DocuSign Envelope ID: F4F12EE9-368E-447B-87B4-2BA92F0216A4
<br />DESIGN CRITERIA AND LOADS
<br />Buildinq Code
<br />Florida Building and Residential Codes ,
<br />VI" Edition (2020)
<br />Code for Design Loads
<br />ANSI/ASCE 7-16
<br />ROOF LOADING. .............................................
<br />Cd = 1.25
<br />TOP CHORD LIVE LOAD...............................20
<br />PSF
<br />TOP CHORD DEAD LOAD................................7
<br />PSF (TILE = 15 PSF)
<br />BOTTOM CHORD LIVE LOAD
<br />ATTICS WITH LIMITED STORAGE ...............
<br />20 PSF
<br />ATTICS WITHOUT STORAGE .......................10
<br />PSF
<br />(NON -CONCURRENT)
<br />BOTTOM CHORD DEAD LOAD........................5
<br />PSF
<br />WIND LOADING ^3...........................................
<br />Cd 1.60
<br />ASCE 7-16, 3S GUST........................................139
<br />MPH
<br />BASIC WIND SPEED
<br />EXPOSURE CATEGORY ................ ........
<br />.......... C
<br />BUILDING CATEGORY ....................................
<br />11
<br />ENCLOSURE CLASSIFICATION ......................
<br />ENCLOSED
<br />INTERNAL PRESSURE COEFF .......................0.18
<br />C&C DESIGN PRESSURES..............................(SEE
<br />TABLE 1)
<br />FLOOR LOADING ................. ......... ............
<br />........ Cd = 1.00
<br />TOP CHORD LIVE LOAD..................................40
<br />PSF
<br />TOP CHORD DEAD LOAD................................10
<br />PSF (TILE = 17 PSF)
<br />BOTTOM CHORD LIVE LOAD_- .....................
<br />0 PSF
<br />BOTTOM CHORD DEAD LOAD........................5
<br />PSF
<br />SPECIAL FLOOR (GAME ROOM) LOADING .... Cd = 1.00
<br />TOP CHORD LIVE LOAD..................................60
<br />PSF
<br />TOP CHORD DEAD LOAD................................10
<br />PSF
<br />BOTTOM CHORD LIVE LOAD.... ......... .............
<br />0 PSF
<br />BOTTOM CHORD DEAD LOAD ........................
<br />5 PSF
<br />MAXIMUM FLOOR TRUSS SPACING...............16"
<br />O.C.
<br />DEFLECTION CRITERIA
<br />LL / 240
<br />ROOF TRUSSES ..............................................
<br />TL / 180
<br />TL MAX V UP TO 40' SPAN
<br />LL / 480
<br />OPEN WEB FLOOR TRUSSES .......................
<br />TL / 360
<br />LL / 480
<br />TL/240
<br />WOOD I JOISTS ...............................................
<br />TL MAX'/2"
<br />ILL /360
<br />BEAMS'.........................................................
<br />TL / 240
<br />NOTES:
<br />1. PORCH BEAMS AND BEAMS SUPPORTING EXTERIOR WALL
<br />ABOVE SHALL NOT EXCEED Y4 DEFLECTION
<br />2. MAX 16" O.C. FLOOR TRUSS SPACING BELOW GAME ROOM
<br />3. ROOF TRUSS WIND DESIGN METHOD SHALL BE MWFRS
<br />(DIRECTIONAL -OR- ALL HEIGHT) C-C HYBRID
<br />TABLE 1: COMPONENT AND
<br />CLADDING DESIGN PRESSURES
<br />WINDOWS AND DOORS
<br />EFFECTIVE
<br />WIND AREA
<br />ZONE DESIGNATION
<br />IZ - Interior Zone (psf)
<br />EZ - End Zone (psf)
<br />0 - 20 ft2
<br />+28.54 -30.96
<br />+28.54 -38.22
<br />21 - 50 ft2
<br />+27.17 -29.59
<br />+27.17 -35.47
<br />51 - 100 ft2
<br />+25.52 -27.94
<br />+25.52 -32.17
<br />101 - 200 ft2
<br />+24.25 -26.67
<br />+24.25 -29.64
<br />SOFFIT MAX PRESSURE (psf) +28.6 -38.3
<br />GARAGE DOOR PRESSURE +21.7 -24.6
<br />END ZONE KEY MAP
<br />END ZONE: END ZONES SHALL BE TAKEN
<br />AS THE 1 ST 4.0' PER FIGURE R301.2 (7)
<br />I
<br />N '�_ 7
<br />1ST FLOOR .0 F
<br />TYP)
<br />END ZONE
<br />DESIGNATION
<br />TABLE 2: WOOD STRUCTURAL PANEL SHEATHING REQUIREMENTS
<br />NOTES 3.4
<br />p O
<br />STUCCO AND DIRECTLY
<br />MIN 1%g2" 32/16 SPAN RATED OSB OR PLYWOOD INSTALLED VERTICALLY OR (%6" 24/16
<br />w =
<br />ADHERED STONE
<br />INSTALLED HORIZONTALLY) W/ 8d COMMON: 6" O.C. AT PANEL EDGES, 12" O.C. IN THE
<br />^
<br />� I- N
<br />(NOTE 6)
<br />FIELD. 2x4 BLOCKING IS RECOMMENDED AT UNSUPPORTED PANEL EDGES.
<br />LQ Lu
<br />LU
<br />u
<br />_j�O
<br />Q �-
<br />t) � Z
<br />ALL OTHER VENEER
<br />MIN15 32/16 SPAN RATED OSB OR PLYWOOD INSTALLED VERTICAL OR HORIZONTAL
<br />C 0 O
<br />/32 NTAL
<br />(NOTE 8)
<br />W/ 8d COMMON: 6" O.C. EDGES AND FIELD (UNBLOCKED HORIZONTAL PANEL EDGES);
<br />6" O.C. AT PANEL EDGES, 6" O.C. IN FIELD (BLOCKED HORIZONTAL PANEL EDGES)
<br />Y (� rn
<br />TILE AND METAL ROOF
<br />MIN 15/2" 32/16 SPAN RATED PLYWOOD INSTALLED WITH LONG DIMENSION
<br />(NOTE 7)
<br />PERPENDICULAR TO SUPPORTS W/ RSRS-01 NAILS: 4" O.C. AT PANEL EDGES AND
<br />ul
<br />6" O.C. IN THE FIELD
<br />LLJ
<br />p w F-
<br />MIN'/6" 24/16 SPAN RATED OSB OR PLYWOOD INSTALLED WITH LONG DIMENSION
<br />O = Oz
<br />SHINGLE ROOF
<br />PERPENDICULAR TO SUPPORTS W/ RSRS-01 NAILS: 6" O.C. AT PANEL EDGES, 6"
<br />O.C. IN THE FIELD.
<br />FLOOR DECK SHEATHING:
<br />23/32" T&G OSB OR PLYWOOD W/ 10d COMMON: 6" O.0 AT PANEL EDGES, 12" O.C. IN THE
<br />(NOTE 5)
<br />FIELD.
<br />MIN 3/" OSB OR PLYWOOD OR CDX INSTALLED PERPENDICULAR TO SUPPORTS W/ 8d
<br />PORCH CEILING BOARD SHEATHING:
<br />COMMON: 3" O.C. AT PANEL EDGES, 12" O.C. IN THE FIELD OR MIN %" EXTERIOR GYPSUM
<br />CEILING BOARD, FASTEN w/ 5d x 1 %" COOLER NAIL OR NO.6 x 1 %" LONG SCREWS @
<br />4" O.C. EDGES, 8" O.C. FIELD
<br />NOTES:
<br />1. FOR SHEATHING THICKNESS GREATER THAN 15/32" CATEGORY, USE RSRS-03 NAILS.
<br />2. COMMON NAILS IN WALL SHEATHING MAY BE SUBSTITUTED W/ 8d GALVANIZED BOX NAILS.
<br />3. ZIP WALL SHEATHING IS AN ACCEPTABLE ALTERNATE FOR APA RATED WOOD STRUCTURAL PANEL.
<br />4. ALL WOOD STRUCTURAL PANEL SHALL CONFORM TO THE MOST CURRENT APPLICABLE SPECIFICATION AND SUPPLEMENTS OF
<br />CURRENT APPROVED APA.MANF. SPECIFICATIONS.
<br />5. FLOOR FASTENERS ARE MINIMUM REQUIRED FOR DIAPHRAGM DESIGN. FOR INCREASED FLOOR PERFORMANCE AND TO
<br />REDUCE SQUEAKING, RSRS-01 NAILS OR 8d SCREW NAILS ARE RECOMMENDED.
<br />6. 1%2" 32/16 SPAN RATED OSB OR PLYWOOD WITH BLOCKED PANEL EDGES IS AN APA RECOMMENDATION PER APA TECHNICAL
<br />BULLETIN Q370 WHEN STUCCO LATH IS ATTACHED DIRECTLY TO OSB OR PLYWOOD.. SHOULD BUILDER SPECIFICATIONS ALLOW, MIN
<br />STRUCTURAL REQUIREMENTS ARE %6" 24/16 SPAN RATING INSTALLED HORIZONTALLY OR VERTICALLY PER FLEXIBLE VENEER WALL
<br />SPECIFICATIONS. INCLUDES FULL AND PARTIAL HEIGHT VENEER APPLICATIONS.
<br />7. 1%2" PLYWOOD IS A WARRANTY LIMITATION COMMON TO TILE MANUFACTURER'S MINIMUM RECOMMENDATIONS. SHOULD WARRANTY
<br />AND INSTALLATION REQUIREMENTS ALLOW, 15/2" APA RATED OSB OR EQUAL MAY BE USED TO SUPPORT TILE ROOF.
<br />8. WOOD STRUCTURAL PANEL MAY BE INSTALLED VERTICALLY OR HORIZONTALLY W/ UNBLOCKED HORIZONTAL PANEL EDGES.
<br />9. ROOF DECK SHEATHING HAS BEEN ENGINEERED TO RESIST ASCE 7-16 WIND LOADS IN ACCORDANCE WITH FRC R301.2.2.1
<br />TABLE 4: NAIL SIZE LEGEND TABLE 5: FASTENERS IN
<br />NOTES 1, 2, 3, 4 PRESSURE TREATED LUMBER
<br />DIAMETER
<br />LENGTH
<br />8d COMMON
<br />0.131"
<br />2-Y2"
<br />RSRS-01
<br />0.113"
<br />2 %"
<br />RSRS-03
<br />0.131"
<br />2-1/2"
<br />10d
<br />0.131"
<br />3"
<br />10d COMMON
<br />0.148"
<br />3"
<br />12d COMMON
<br />0.148"
<br />3-%'
<br />16d SINKER
<br />0.148"
<br />3-Y4'
<br />16d COMMON
<br />0.162"
<br />3-'/2"
<br />PRESERVATIVE
<br />FASTENER TYPE
<br />ACZA
<br />STANDARD CARBON STEEL
<br />SODIUM BORATE (NOTE 1)
<br />STAINLESS CONNECTORS AND
<br />FASTENERS REQUIRED.
<br />CONNECTORS MUST HAVE
<br />HER PT
<br />Z-MAX, G120 OR TRIPLE ZINC
<br />NG ACQ & MCQ)
<br />17!
<br />COATED FINISH.
<br />ALL FASTENERS MUST BE HOT
<br />DIPPED GALVANIZED.
<br />NOTES:
<br />1. INSTALL 10d NAILS UNLESS OTHERWISE SPECIFIED.
<br />NOTES:
<br />2. COMMON WIRE NAILS AND THREADED HARDENED STEEL NAILS
<br />1 SILL PLATES W/ SODIUM BORATE TREATMENTS BEARING ON
<br />SHALL CONFORM TO THE NOMINAL SIZES SPECIFIED IN ASTM
<br />CONCRETE OVER VAPOR BARRIER ARE NOT DIRECTLY
<br />F1667. NOMINAL DIAMETER SIZES APPLY TO FASTENERS
<br />EXPOSED TO EARTH OR WEATHER AND HAVE BEEN PROVEN
<br />BEFORE APPLICATION OF PROTECTIVE COATING.
<br />TO BE NON -CORROSIVE TO CARBON STEEL FASTENERS.
<br />3. WHEN A BORED HOLE IS REQUIRED TO PREVENT SPLITTING OF
<br />A WOOD DUE TO FASTENER PENETRATION, THE BORED HOLE
<br />SHALL NOT EXCEED 75% OF THE NAIL OR SPIKE DIAMETER.
<br />4. THE NOMINAL DIAMETER AND LENGTH OF TYPICAL FASTENERS
<br />SPECIFIED FOR THIS PROJECT ARE AS LISTED IN TABLE 4.
<br />CONCRETE AND FOUNDATION NOTES
<br />1. CONCRETE COMPRESSIVE STRENGTH FOR FOOTINGS= 2,500 PSI AT 28 DAYS (UNO).
<br />2. CONCRETE COMPRESSIVE STRENGTH FOR SLAB = 2,500 PSI AT 28 DAYS (UNO).
<br />3. ALL REINFORCING STEEL #3 AND BIGGER SHALL BE ASTM A615 GRADE 40 DEFORMED BARS (UNO).
<br />4. ALL REINFORCING STEEL SHALL HAVE 90 DEGREE BEND AT CORNERS WITH A 24" LAP. 24" LONG #4 BAR IS RECOMMENDED TO BE
<br />INSTALLED AT ALL REENTRANT CORNERS.
<br />5. FIBERMESH IS AN ACCEPTABLE ALTERNATIVE AND SHALL NOT REQUIRE WWF. FIBER LENGTH HALL BE 2 T 2" IN LENGTH.
<br />OSS / 0
<br />DOSAGE AMOUNTS SHALL RANGE FROM 0.75 TO 1.5 POUNDS PER CUBIC YARD IN ACCORDANCE WITH THE MANUFACTURER'S
<br />RECOMMENDATIONS. SYNTHETIC FIBERS SHALL COMPLY WITH ASTM C1116. THE MANUFACTURER OR SUPPLIER SHALL PROVIDE
<br />CERTIFICATION OF COMPLIANCE WHEN REQUESTED BY THE BUILDING OFFICIAL.
<br />Q
<br />6. MASONRY STEMWALL AND MONOLITHIC FOOTING ARE INTERCHANGEABLE.
<br />7. EARTH AND EARTH FILL SUPPORTING SLABS ON GRADE IS ASSUMED TO HAVE A MINIMUM BEARING CAPACITY OF 2,000 PSF IN
<br />ACCORDANCE WITH TABLE R401.4.1, AND SHALL BE FREE OF ORGANIC MATERIAL AND COHESIVE SOILS.
<br />COMPACT THE FILL IN 12" LIFTS TO AT LEAST 95% OF MODIFIED PROCTOR MAXIMUM DRY DENSITY. IT IS THE OWNER'S OR
<br />CONTRACTOR'S RESPONSIBILITY TO CONFIRM THESE ASSUMPTIONS.
<br />8. CONCRETE FLOOR SLABS ON GRADE SHALL BE INSTALLED OVER A MINIMUM 6 MIL POLYETHYLENE VAPOR RETARDER WITH
<br />JOINTS LAPPED 6" AND SEALED OVER CLEAN, COMPACTED EARTH OR FILL WITH CODE APPROVED PROVISIONS FOR
<br />PREVENTION OF SUBTERRANEAN TERMITES.
<br />9. STEMWALLS OVER 4 COURSES TALL REQUIRE SPECIAL ATTENTION TO BRACING DURING CONSTRUCTION. CONTACT ENGINEER
<br />OF RECORD IF THIS CONDITION EXISTS.
<br />10. TO CONTROL CRACKING, CUT V SAWCUTS IN THE SLAB IN A 15'x15' GRID WITHIN 12 HOURS OF CONCRETE PLACEMENT.
<br />CONTACT FOR FOR ALTERNATIVE METHODS. CONTROL JOINTS ARE NOT REQUIRED WHEN WWF OR FIBERMESH ARE INCLUDED
<br />WITH CONCRETE WORK.
<br />11. DO NOT SCALE FOOTING DIMENSIONS AND LOCATIONS FROM THE FOUNDATION PLAN. DO NOT DETERMINE FOOTING LOCATION
<br />FROM ARCHITECTURAL PLANS OR FRAMING PLAN. IF FOOTING SIZE OR LOCATION IS NOT DETERMINATE FROM USE OF
<br />FOUNDATION PLAN ALONE, CONTACT THE ENGINEER OF RECORD.
<br />PRE-ENGINEERED TRUSSES & I -JOISTS
<br />1. ROOF TRUSS TOP CHORDS SHALL HAVE A MINIMUM SPECIFIC GRAVITY OF 0.49 (SYP SPECIES OR BETTER).
<br />2. ROOF OR FLOOR TRUSSES FABRICATED TO ACHIEVE THE ROOF PLANES DEPICTED ON THE ARCHITECTURAL PLANS SHALL BE
<br />DESIGNED UNDER THE SUPERVISION OF A REGISTERED PROFESSIONAL ENGINEER. ENGINEERING SHOP DRAWINGS
<br />SHALL BE PREPARED IN ACCORDANCE WITH ANSI/TPI AND SUBMITTED TO THE ENGINEER OF RECORD FOR APPROVAL PRIOR TO
<br />FABRICATION. DESIGN CRITERIA IS LOCATED ON SHEET ST-1 OF THE PLAN SET. TEMPORARY BRACING SHALL BE THE
<br />RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE LEFT IN PLACE AFTER CONSTRUCTION IS COMPLETE,
<br />3. TRUSSES OR I -JOISTS SHALL BE DESIGNED TO MATCH THE ORIENTATION, SPAN DIRECTION, SPACING, BEARING LOCATION AND
<br />NAMING CONVENTION OF THE LAYOUT SHOWN HERE.
<br />4. THE TRUSS ENGINEER SHALL PROVIDE ALL TRUSS TO TRUSS CONNECTION DESIGN AND SPECIFICATIONS AND SUBMIT THEM
<br />UNDER SIGN AND SEAL WITH THE TRUSS SHOP DRAWINGS.
<br />5. TRUSS UPLIFTS HAVE BEEN CALCULATED BY THE ENGINEER OF RECORD AND TAKEN INTO CONSIDERATION DURING THE DESIGN
<br />OF THE UPLIFT RESTRAINT SYSTEM FOR THIS STRUCTURE. AS SUCH, THE REPORTED UPLIFTS ON THE TRUSS SHOP DRAWINGS
<br />MAY BE DISREGARDED.
<br />6. I -JOISTS FABRICATED TO ACHIEVE THE FLOOR PLANS DEPICTED ON THE ARCHITECTURAL PLANS SHALL BE DESIGNED AND
<br />SUBMITTED TO THE ENGINEER OF RECORD FOR APPROVAL PRIOR TO FABRICATION AND INSTALLATION. SEE DESIGN CRITERIA,
<br />THIS SHEET.
<br />TABLE 7: METAL CONNECTOR SCHEDULE
<br />NOTES 2 3 4
<br />USP & SIMPSON CONNECTORS IN CORRESPONDING ROWS BELOW ARE EQUAL
<br />ALTERNATIVES AND MAY BE CONSIDERED INTERCHANGEABLE
<br />SIMPSON
<br />SIMPSON FASTENERS
<br />MITEK
<br />USP FASTENERS
<br />SIMPSON
<br />SIMPSON
<br />FASTENERS
<br />MITEK
<br />USP FASTENERS
<br />1 -'
<br />(8)Y. X 1 /2 SIDS SCREWS
<br />,� %
<br />8 /< x 1 /2 WS15-GC
<br />DTT2Z
<br />IN STUD'/i' 0 X 4 Y2"
<br />WOOD SCREWS IN S1 LID
<br />(9) 10d COMMON
<br />(9) 10d
<br />(NOTE 2)
<br />EMBED EPDXY OR
<br />DTB-TZ
<br />'/2 O x 4'/2" EMBED EPDXY
<br />CS18
<br />EACH END
<br />CS20
<br />COMMON
<br />SCREW ANCHOR
<br />OR SCREW ANCHOR
<br />EACH END
<br />(18)0.162"x2'/2"IN
<br />(18)0.162"x2'Y2"IN
<br />HTT4
<br />STUD/BEAM/TRUSS
<br />STUD/BEAM/TRUSS
<br />(7) 10d x 1 '/2"
<br />(7) 10d x 1 1/2"
<br />(NOTE 2)
<br />§$" 0 x 6" EMBED ANCHOR
<br />HTT45
<br />4811 0 x 6" EMBED ANCHOR
<br />MTS12
<br />EACH END
<br />MTW12
<br />EACH END
<br />IN CONCRETE
<br />IN CONCRETE
<br />(26) 0.162" x 2 '/2" IN
<br />(26) 0.162" x 2 'Y2" IN
<br />HTT5
<br />STUD/BEAM/TRUSS
<br />HTT45
<br />STUD/BEAM/TRUSS
<br />MSTA24
<br />(9) 10d COMMON
<br />MSTA24
<br />(9) 10d COMMON
<br />(NOTE 2)
<br />�8" 0 x 6" EMBED ANCHOR
<br />§6" 0 x 6" EMBED ANCHOR
<br />EACH END
<br />EACH END
<br />IN CONCRETE
<br />IN CONCRETE
<br />(20)'%" x 3" SIDS SCREWS
<br />(24) 3" WS IN STUD
<br />HDQ8-SDS3
<br />IN STUD GROUP
<br />PHD8
<br />GROUP 7 " 0 x 12" EMBED
<br />a
<br />MSTA36
<br />(13) 10d COMMON
<br />MSTA36
<br />(13) 10d COMMON
<br />7/8" 0 x 12" EMBED
<br />ANCHOR IN CONCRETE
<br />EACH END
<br />EACH END
<br />ANCHOR IN CONCRETE
<br />(7) 10d x 1 '/2" IN TRUSS
<br />(7) 10d x 1 'Y2" IN TRUSS
<br />(7) 10d COMMON IN
<br />(7) 10d COMMON IN
<br />META12
<br />4" WET EMBED IN
<br />HTA16-18
<br />4" WET EMBED IN
<br />MSTAM36
<br />WOOD FRAMING
<br />MSTAM36
<br />WOOD FRAMING
<br />GROUTED BLOCK WALL
<br />GROUTED BLOCK WALL
<br />(4) '/<" x 2 'Y," TITEN
<br />(5) 'Y4" x 2 '/4' TAPCON IN
<br />SCREWS IN MASONRY
<br />MASONRY
<br />(8) 10d x 1 'Y2" IN TRUSS
<br />(9) 10d x 1 ''/2" IN TRUSS
<br />(11) 10d x 1 '/2" IN
<br />(11) 10d x 1 'h" IN
<br />META20
<br />4" WET EMBED IN
<br />HTA20-18
<br />4" WET EMBED IN
<br />HTS20
<br />TRUSS/RAFTER
<br />HTW20
<br />TRUSS/RAFTER
<br />GROUTED BLOCK WALL
<br />GROUTED BLOCK WALL
<br />(11) 10d x 1 '%" IN
<br />(11) 10d x 1 '/2" IN
<br />STUD
<br />STUD
<br />(12)10dx1'/2"IN
<br />(8)10dx1'/2"IN
<br />ABU44
<br />(12) 16d COMMON NAILS
<br />PAU44
<br />(12) 16d COMMON NAILS
<br />HTSM20
<br />TRUSS/RAFTER
<br />HTWM20
<br />TRUSS/RAFTER
<br />(NOTE 6)
<br />§8" 0 x 7 EMBED EPDXY
<br />�6" 0 x 7 EMBED EPDXY
<br />(12) 10d x 1 /2' IN
<br />(4) %" x 3" WEDGE BOLT
<br />STUD
<br />OR EQUIVALENT IN STUD
<br />(12) 16d COMMON NAILS
<br />(12) 16d COMMON NAILS
<br />(5) 8d x 1'Y2" IN
<br />(5) 8d x 1'/2" IN
<br />ABU66
<br />4 " 0 x 7" EMBED EPDXY
<br />PAU66
<br />4 " 0 x 7" EMBED EPDXY
<br />H2.5T/
<br />TRUSS
<br />RT7/
<br />TRUSS
<br />(NOTE 6)
<br />(12" EMBED AT GARAGE
<br />(12 EMBED AT GARAGE
<br />HA8
<br />(5)8dx1/2 IN
<br />RT7AT
<br />(5)8dx1/2 IN
<br />DOOR RETURNS)
<br />DOOR RETURNS)
<br />TOP PLATE
<br />TOP PLATE
<br />HU48,
<br />(14) 16d COMMON IN
<br />HD48,
<br />(14) 16d COMMON IN
<br />(5) 10d x 1 Yz" IN
<br />(5) 10d x 1'/2" IN
<br />HUC48,
<br />HEADER
<br />HD481F,
<br />HEADER
<br />H8
<br />TRUSS
<br />RT8A
<br />TRUSS
<br />HU28-2,
<br />HUC28-2
<br />(6) 10d COMMON IN BEAM
<br />HD28-2,
<br />HD28-21F
<br />(6) 10d COMMON IN BEAM
<br />(5) 10d x 11/2" IN
<br />TOP PLATE
<br />(5) 10d x 1 Y2" IN
<br />TOP PLATE
<br />HU410,
<br />(18) 16d COMMON IN
<br />HD410,
<br />(18) 16d COMMON IN
<br />(16) 10d COMMON TO
<br />HUC410,
<br />HEADER
<br />HD4101F,
<br />HEADER
<br />LGT2
<br />TRUSS/RAFTER
<br />'W 'W
<br />LUGT2
<br />TRUSS/RAFTER
<br />HU210-2,
<br />(10) 10d COMMON IN
<br />HD210-2,
<br />(10) 10d COMMON IN
<br />(7) x 2 TITEN
<br />(5)'0" x 3" WEDGE BOLT
<br />HUC210-2
<br />BEAM
<br />HD210-21F
<br />BEAM
<br />SCREWS IN MASONRY
<br />OR EQUIVALENT
<br />(22) 16d COMMON IN
<br />(22) 16d COMMON IN
<br />(26) 16d SINKER
<br />(28) 16d SINKER IN WALL
<br />HUC212-2
<br />HEADER
<br />HD212-21F
<br />HEADER
<br />LGT3
<br />WALL FRAMING
<br />LUGT3
<br />FRAMING
<br />10 10d COMMON IN BEAM
<br />10 10d COMMON IN BEAM
<br />(12) SIDS '/4' x 2 Y2"
<br />(1
<br />(12) WS25 '/4' x 2 Y2"
<br />(4)'/4' x 1 Y2" SIDS SCREW
<br />(4) Y4' x 1'/" WS15 SCREWS
<br />IN TRUSS
<br />IN TRUSS
<br />IN TRUSS/RAFTER
<br />IN TRUSS/ RAFTER
<br />HGA10KT
<br />(4)'%" x 3" SIDS SCREWS
<br />HGA10
<br />(4) '%' x 3" WS3 SCREWS
<br />IN TOP PLATE
<br />IN TOP PLATE
<br />SDWC14500, SDWC15600
<br />NO USP EQUIVALENT
<br />(4) SDS''/4' x 1 '/2" SCREWS
<br />(4) Y4' x 1'/2" WS15 SCREWS
<br />HGAM10KT
<br />IN TRUSS/RAFTER
<br />''/4'
<br />HGAM10KT
<br />IN TRUSS/ RAFTER
<br />(4) /< x 1 /< WEDGE BOLT
<br />(4) x 23/4" TITEN SCREWS
<br />OR EQUIVALENT IN
<br />IN MASONRY
<br />MASONRY
<br />NOTES:
<br />1. REFER TO FRAMING NOTES THIS SHEET FOR ACRYLIC -TIE INSTALLATION SPECIFICATIONS.
<br />2. PRODUCTS SELECTED USING SIMPSON 2019-2020 CATALOG. PRODUCTS MAY BE SUBSTITUTED WITH EQUAL OR BETTER APPROVED ALTERNATES.
<br />3. REFER TO SIMPSON CATALOG FOR ADDITIONAL INSTALLATION INSTRUCTIONS.
<br />4. IF CONNECTOR IS NOT LISTED ABOVE, CONTACT FOR FOR SPECIFIC FASTENING REQUIREMENTS.
<br />5. POSITIVE PLACEMENT GUN NAILS, 2'/2" LONG, WITH EQUIVALENT DIAMETER TO COMMON NAILS SPECIFIED ABOVE MAY BE USED FOR
<br />ABU POST BASE ANCHORS, CS16, AND MSTA FLAT STRAPS.
<br />6. MASONRY APPLICATION REQUIRE EQUIVALENT NUMBER OF TITEN ANCHORS IN LIEU OF 16d NAILS TO HDR CONNECTION. CMU REQUIRES
<br />''Y." 0 x 2 3/" TITENS ILO 16d. CONCRETE REQUIRES EQUIVALENT NUMBER OF'Y," 0 x 1 %" TITENS ILO 16d.
<br />MASONRY NOTES
<br />1. ALL MASONRY UNITS SHALL HAVE fm = 1,500 PSI AND SHALL ERECTED IN RUNNING BOND WITH TYPE M OR S MORTAR OVER FULL
<br />BED.
<br />2. SHOULD LIMITED AREAS OF STACK BOND MASONRY EXIST, EVERY OTHER COURSE SHALL BE EQUIPPED w/ 9 GAUGE LADDER
<br />TYPE HORIZONTAL JOINT REINFORCEMENT
<br />3. ALL GROUT TO MIXED PER ASTM C476 STANDARDS AND INSTALLED TO COMPLY WITH FBC R606.3.5. fc = 3,000 PSI.
<br />4. VERTICAL WALL REINFORCING TO BE ASTM A615 GRADE 60 REBAR.
<br />5. LAPS BETWEEN VERTICAL REINFORCING AND DOWELS TO BE 30".
<br />6. VERTICAL REINFORCING TO HAVE 10" STANDARD HOOK INTO BOND BEAM. DOWEL TO HAVE 10" STANDARD HOOK INTO FOOTING
<br />7. PRE -CAST MASONRY LINTELS: SEE "TYPICAL PRE -CAST LINTEL OPTIONS" DETAIL ON STRUCTURAL DETAIL SHEET.
<br />8. PROVIDE MOISTURE BARRIER FOR ALL UNTREATED LUMBER IN CONTACT WITH MASONRY OR CONCRETE.
<br />>O
<br />_w
<br />N �
<br />LEGEND
<br />�"
<br />OR
<br />"OR" SHALL MEAN THAT EITHER OPTION PROVIDED IS AN EQUAL
<br />ALTERNATIVE FOR THE APPLICATION SHOWN
<br />LINO
<br />UNLESS NOTED OTHERWISE ON PLAN OR DETAIL
<br />O
<br />FOR
<br />ENGINEER OF RECORD
<br />c3
<br />EW
<br />EACH WAY
<br />O
<br />OSB
<br />ORIENTED STRAND BOARD
<br />O
<br />WSP
<br />WOOD STRUCTURAL PANEL
<br />N
<br />0
<br />SYP
<br />SOUTHERN YELLOW PINE
<br />U
<br />APEX
<br />SPF
<br />SPRUCE -PINE -FUR
<br />�
<br />0
<br />CONT
<br />CONTINUOUS
<br />O.C.
<br />ON CENTER
<br />LSL
<br />1.55E TIMBERSTRAND LSL ENGINEERED LUMBER, 1 3/" WIDE, UNO.
<br />(3 %" WIDE LSL BEAMS ARE EQUIVALENT TO 2-PLY 1 3/" BEAM)
<br />LVL
<br />2.0E MICROLLAM LVL ENGINEERED LUMBER, 1 3/" WIDE
<br />PSL
<br />2.0E PARRALLAM PSL ENGINEERED LUMBER, 3 '/2' WIDE, UNO.
<br />N
<br />SYS 42
<br />PROPERLY RATED OPEN WEB HEADER
<br />cN
<br />o
<br />INTERIOR ROOF LOAD BEARING WALL, SPECIFICATIONS
<br />OUTLINED ON TYPICAL WALL SECTIONS, DETAIL SHEETS
<br />LL
<br />LLItd
<br />S
<br />INTERIOR BEARING WALL WITH NO UPLIFT. NO UPLIFT ANCHORS REQUIRED. MINIMUM
<br />J
<br />i�
<br />BOTTOM PLATE ANCHORAGE IS '/2" ANCHOR @ 8'-0" O.C. (UNO ON FRAMING PLAN OR
<br />tr &'s=r sudh s
<br />>�
<br />SW SPECIFICATIONS)
<br />Z
<br />O
<br />STRUCTURAL WOOD BEAM
<br />W
<br />STUD COLUMN KEYNOTE
<br />Q
<br />NUMBER OF SDWC15600 CONNECTING TOP PLATE TO STUDS.
<br />O
<br />NUMBER OF STUDS BELOW BEAM/GIRDER TRUSS. STUDS
<br />O
<br />�-
<br />TO MATCH WALL FRAMING SIZE AND GRADE, UNO.
<br />2 2 STUDS U) w
<br />H
<br />o
<br />ADDITIONAL CLARITY FOR THE LOCATION OF THE STUD COLUMN
<br />2 ANCHOR �
<br />U)
<br />BOTTOM OF STUD COLUMN CONNECTION
<br />1ST LEVEL STUD COLUMN: HOLDDOWN REQUIRED AT BASE OF COLUMN
<br />>
<br />2ND LEVEL STUD COLUMN: STRAPPING REQUIRED FROM 2ND LEVEL
<br />J
<br />COLUMN TO 1ST LEVEL STUDS/HEADER/BEAM.
<br />m
<br />"ANCHOR" REQUIRES BOTTOM PLATE ANCHOR WITHIN 3" OF STUD COLUMN
<br />W
<br />NUMBER OF SDWC15450 CONNECTING STUDS TO BOTTOM PLATE
<br />Q
<br />HEADER STRAPPING KEYNOTE
<br />NUMBER OF STRAPS CONNECTING HEADER TO JACK STUD
<br />0
<br />�MSTA24
<br />1
<br />TYPE OF STRAP CONNECTING HEADER TO JACK STUD
<br />(}j
<br />1 DTT2Z
<br />KING/JACK GROUP BOTTOM CONNECTION
<br />Z
<br />W
<br />1ST LEVEL STUD GROUP: HOLDDOWN REQUIRED AT BASE OF STUD GROUP
<br />(D
<br />2ND LEVEL STUD COLUMN: STRAPPING REQUIRED FROM 2ND LEVEL STUD
<br />LLI
<br />GROUP TO 1ST LEVEL STUDS/HEADER/BEAM.
<br />�
<br />NUMBER OF HOLDDOWNS/STRAPS AT BASE OF KING/JACK GROUP
<br />O
<br />O
<br />NON -BEARING HEADER FRAMING KEYNOTE
<br />NO HDR #
<br />NUMBER OF KING STUDS EACH SIDE OF OPENING
<br />~
<br />LO
<br />HEADER MAY BE FRAMED AS NON BEARING HEADER DUE TO LIGHTLY
<br />LOADED CONDITIONS ABOVE
<br />b
<br />Z
<br />#2 SYP HEADER FRAMING KEYNOTE
<br />U)
<br />(2) 2x10 - 1 / 2
<br />NUMBER OF KING STUDS EACH SIDE OF OPENING
<br />W
<br />W
<br />NUMBER OF JACK STUDS EACH SIDE OF OPENING
<br />z
<br />DEPTH OF LOAD -BEARING #2 SYP HEADER
<br />NUMBER OF PLIES IN HEADER
<br />m
<br />ENGINEERED LUMBER HEADER FRAMING KEYNOTE
<br />W
<br />W
<br />(2) 9'/z' LSL- 1 / 2
<br />NUMBER OF KING STUDS EACH SIDE OF OPENING
<br />Z
<br />NUMBER OF JACK STUDS EACH SIDE OF OPENING
<br />Z
<br />HEADER MATERIAL (LSL, LVL, PSL, OR SYS42) W
<br />DEPTH OF LOAD -BEARING EWP HEADER Q
<br />NUMBER OF PLIES IN HEADER (1 3/" WIDE UNO)
<br />HEADER FRAMING
<br />°
<br />J
<br />LL
<br />1. ALL HEADER JACK AND KING STU DS SHALL BE FASTENED TO EACH OTHER WITH (2) ROWS 10d @ 8" O.C.
<br />Z
<br />STAGGERED.
<br />0
<br />2. NON BEARING HEADERS: DUE TO LIGHTLY LOADED CONDITIONS, 49" OR LESS CLEAR -OPENINGS IN AN
<br />EXTERIOR WALL DO NOT REQUIRE LOAD BEARING HEADER, SEE PLAN.
<br />Q
<br />3. FASTEN ALL MULTI -PLY HEADERS TOGETHER WITH (2) ROWS 10d @ 8" O.C., STAGGERED ALONG EACH EDGE.
<br />�
<br />4. FASTEN ALL HEADERS TO KING STUDS WITH (3)8d TOE NAILS .
<br />O
<br />5. IF HEADER NOT SPECIFIED, CONTACT ENGINEER OF RECORD.
<br />0-
<br />6. UNO ON PLAN, MIN (1) SDWC15600 TOP PLT TO KING STUD AND (1) SDWC15450 KING STUD TO BOTTOM PLATE
<br />O
<br />CONNECTION REQUIRED EACH SIDE OF OPENING (NO CONNECTION REQUIRED FOR OPENINGS AT FIRST
<br />U
<br />FLOOR HEADER WHEN A 2ND LEVEL FLOOR SYSTEM IS ABOVE.
<br />7. TOP PLATE TO HEADER CONNECTION PER ONE OF THE FOLLOWING (NO CONNECTION REQUIRED FOR
<br />OPENINGS 39" OR LESS, OR AT FIRST FLOOR HEADERS WHEN A 2ND LEVEL FLOOR SYSTEM IS ABOVE:
<br />• SDWC15600 @ MAX 32" O.C. AS SHOWN, "ALTERNATE SECTION (HEADERS),ST-5
<br />Of
<br />• SPH w/ (12) 10d x 1- Y2" @ 16" O.C. OR
<br />0
<br />. DSP w/ (14) 10d x 1-'/2" @ 16" O.C. OR
<br />. FASTEN TRUSS DIRECTLY TO HEADER w/ MTS OR FITS w/ (14) 10d x 1 ''/2' (OR EQUAL APPROVED BY EOR).
<br />Q
<br />8. CRIPPLE BLOCKS BELOW LOAD -BEARING HEADERS MAY BE FRAMED AT 24" O.C.
<br />U
<br />z
<br />FRAMING NOTES
<br />1. SIMPSON ACRYLIC -TIE ADHESIVE OR EQUAL SHALL BE USED IN ALL DRILLED AND EPDXIED ANCHOR APPLICATIONS.
<br />O
<br />J
<br />ANCHOR BOLT, THREADED ROD, OR DOWELED REINFORCING STEEL MAY BE EMBEDDED TO THE SPECIFIED DEPTH, IN
<br />O
<br />A HOLE AS SPECIFIED BY MANF (TYPICALLY 1/16" TO 1/8" GREATER THAN SPECIFIED ANCHOR DIAMETER).
<br />Z
<br />ADHESIVE/EPDXY MUST FILL THE HOLE IN THE CONCRETE AND WOOD BOTTOM PLATE. MANUFACTURER'S
<br />2
<br />SPECIFICATIONS MUST BE FOLLOWED FOR PROPER INSTALLATION.
<br />U
<br />2. ALL LUMBER SPECIFIED ON DRAWINGS IS INTENDED FOR DRY USE ONLY, UNO. ALL WATERPROOFING AND FIRE SAFETY
<br />H
<br />SYSTEMS ARE THE RESPONSIBILITY OF THE CONTRACTOR AND ARE TO BE DESIGNED AND DETAILED BY OTHER.
<br />X
<br />3. ALL METAL CONNECTORS SPECIFIED ON PLAN ARE IN ADDITION TO FRAMING FASTENER REQUIREMENTS LISTED IN
<br />W
<br />TABLE 2304.10.1
<br />W
<br />4. BEAMS IDENTIFIED BY NUMBER ON PLAN ARE TO BE PROVIDED BY TRUSS MANUFACTURER OR LUMBER SUPPLIER.
<br />Q
<br />5. FASTEN ALL MULTI -PLY STUD COLUMNS AND CORNERS TOGETHER WITH (2) ROWS 10d @ 8" O.C. STAGGERED.
<br />x
<br />UPPER LEVEL MULTI -PLY STUD GROUPS BELOW ALL GIRDER LOCATIONS TO BE CONTINUOUS THROUGH FLOOR
<br />Q
<br />SYSTEM TO FOUNDATION. (NOT REQUIRED BELOW HEADER JACK/KING STUD GROUPS)
<br />6. FASTEN ALL STUDS TO BOTTOM AND TOP PLATES WITH (4)8d TOE NAILS OR (2)16d COMMON END NAILS.
<br />7. FASTEN ALL TRUSSES AND RAFTERS TO TOP PLATES WITH (3)8d TOE NAILS.
<br />Do
<br />8. ALL MULTI -PLY TRUSS GIRDERS AND BEAMS TO HAVE SOLID STUD GROUP BELOW MATCHING GIRDER OR BEAM
<br />0
<br />THICKNESS AND MATCHING WALL STUD SPECIFICATIONS AS NOTED ON STRUCTURAL PLAN, UNO.
<br />W
<br />9. EXTERIOR WALL DESIGN ASSUMES CONTINUOUSLY SHEATHED WITH OSB OR PLYWOOD
<br />Z
<br />O
<br />W
<br />Q
<br />Z
<br />U)
<br />O
<br />F-
<br />U
<br />U_
<br />Q
<br />U)
<br />C7
<br />O
<br />J
<br />O
<br />Z
<br />2
<br />U
<br />LU
<br />H
<br />X
<br />w
<br />i2
<br />9000 REGENCY SQUARE BLVD.
<br />SUITE 100, JACKSONVILLE, FL 32211
<br />01HORMN'
<br />4-
<br />0 N \\ ll` p wVv\\\\
<br />\�Q
<br />>N
<br />This item has been electronically
<br />signed and sealed by Justin M Lanier,
<br />PE on the date and/or time stamp
<br />shown using a digital signature.
<br />Printed copies of this document are
<br />>1111not considered signed and sealed
<br />and the signature must be verified
<br />111by a 3rd Party Certificate Authority
<br />Qon any electronic copy I _
<br />Uj W
<br />W
<br />LU _0 co
<br />Q
<br />Q 0
<br />Q Q
<br />LLI o
<br />0 J w LLILLJ
<br />W �
<br />X
<br />LL
<br />Q z
<br />Z
<br />O
<br />0
<br />W
<br />i-
<br />Z
<br />0-
<br />LL
<br />W
<br />Abbott Park -'
<br />U
<br />U)
<br />LOT 021-03-1 B o
<br />W
<br />F-
<br />Z
<br />0
<br />0
<br />PROJECT NO: LLI
<br />2021.014960
<br />LL
<br />O
<br />DRAWN:
<br />KME o
<br />O
<br />cHi<o. LO
<br />MJ P
<br />W
<br />J
<br />U
<br />U)
<br />��� , \ G•E•N S ��i Z_
<br />N o 0 ign`ed by
<br />QN
<br />I
<br />AT E OF
<br />3F4671D CDEF�tZ,
<br />.��, •,. OR , p: 121
<br />Z
<br />12-29-2021 p
<br />w
<br />REVISIONS: U)
<br />2
<br />No. Description Date ~
<br />w
<br />J
<br />Q
<br />U
<br />U)
<br />O
<br />Z
<br />O
<br />ST=1
<br />II dr 111 11 I, ::i :.I111IiN." idiii i, i 11 1 1 1 -I 1T- - 1-1 - ii
<br />CMUIMETAL CONNECTOR ENGINEERING
<br />
|