ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />150A1200A INDOOR <br />PANEL CENTER <br />10 #14 to lights & outlets <br />NEMA 1 10 #12 to appliances and GFI <br />150 AMP/ <br />200 AMP 10 #10 to WH <br />10 #8 to Range <br />10 #6 to HVAC <br />METER <br />MOY150=2/0 <br />200=4/0 in 2" Conduit <br />200 amp <br />150 amp <br />UNDERGROUND Disconnect <br />SERVICE BY POWER CO. <br />INTERSYSTEM 4 Bare Cu Ground <br />BONDING #4 GROUNDING WIRE <br />TERMINATION PER Y WITH CODE APPROVED <br />NEC 17, 250.94 CLAMP PER 250,50 AND <br />250.52 OF THE 2017 NEC. <br />GENERAL ELECTRICAL NOTES . Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />Notes: unless otherwise noted, PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />11 CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be. 16 AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />FZF <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />?4 <br />FOUR-WAY SWITCH <br />R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />4-F.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />OD <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />DB <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />a <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />TV� <br />TELEVISION (OPTIONAL) <br />7 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />119 <br />ELECTRIC METER <br />nr <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />C� J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />r J <br />OPT. CEILING FAN <br />(1) PHONE LINE, (1) DATA PORT <br />DEDICATED ' <br />RECEPTACLE FOR <br />MICROWAVE RANG <br />HOOD PER SPECS <br />1.5" VTR `III 3" VTR <br />ICI` I\ <br />1 <br />I I <br />I i <br />I ^ I <br />\I <br />I � \ <br />I\ <br />3 VTR <br />PLUMBING RISER <br />SCALE: NTS <br />I <br />Gil <br />1 <br />I <br />GFI <br />I <br />/ <br />LL <br />XC <br />N �^ <br />GI <br />II I <br />I <br />FG <br />L <br />\�— <br />Gil <br />NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />a <br />SV1!ITCH FOR <br />DISPOSAL <br />ITCHEN <br />F <br />TE�F <br />SPEC 3 & 4 KITCHEN <br />SCALE: %4'=1'-0" <br />A/C PAD <br />DISC. WID <br />GFI <br />/fly <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />HOOD PER SPECS <br />FI M \-1•—DB & GFI TO <br />— — — — — — — BE ALIGNED <br />VERTICALLY <br />I <br />f <br />COACH LIGHTS COACH LIGHTS <br />OR PREWIRE AS / OR PREWIRE AS <br />PER SPECS / PER SPECS <br />FIRST FLOOR ELECTRICAL PLAN -A <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I <br />I <br />I <br />I <br />I <br />� <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I— — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — - <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />SECOND FLOOR ELECTRICAL PLAN -A <br />!V <br />Cq <br />CV <br />Iln <br />>= <br />d� <br />C <br />c cower <br />N C <br />v <br />o <br />r_ 3 m <br />3 �- <br />� <br />N L <br />c F <br />M <br />N <br />0 <br />N <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural <br />plans and specifications contained within these <br />drawings comply with the 2020 Florida Building Code - <br />Residential <br />7th Edition. Engineer's <br />signature and seal is only for <br />the structural <br />engineering portions <br />of the drawing pages bearing <br />Engineer's <br />signature and seal. <br />Nr. N <br />A" <br />o E <br />ID I <br />O Cr c0 <br />0 <br />•� � W N N r <br />C'j CD <br />' <br />\ <br />C J L lJi u <br />a <br />13Z <br />M LL <br />-o <br />l <br />— a 4 <br />m e n <br />^S <br />:kWy a� <br />z <br />Q' <br />W <br />y E - 0 <br />7,oNco 0 <br />o2 <br />W <br />Zco <br />L/ <br />rn <br />Z 4 J <br />co 0 <br />t9 <br />N J <br />O <br />O U <br />Z <br />U <br />r & W <br />❑❑ <br />z N M <br />0 0 <br />z � N <br />z o � <br />� <br />M <br />Z a <br />o <br />CD' <br />V) <br />w S <br />ass <br />CC3 <br />'- <br />(5 <br />LU <br />— <br />U a N <br />c U) <br />N <br />��101 <br />o <br />w <br />M <br />Cl) <br />Q <br />Z <br />U_ <br />to E <br />oo <br /><� <br />UU <br />z <br />oa <br />n3 <br />O [ <br />E <br />g OU <br />4 <br />0 OU <br />p , <br />O <br />a' <br />wo <br />X Z <br />h <br />w <br />@ <br /><z <br />a <br />o <br />mo <br />01 <br />Z' <br />Z <br />aJ <br />J <br />o <br />¢m <br />< <br /><z <br />o< <br />go <br />C/5 <br />a <br />w <br />o <br />m <br />F <br />=G <br />=F <br />0 <br />o <br />w¢ <br />o <br />a= <br />O� <br />2 0 <br />M <br />J <br />Om <br />t6 <br />M <br />co <br />0 <br />NCL <br />Cr <br />0 <br />O <br />0 <br />m <br />0' <br />Ln <br />�--+LIL <br />o <br />Cal N <br />0 <br />m <br />O <br />N <br />Q <br />o N <br />oo <br />E <br />Y <br />_ <br />Cfl r <br />0 <br />z <br />m <br />z <br />E E O <br />w r <br />m <br />E <br />U <br />2 <br />a <br />.j <br />Q O <br />JOB <br />NO: <br />23-00509 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />3 <br />