST Of
<br />STANDARD PRODUCTS.
<br />APPROVED MANUfACTURERS:
<br />GENERAL ELECTRIC
<br />CUTLER HAMMER
<br />SQUARE D
<br />SIEMENS
<br />THERMAL -MAGNETIC 13OLT-IN TYPE CIRCUIT BREAKERS WITH QUICK -MAKE, QUICK -BREAK
<br />CONTACTS; TRIP-f REE OPERATION WITH OVER -THE -CENTER TOGGLE HANDLE OR
<br />NON-REMOVA13LE MONOLITHIC TIE -HANDLE.
<br />MULTI -POLE BREAKER5 SHALL HAVE INTERNAL COMMON TRIP AND COMMON RE5ET WITH A
<br />SINGLE TOGGLE HANDLE OR NON-REMOVABLf MONOLITHIC TIE -HANDLE.
<br />TRIP RATINGS SHALL BE MOLDED ON THE HANDLE OR fACE Of BREAKER.
<br />BREAKER TERMINALS SHALL 13E RATED TO ACCOMMODATE A MINIMUM Of 75 DEGREE C.
<br />CONDUCTORS.
<br />BREAKER SHALL BE RATED fOR MOUNTING AND OPERATION IN ANY POSITION; SHALL
<br />ACCOMMODATE AND MATCH THE TYPE Of TERMINATIONS REQUIRED.
<br />SINGLE POLE BREAKERS RATED 15 AND 20 AMPERES SHALL 13E UL LA13ELED AS "5WITCHING
<br />BREAKERS" AT THE APPLIED CIRCUIT VOLTAGE.
<br />MULTI -POLE BREAKERS RATED 100 AMPERES AND LARGER SHALL BE MOLDED CASE
<br />THERMAL -MAGNETIC BOLT -IN TYPE BREAKER WITH ADJUSTABLE INSTANTANEOUS TRIP.
<br />LIGHTING fIXTURE
<br />SUBMITTAL:
<br />SCHEDULE BY TYPE DESIGNATION ALL LIGHTING f IXTURE5, EACH COMPLETE WITH DATA
<br />SHEET WITH COMPLETE PHYSICAL, ELECTRICAL AND LIGHTING CHARACTERISTICS, LAMP TYPE
<br />AND LAMP DATA.
<br />REfER TO THE "LIGHTING fIXTURE SCHEDULE" VN THE DRAWINGS fOR INDIVIDUAL fIXTURE
<br />DESCRIPTIONS AND MANUfACTURER TYPES.
<br />PROVIDE LAMPS fOR EACH fIXTURE OF: QUANTITY, TYPE AND COLOR AS LISTED IN LIGHTING
<br />fIXTURE SCHEDULE. GE, SYLVANIA OR PHILIPS ARE ACCEPTABLE.
<br />EACH LIGHTING f IXTURE SHALL 13E UL LABELED fOR PROPER OPERATION IN THE TYPE Of
<br />CEILING CONSTRUCTION AND fOR THE MOUNTING ARRANGEMENT ON/IN WHICH IT 15
<br />INSTALLED.
<br />NELD VERIfY ACTUAL CEILING SLOPE fOR fIXTURES INSTALLED IN SAME AND ACTUAL NELD
<br />DIMENSIONS AND ANGLES Of CONSTRUCTION fOR ANY fIXTURf CONfORMING THE SHAPE
<br />AND LENGTH Of SAME, fOR COORDINATION Of f IXTURE CONSTRUCTION.
<br />SUBMITTAL:
<br />INCLUDE SCHEDULE Of EACH PANELBOARD WITH ALL DEVICES AND COMPLETE WITH PHY51CAL AND
<br />ELECTRICAL DATA AND WITH RATINGS fOR. EACH COMPONENT INCLUDING BPTAKMf USE OVERLAY
<br />CURVES.
<br />LABELED PEP, UL #G7 AND #50, CONfORM WITH NEMA #250 AND PB 1, NfPA #70-384 AND 70-373.
<br />ALL JUNCTION BOXES SHALL BE LABELED WITH PANEL AND CIRCUIT DESIGNATION.
<br />PROVIDE TYPED CIRCUIT DIRECTORY WITH EACH CIRCUIT SERVING DEVICES AND AREA 75 SERVING.
<br />APPROVED MANUfACTUPTR5:
<br />GENERAL El FCTRIC
<br />CUTLER HAMMER
<br />SQUARE D
<br />SIEMENS
<br />LIGHTING CONTROL
<br />TIME SWITCHES:
<br />50LID STATE, PROGRAMMABLE, WITH ALPHANUMERIC DISPLAY; COMPLYING WITH UL 3 17.
<br />20-A BALLAST LOAD, 120/24OVAC.
<br />TWO ON -Off SET POINTS ON A 24-HOUR SCHEDULE AND ANNUAL HOLIDAY 5CHDULE THAT
<br />OVERRIDES THE WEEKLY OPERATION ON HOLIDAYS.
<br />ALLOW CONNECTION Of A PHOTOEI ECTRIC RELAY AS SUBSTITUTE fOR ON -Off f UNCTION
<br />Of A PROGRAM
<br />BATTERY BACKUP fOR NOT LE55 THAN SEVEN DAYS RESERVE TO MAINTAIN SCHEDULES AND
<br />TIME CLOCK.
<br />INDOOR OCCUPANCY SENSORS:
<br />WALL OR CEILING MOUNTED 5OLID-5TATE INDOOR OCCUPANCY 5EN50RS WITH A SEPARATE
<br />POWER PACK
<br />ADJUSTABLE TIME -DELAY OVER A RANGE Of I TO 30 MINUTES.
<br />SENSOR OUTPUT: CONTACTS RATED TO OPERATE THE CONNECTED RELAY, COMPLYING WITH
<br />UL773A. SENSOR 15 POWERED fROM POWER PACK.
<br />POWER PACK: DRY CONTACTS RATED fOR 20-A BALLAST LOAD AT 120 OR 277 VAC.
<br />AUTOMATIC LIGHT -LEVEL 5EN5OR: ADJUSTABLE f ROM 2 TO 200 fC (2 1.5 TO 2 152 LUX);
<br />TURN LIGHTS Off WHEN SELECTED LIGHTING LEVEL 15 PRESENT.
<br />DUAL SENSOR TYPE: DETECT OCCUPANCY AREA USING PIR (PASSIVE INfRA-RED) AND
<br />ULTRASONIC DETECTION METHOD.
<br />5PECINCATION5
<br />GROUNDING AND 13ONDING
<br />ALL GROUNDING AND U30NDING SHALL CONfORM TO NEC ARTICLE 250.
<br />COPPER WIRE OR CA13LE INSULATED fOR GOOV UNLESS REQUIRED BY APPLICABLE CODE OR
<br />AUTHORITIES HAVING JURISDICTION.
<br />INSTALL SOLID CONDUCTOR fOR #8 AWG AND SMALLER AND STRANDED CONDUCTORS fOR
<br />#G OR LARGER.
<br />INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTORS fOR ALL EQUIPMENT.
<br />LOW VOLTAGE TRAN5fORMER5
<br />SUBMITTALS: PROVIDE PRODUCT DATA fOR EACH TRAN5fORMER. INDICATE DIMEN51ON5
<br />AND WEIGHTS.
<br />PROVIDE CEKTIf ICATION THAT TRAN5fORMER5, ACCESSORIES, AND COMPONENTS WILL
<br />WITHSTAND SEISMIC fORCES.
<br />MANUfACTURERS: CUTLER -HAMMER, SIEMENS, GE AND SQUARE D.
<br />INSULATION CLA55: 220 DEG C, UL COMPONENT RECOGNIZED INSULATION SYSTEM WITH
<br />MAXIMUM Of 150 DEG C R15E ABOVE 40 DEG C AMBIENT TEMPERATURE.
<br />COMPLY WITH NEMA TP 1, CLA55 I EffICIENCY LEVELS AND TESTED ACCORDING TO NEMA
<br />TP2.
<br />TESTING AND INSPECTION: PERFORM V15UAL AND MECHANICAL INSPECTION AND ELECTRICAL
<br />TEST STATED IN NETA ACCEPTANCE TESTING 5PECINCATION. CEKTIfY COMPLIANCE WITH
<br />TEST PARAMETERS.
<br />PERfORM AN INf PARED SCAN Of TRAN5fORMf_R CONNECTIONS TWO MONTHS AfTER
<br />1 SUBSTANTIAL COMPLETION, PLUS 2 fOLLOW UP SCANS. ONE AT 4 MONTHS AND THE OTHER
<br />i
<br />AT I I MONTHS. PROVIDE CERTIfIED REPORT.
<br />GENERAL NOTE5
<br />ALL EXIT SIGNS, NIGHT LIGHTS AND EMERGENCY BALLA5T CHARGING CIRCUITS SHALL BE
<br />CONNECTED TO UN5WITCMED PORTION Of LIGHTING CIRCUIT SHOWN.
<br />NXTURE TYPE INDICATED BY UPPER CASE CHARACTERS, SWITCHING AND GROUPING
<br />DESIGNATED 13Y LOWER CASE LETTER AND CIRCUIT BY NUMBER (WHERE APPLICABLE).
<br />WMEN CONDUCTOR OR CONDUIT SIZE 15 INDICATED fOR BRANCH CIRCUIT HOME RUN, THE
<br />CONDUCTOR AND CONDUIT SIZE INDICATED SHALL BE USED fOR THE COMPLETE CIRCUIT.
<br />REfER TO THE ARCHITECTURAUINTERIOR5 DOCUMENTS fOR ACTUAL DEVICE LOCATIONS
<br />AND DIMENSIONS.
<br />REfERTO THE APPROPRIATE DRAWINGS fORTME EXACT LOCATION Of EQUIPMENT INSTALLED
<br />UNDER OTHER DIVISIONS Of THE DOCUMENTS, WHICH REQUIRE ELECTRICAL SERVICE.
<br />REf ER TO APPROPRIATE DRAWINGS AND MANUfACTURER5 INSTALLATION MANUAL TO
<br />PROVIDE ALL SUPPLEMENTARY AND CONTROL CIRCUITS TO BRING EQUIPMENT TO fULL
<br />WORKING CONDITION.
<br />EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSTALLED IN ALL RACEWAYS.
<br />WALL SWITCHES CONTROLLING CIRCUITS Of OPPOSITE PHASES SMALL NOT 13E INSTALLED IN
<br />COMMON E30X UNLE55 PERMANENT BARRIER 15 PROVIDED.
<br />ALL RACEWAY AND EQUIPMENT SUPPORTS AND HANGERS SMALL 13F f LILLY COORDINATE[)
<br />WITH STRUCTURAL DRAWINGS.
<br />REfER TO THE ARCHITECTURAUINTERIOR5 REfLECTED CEILING PLANS fOR EXACT FIXTURE
<br />PLACEMENT AND DIMENSIONS.
<br />REfER TO THE ARCMITECTURAUINTERIORS DOCUMENTS fOR ACTUAL DEVICE LOCATIONS AND
<br />DIMENSIONS. NELD VERIfY LAYOUT WITH EX15TING CONDITIONS AND STRUCTURE PRIORTO
<br />BEGINNING INSTALLATION.
<br />1 SEE MVAC DRAWINGS fOR LOCATIONS Of EQUIPMENT TO BE POWERED.
<br />COORDINATE WITH EQUIPMENT CUT5HEETS AND PROVIDE ADDITIONAL CONTROL CIRCUITS If
<br />REQUIRED BY MANUfACTURER.
<br />GENERAL DIAGRAMMATIC RACEWAY INTERCONNECTIONS Of EQUIPMENT, fIXTURE5 AND
<br />DEVICES ARE INDICATED ON fLOOR AND REfLECTED CEILING PLANS, REfER TO STRUCTURAL
<br />AND ARCHITECTURAL PLANS fOR ELEVATION CHANGES AND RACEWAY ROUTES.
<br />PROVIDE SURGE PROTECTION fOR ELECTRICAL AND TELEPHONE SERVICES.
<br />EACH PENETRATION Of A f IRE RESISTANT RATED A55EMBLY 13Y A PIPE, TUBE WIRE OR
<br />CONDUIT SMALL BE PROTECTED BY A THROUGH PENETRATION fIRE STOP SYSTEM THAT HAS
<br />BEEN TESTED ACCORDING TO A5TM E814 OR E 199.
<br />ELECTRIC RECEPTACLES, 5WITCME5, OUTLETS, ETC. SHALL NOT BE INSTALLED 13ACK TO BACK
<br />ON f IRE RE515TANCE RATED WALLS. TMffY SHALL BE AT LEAST 24-INCHE5 APART.
<br />LEGEN D
<br />SYMBOLS
<br />DESCRIPTION
<br />MOUNTING
<br />1p
<br />DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20P,
<br />15" Aff
<br />DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20P,
<br />42" Af f OR G" ABOVE
<br />COUNTER TOP
<br />QUADRAPLEX RECEPTACLE, 120V, 20A, NEMA
<br />5-2OR
<br />18" Af f
<br />QUADRAPLEX RECEPTACLE, 1 20V, 20A, NEMA
<br />42" Af f OR G" ABOVE
<br />AC
<br />5-2OR
<br />COUNTER TOP
<br />RN
<br />DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20P,
<br />fLU5H WITH fIN15HED
<br />fLOOR
<br />0
<br />DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-2OR
<br />IN CEILING
<br />SPECIAL RECEPTACLE, CONfIGURATION AND
<br />ELECTRICAL CHARACTERISTIC AS NOTED ON DWG
<br />18" Af f
<br />JUNCTION BOX FLUSH IN WALL WITH COVER. 51ZE
<br />PEP, NEC.
<br />18" Af f
<br />JUNCTION 13OX fLUSH IN CEILING WITH COVER.
<br />SIZE PEP, NEC.
<br />IN CEILING
<br />El
<br />JUNCTION 13OX f LUSH IN f IN5HED f LOOK WITH
<br />fLU5H WITH fINI5hED
<br />COVER. 51ZF PER NEC.
<br />fLOOR
<br />SWITCH
<br />42" Aff
<br />$3
<br />SWITCH - 3 WAY
<br />42" Aff
<br />$05
<br />SWITCH - WALL MTD, INTEGRAL OCCUPANCY
<br />42" Aff
<br />SENSOR
<br />$LV
<br />SWITCH - WALL MTD, LOW VOLTAGE, PILOT LIGHT
<br />42" Aff
<br />SWITCH - WALL MTD, DIMMING
<br />42" Aff
<br />SWITCH - CEILING MOUNTED OCCUPANCY SENSOR
<br />IN CEILING
<br />9
<br />TV OUTLET
<br />18" Aff
<br />v
<br />TELEPHONE OUTLET
<br />16" Aff
<br />TELEPHONE OUTLET. SUBSCRIPT: f - fIREMAN'5
<br />42" Af f OR G" ABOVE
<br />PHONE, H - HOUSE PHONE, P - PAY PHONE
<br />COUNTER TOP
<br />TELEPHONE DATA COMBINATION OUTLET
<br />18" Af f
<br />TELEPHONE DATA COMBINATION OUTLET
<br />FLUSH WITH fIN15HED
<br />f LOOP,
<br />TELEPHONE DATA COMBINATION OUTLET
<br />42" Af f OR G" ABOVE
<br />COUNTER TOP
<br />17
<br />DATA OUTLET
<br />18" Aff
<br />DATA OUTLET
<br />42" Af f OR G" ABOVE
<br />COUNTER TOP
<br />D15CONNECT SWITCH. SUBSCRIPT: AMP / # Of
<br />AS INDICATED ON
<br />POLES / ENCLOSURE
<br />DWG
<br />Ep
<br />f USED DISCONNECT SWITCH. SUBSCRIPT: AMP/#
<br />AS INDICATED ON
<br />Of POLES / ENCL05U RE / f USE
<br />DWG
<br />ELECTRICAL PANELBOARD. REfER TO
<br />SURfACE MOUNTED
<br />PANELDOARD SCHEDULE.
<br />ON WALL
<br />EQUIPMENT AS NOTED ON DRAWING.
<br />5URfACE MOUNTED
<br />ON WALL
<br />xo/
<br />MOTOR
<br />HOME RUN WITH WIPE TICKS. XX - PANEL
<br />DESIGNATION, # - CIRCUIT DESIGNATION. WIRE
<br />XX4
<br />TICKS - (1) NEUTRAL 1, (3) HOT III * (1) GROUND -
<br />_9MOKff DETECTOR. CEILING / WALL MOUNTED
<br />CEILING /80" Aff
<br />HEAT DETECTOR. CEILING/WALL MOUNTED
<br />CEILING / (50" Af f
<br />fIRE ALARM NOTINCATION DEVICE. AUDIO AND
<br />VISUAL.
<br />80" Aff
<br />fIREALARMNOTIfICATION DEVICE. AUDIO.
<br />80" Af f
<br />fIREALARMNOTIfICATION DEVICE. VISUAL.
<br />(50" Af f
<br />m _FfIRE
<br />ALARM INITIATION DEVICE. PULL STATION.
<br />42" Aff
<br />ABBREVIATION5
<br />AC
<br />G" A13OVE COUNTER SPACE OR
<br />42" Aff
<br />IG
<br />ISOLATED GROUND
<br />Af
<br />AMPfU5f
<br />Isc
<br />SHORT CIRCUIT CURRENT
<br />Aff
<br />A13OVE fINI5HED f LOOP,
<br />LTG
<br />LIGHTING
<br />AL
<br />ALUMINUM
<br />MTD
<br />MOUNTED
<br />BFC
<br />BELOW fIN15HED CEILING
<br />N
<br />NEUTRAL
<br />E3KR
<br />BREAKER
<br />NL
<br />NIGHT LIGHT
<br />CND
<br />CONDUIT
<br />NEC
<br />NATIONAL ELECTRICAL CODE
<br />CONN
<br />CONNECTED OR CONNECTION
<br />PNL
<br />PANEL
<br />CTI5
<br />CA13LE TV TERMINAL
<br />BACKBOARD
<br />RECPT
<br />RECEPTACLE
<br />CU
<br />COPPER
<br />TEL
<br />TELEPHONE
<br />DN
<br />DOWN
<br />TTB
<br />TELEPHONE TERMINAL BOARD
<br />EC
<br />EMPTY CONDUIT
<br />TV
<br />TELEV15ION
<br />ELEC
<br />ELECTRICAL
<br />TVSS
<br />TRANSIENT VOLTAGE SURGE
<br />SUPPRESSOR
<br />fACP
<br />fIRE ALARM CONTROL PANEL
<br />TYP
<br />TYPICAL
<br />fAA
<br />fIRE ALARM ANNUNCIATOR
<br />PANEL
<br />XfMpl
<br />TRANSFORMER
<br />G OR GRND
<br />GROUND
<br />UG
<br />UNDERGROUND
<br />GfCI OR Gf
<br />GROUND fAULT CIRCUIT
<br />INTERRUPTER
<br />WP
<br />WEATHERPROOf
<br />[it of,,, 1/
<br />A
<br />101%
<br />67193
<br />FLORIO'
<br />AL
<br />tollimill
<br />1-111 MIAMI! 000111_'�,_l I
<br />WIPP-1,
<br />PROFICIENT
<br />E N G I N E E R I N G
<br />6991 Peachtree Industriad Btvd Building 700
<br />Peachtree Cwwn, Georgia 30092
<br />404.330.9798
<br />PROJECT # 118537
<br />FL COA #28783
<br />lu
<br />u =, �� oo�
<br />U) UJ (D uj
<br />ui 0 ui LL_ co I— C� Z _j
<br />a� z 3� Fj - < <
<br />< -i >_ W UJ 0
<br />_j <Z U
<br />U) -i Llj EL LL LLI < uj w
<br />z < Lu V) < m Lu
<br />(D u-ji F-- LC-) ou '0--
<br />M < u Cr z
<br /><
<br />LLJ < F- Z Of < C) a- 0
<br />mzz=)O �j�-o Cr �j Lli
<br />0-<oF,-)z D V)�--LLQfm
<br />z F___ = V) 0 Z C/) W Z Z - 0
<br />U) F- o o o LL_
<br />< U Ll
<br />LLZ§K,L,
<br />Cif Z F- Z LU
<br />of LLJ Z S
<br />Lu z U Lij
<br />Ic Y-- IDX =u, > - �w_ (-
<br />) F-
<br />< LU F-- C) F-- 0 Lli C12 H� Z V)
<br />Cr a- u 0 u C� (-) C� LL -i < Z V)
<br />m 0 Lu O� Lu LIJ Z LL. _J 0 u (D
<br />a � CL �- Er z < E < U-i Q� CL 0
<br />LU Lu U z
<br />V) a- - Lu - < <
<br />ui ui u ch UJ Lu < Lu Fr Lu
<br />U LLj F- F- <
<br />J_ = Cr w Of Cr < Z ui = �Q § Of
<br />L F F-- < m < a- u) 0 0 > F__ m 0-
<br />U
<br />V
<br />as
<br />CAI
<br />u
<br />CA
<br />0
<br />7:1
<br />0
<br />u
<br />PLO
<br />�;,
<br />0 r-4
<br />u
<br />ul
<br />�l w
<br />ISSUE: FOR CONSTRUCTION
<br />UVISIONS: I I
<br />PROJECT NUMBER
<br />201812
<br />DATE 4-3-19
<br />I I SHEET NUMBER I I
<br />E09 I