NOTES:
<br />• INSTALL OUTLETS AT FIXTURE BACK PANEL 30" A.F.F.
<br />POS OUTLET WIRED TO SEPARATE ISOLATED GROUND PANEL
<br />• HOLD WIRING BETWEEN FIXTURE UPRIGHTS AS ON
<br />DETAIL 3/E6
<br />• WIRING RUN IN SHELVING UPRIGHTS TO RECEIVE
<br />1/2" GREENFIELD OR BX SLEEVE.
<br />• INSTALL THE CASH DROP BOXES IN
<br />LOCATIONS AS SHOWN.
<br />• LOCATE UNDERCOUNTER CASH CHANGE DRAWER AS DIMENSIONED.
<br />• DRILL 2-1/2" DIAMETER HOLE IN CHECKOUT TOP AS DIMENSIONED.
<br />PROVIDE BLACK GROMMET TO FIT.
<br />DPC - DUPLEX POS ISOLATED GROUND OUTLET
<br />DC - DUPLEX CONVENIENCE OUTLET M3"
<br />FP - COMPUTER FACE PLATE BOXMO - MONEY ORDER
<br />TYPICAL OUTLET
<br />SPACING
<br />THE ELECTRICAL REVISIONS DESCRIBED HEREIN ARE PURELY
<br />INCIDENTAL TO THE RELOCATION AND/OR REPLACEMENT OF
<br />PARTITIONS, EQUIPMENT AND FURNISHINGS FOR THE PROJECT.
<br />IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO ASCERTAIN
<br />AND PROVIDE FOR ANY ADDITIONAL ENGINEERING TO
<br />ACCOMPLISH THE WORK DESCRIBED; & TO DETERMINE THE
<br />CONDITION OF THE EXISTING PANEL OR SUBPANEL AND
<br />EXISTING DEVICES, CONDUIT, ETC. BEFORE REUSING
<br />COMPONENTS OR RECONNECTING SAME TO EXISTING PANELS
<br />OR SUBPANELS. NOTIFY THE ARCHITECT IF REPLACEMENT OF
<br />COMPONENTS OTHER THAN THOSE SHOWN OR UPGRADING OF
<br />COMPONENTS IS NECESSARY DUE TO CONDITION,
<br />SERVICEABILITY OR A CHANGE OF CONNECTED LOAD.
<br />NOTE:
<br />VERIFY ALL EXISTING CONDITIONS IN FIELD PRIOR TO CONSTRUCTION.
<br />POWER RISER IS EXISTING TO REMAIN.
<br />SCOPE OF WORK
<br />THE SCOPE OF ELECTRICAL WORK SHALL INCLUDE, BUT IS NOT LIMITED
<br />TO THE FOLLOWING:
<br />1. IDENTIFY ALL THE CIRCUITS BEING FED FROM EXISTING PANELS,
<br />WHICH ARE BEING REUSED FOR RENOVATIONS IN RETAIL, AND
<br />FOR THE RELOCATED POWER POLES.
<br />2. ELECTRICAL CONTRACTOR TO VERIFY ALL EXISTING
<br />CONDITIONS PRIOR TO BID & INSTALLATION. INFORM ENGINEER
<br />OF RECORD OF ANY DISCREPANCY BETWEEN THE DOCUMENTS
<br />& THESE CONDITIONS & HE SHALL INCLUDE IN HIS BID TO
<br />CORRECT THE SAME AS DIRECTED. THE ENGINEER &
<br />ARCHITECT ARE NOT RESPONSIBLE FOR ANY ADDITIONAL
<br />COSTS RESULTING FROM VERIFIABLE EXISTING CONDITIONS
<br />DISCOVERED AFTER THE CONTRACT HAS BEEN AWARDED.
<br />3. ELECTRICAL CONTRACTOR SHALL KEEP AS -GUILTS AND SUBMIT
<br />TO ENGINEER OF RECORD FOR REVIEW. ALL CHANGES SHALL BE
<br />FORWARDED A MINIMUM OF (2) WEEKS PRIOR TO FINAL
<br />INSPECTION. ANY EXPENSES, SUCH AS REVISIONS OR
<br />AS-BUILTS, NECESSARY FOR FINAL C.O. SHALL BE AT THE
<br />EXPENSE OF THE OWNER.
<br />NOTE:
<br />CONTRACTOR TO REPAIR ALL BURNT OUT
<br />LAMPS AND BALLASTS. LIGHTING TO BE
<br />100% OPERATIONAL UPON LEAVING. CLEAN
<br />ALL EMERGENCY LIGHTS.
<br />SYMBOL LEGEND
<br />MOUNTING HEIGHT IS FROM FINISHED FLOOR TO CENTERLINE OF DEVICE OR OUTLET.
<br />HEIGHT
<br />MAY VARY TO COINCIDE WITH BUILDING CONSTRUCTION.
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />HEIGHT
<br />DUPLEX RECEPTACLE OUTLET
<br />AS NOTED
<br />RECESSED CLOCK RECEPTACLE OUTLET
<br />AS NOTED
<br />TELEPHONE OUTLET. PROVIDE 1 - 1" C. (WITH PULLWIRE) TO 6" ABOVE
<br />AS NOTED
<br />SUSPENDED CEILING. REFER TO TELEPHONE WIRING DIAGRAM FOR
<br />FURTHER INFORMATION.
<br />a
<br />DATA
<br />AS NOTED
<br />QJ
<br />JUNCTION BOX W/ COVERPLATE - WALL MOUNTED
<br />AS NOTED
<br />NOTE: UNLESS OTHERWISE NOTED ALL OUTLETS & J-BOXES TO BE LOCATED 18" A.F.F.
<br />COLOR OF RECEPTACLES TO BE "MITE". REVIEW ELECTRICAL NOTES TO VERIFY
<br />CONDITIONS PER ELECTRICAL LEGEND.
<br />ELECTRICAL LEGEND NOTES:
<br />R1 RELOCATED POWER POLE AS MANUF. BY WEIDENBACH-BROWN
<br />WITH ALL COMPONENTS FOR A COMPLETE AND STATIONARY
<br />INSTALLATION. WIRING CHASES TO BE FLUSH MOUNTED TO TOP OF
<br />GONDOLA RE: 8/E-1. PROVIDE JUNCTION BOX 6" ABOVE CEILING FOR
<br />WRING CHASE CONNECTION.
<br />OPROVIDE NEW DUPLEX RECEPTACLE FOR RELOCATED APEX
<br />MACHINE COORDINATE EXACT LOCATION WITH FINAL CVS
<br />MERCHANDISE PLAN (F-1). INTERCEPT AND EXTEND EXISTING
<br />BRANCH CIRCUIT TO RELOCATED APEX MACHINE LOCATION
<br />RECONNECT AS REQUIRED FOR OPERATION.
<br />R3 PROVIDE NEW RECEPTACLE FOR RELOCATED PRINTER.
<br />COORDINATE EXACT LOCATION WITH FINAL CVS MERCHANDISE
<br />PLAN. INTERCEPT AND EXTEND EXISTING BRANCH CIRCUIT TO
<br />RELOCATED PRINTER LOCATION. RECONNECT AS REQUIRED FOR
<br />OPERATION.
<br />R4 PROVIDE NEW RECEPTACLE FOR RELOCATED MONEYGRAM.
<br />COORDINATE EXACT LOCATION WITH FINAL CVS MERCHANDISE
<br />PLAN. INTERCEPT AND EXTEND EXISTING BRANCH CIRCUIT TO
<br />RELOCATED MONEYGRAM LOCATION. RECONNECT AS REQUIRED
<br />FOR OPERATION.
<br />R5 PROVIDE NEW RECEPTACLE FOR RELOCATED DOS. COORDINATE
<br />EXACT LOCATION WITH FINAL CVS MERCHANDISE PLAN. INTERCEPT
<br />AND EXTEND EXISTING BRANCH CIRCUIT TO RELOCATED DOS
<br />LOCATION. RECONNECT AS REQUIRED FOR OPERATION.
<br />PROVIDE NEW RECEPTACLE FOR RELOCATED SCANNER.
<br />R6 COORDINATE EXACT LOCATION WITH FINAL CVS MERCHANDISE
<br />PLAN. INTERCEPT AND EXTEND EXISTING BRANCH CIRCUIT TO
<br />RELOCATED SCANNER LOCATION. RECONNECT AS REQUIRED FOR
<br />OPERATION.
<br />R7 PROVIDE ONE NEMA 545R QUAD RECEPTACLE FLUSH MOUNTED @
<br />14" AFF FOR RELOCATED KPM. COORDINATE LOCATION WITH FINAL
<br />CVS MERCHANDISE PLAN. EXTEND BRANCH CIRCUIT TO RELOCATED
<br />KPM LOCATION. RECONNECT AS REQUIRED FOR OPERATION.
<br />Rg PROVIDE ONE NEMA 5-15R QUAD RECEPTACLE MOUNTED ABOVE
<br />CABINET.
<br />R9 PROVIDE ONE NEMA 5-15R QUAD RECEPTACLE FLUSH MOUNTED @
<br />24" AFF TO BOTTOM OF BOX.
<br />R10 PROVIDE ONE NEMA 5-15R QUAD RECEPTACLE FLUSH MOUNTED 1"
<br />BELOWER COUNTER TOP.
<br />R11 PROVIDE AND INSTALL GFI TOP RAIL OUTLETS AS MANUFACTURE BY
<br />WIRING CHASE WITHIN GONDOLA.
<br />R12 PROVIDE ONE JUNCTION BOX AT 24" AFF, WITH 1" CONDUIT WITH
<br />PULL WIRE AT 12" ABOVE CEILING.
<br />R13 NEW POWER POLE AS MANUF. BY WEIDENBACH-BROWN W/ ALL
<br />COMPONENTS FOR A COMPLETE AND STATIONARY INSTALLATION.
<br />WIRING CHASES TO BE FLUSH MOUNTED TO TOP OF GONDOLA RE:
<br />8/E-1. PROVIDE JUNCTION BOX 6" ABOVE CEILING FOR WIRING CHASE
<br />CONNECTION.
<br />ELECTRICAL NOTES
<br />1. ALL WORK SHALL BE IN ACCORDANCE WITH THE 2017 FLORIDA BUILDING CODE, SIXTH EDITION,
<br />THE 2014 NATIONAL ELECTRICAL CODE AND SHALL ALSO COMPLY WITH ALL APPLICABLE RULES
<br />AND REGULATIONS OF LOCAL AND STATE LAWS AND ORDINANCES.
<br />2. ELECTRICAL CONTRACTOR SHALL ARRANGE FOR ALL NECESSARY PERMITS, LICENSES, UTILITY
<br />COORDINATION, AND INSPECTIONS AS REQUIRED BY THE CITY, COUNTY, OR UTILITY COMPANY.
<br />OWNER WILL PAY FEES. CONTRACTOR IS RESPONSIBLE FOR ALL EQUIPMENT REQUIRED BY
<br />UTILITY COMPANY AND SHOULD INCLUDE NECESSARY COSTS IN BID.
<br />3. CONTRACTOR SHALL MAKE A THOROUGH EXAMINATION OF THE SITE AND THE CONTRACT
<br />DOCUMENTS. NO CLAIM FOR EXTRA COMPENSATION WILL BE RECOGNIZED IF DIFFICULTIES
<br />ARE ENCOUNTERED WHICH AN EXAMINATION OF SITE CONDITIONS AND CONTRACT DOCUMENTS
<br />PRIOR TO EXECUTING CONTRACT WOULD HAVE REVEALED.
<br />4. PRIOR TO BID CONTRACTOR SHALL IMMEDIATELY NOTIFY ENGINEER OF AND DISCREPANCIES
<br />WITH CONTRACT DOCUMENTS AND EXISTING SITE CONDITIONS.
<br />5. CONTRACTOR SHALL VERIFY NAMEPLATE DATA AND BREAKER SIZES FOR ALL EQUIPMENT
<br />PRIOR TO PURCHASE.
<br />GROUNDING:
<br />1. THE INTERIOR ELECTRICAL SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS
<br />REQUIRED BY THE NATIONAL ELECTRICAL CODE. ALL METALLIC RACEWAYS SHALL BE
<br />MECHANICALLY AND ELECTRICALLY SECURE AT ALL JOINTS AND AT ALL BOXES, CABINETS,
<br />FITTINGS AND EQUIPMENT.
<br />2. PER ARTICLE 250.50 GROUNDING ELECTRODE SYSTEM, THE CONTRACTOR IS TO UTILIZE ALL OF
<br />THE AVAILABLE ELECTRODES BONDED TOGETHER TO FORM A RELIABLE SYSTEM. ELECTRODES
<br />INCLUDE: METAL UNDERGROUND WATER PIPE, METAL FRAME OF BUILDING, CONCRETE
<br />ENCASED ELECTRODE, GROUND RING, ROD & PIPE ELECTRODES AND PLATE ELECTRODES. AT
<br />A MINIMUM ONE OF THE PRESCRIBED ELECTRODES MUST BE UTILIZED IN ADDITION TO THE
<br />METAL UNDERGROUND WATER PIPE.
<br />OUTLET BOXES / DEVICES:
<br />1. OUTLET SHALL BE GRAY WITH STAINLESS STEEL COVER PLATE.
<br />2. ALL OUTLET BOXES SHALL BE RIGIDLY MOUNTED AND SHALL BE EQUIPPED WITH SUITABLE
<br />SCREW FASTENED COVERS. OPEN KNOCKOUTS OR HOLES IN BOXES SHALL BE PLUGGED WITH
<br />SUITABLE BLANKING DEVICE.
<br />3. OUTLET BOXES LOCATED ABOVE CEILING SHALL BE LEGIBLY IDENTIFIED WITH BRANCH CIRCUIT
<br />NUMBER OF CIRCUIT TERMINATED WITHIN BY MEANS OF BLACK PERMANENT MARKER.
<br />SWITCHGEAR:
<br />1. PANELBOARDS SHALL BE MANUFACTURED BY SQUARE 'D' COMPANY, AND BE NQOD TYPE.
<br />FURNISH WITH COPPER BUS BARS, COPPER EQUIPMENT GROUND BUS AND BOLT -ON CIRCUIT
<br />BREAKERS. APPROVED EQUALS: GENERAL ELECTRIC AND SIEMENS.
<br />2. DISCONNECT SWITCHES SHALL BE HEAVY-DUTY TYPE AND MANUFACTURED BY SQUARED'
<br />COMPANY. FUSES SHALL BE DUAL ELEMENT, CARTRIDGE TYPE, FUSES SHALL BE BY ONE
<br />MANUFACTURER: BUSSMAN "FUSETRON" OR CHASE-SHAWMUT'TRONIC".
<br />3. INSTALL ENGRAVED PLASTIC -LAMINATE LABELS ON EACH MAJOR UNIT OF ELECTRICAL
<br />EQUIPMENT IDENTIFYING PANELBOARD NAME OR EQUIPMENT SERVING. EXAMPLES ARE,
<br />PANELBOARDS AND DISCONNECT SWITCHES, MOTOR STARTERS, I.E. LABELS SHALL BE 1/16"
<br />THICK BLACK PLASTIC LAMINATE WITH 3/8" WHITE CORE PLIE LETTERS.
<br />4. PANELBOARD DIRECTORY CARDS SHALL BE TYPEWRITTEN WITH ACCURATE AND CURRENT
<br />INFORMATION BY THE CONTRACTOR AT THE END OF CONSTRUCTION.
<br />LIGHTING FIXTURES:
<br />1. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE IN ALL RESPECTS ALL LIGHTING
<br />FIXTURES LISTED IN THE FIXTURE SCHEDULE OR SHOWN ON THE PLANS.
<br />Cf]►
<br />2. THE CONTRACTOR SHALL SUBMIT CATALOG CUTS OF ALL THE FIXTURES TO THE
<br />ARCHITECTIOWNER AND SHALL NOT PURCHASE UNTIL APPROVAL IS RECIEVED.
<br />3. BALLASTS FOR FLUORESCENT LAMPS SHALL BE ELECTRONIC MANUFACTURED BY " ORSAM
<br />SYLVANIA" OR EQUAL. ALL BALLASTS FOR FLUORESCENT FIXTURES SHALL BE INDIVIDUALLY
<br />FUSED. FUSES SHALL BE INSTALLED ON THE LINE SIDE OF THE BALLAST.
<br />4. FLUORESCENT LAMPS SHALL BE RAPID START, T8/32 WATT, 3500K. ALL LAMPS SHALL BE AS
<br />MANUFACTURED BY SYLVANIA OR EQUAL.
<br />5. ALL FIXTURES SHALL BE PROPERLY AND CAREFULLY SUPPORTED AND ALIGNED, AND THE
<br />CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY STEEL SHAPES, ETC., FOR
<br />SUPPORT OF FIXTURES AS REQUIRED AND DETAILED ON THE DRAWINGS. PROVIDE JUNCTION
<br />BOX STEM MOUNTED FROM DECK TO SUPPORT ALL CEILING MOUNTED EXIT LIGHTS.
<br />6. LIGHTING FIXTURES SHALL BE CLEAN AND LAMPED WITH NEW LAMPS AT THE TIME OF FINAL
<br />INSPECTION.
<br />7. COORDINATE ALL LOCATIONS OF LIGHTING FIXTURES WITH ARCHITECTURAL DRAWINGS.
<br />WIRE/RACEWAY:
<br />1. ALL CONDUCTORS SHALL BE COPPER, INSULATION SHALL BE DUAL TYPE THHN.THWN 75°C (167°F)
<br />FOR DRY, DAMP AND WET LOCATIONS. CONDUCTOR INSULATION WITH SINGLE TYPE MARKING
<br />THHN 90-C (194"F) MAY BE USED FOR DRY LOCATIONS ONLY. ALL CONDUCTORS SHALL BE
<br />COLOR CODED AS REQUIRED BY NEC AND FURTHER IDENTIFIED AND CODED AS SPECIFIED
<br />HEREINAFTER. COLOR CODING SHALL BE BY MEANS OF COLORED INSULATING MATERIAL,
<br />SUITABLE COLORED, PERMANENT, NON -AGING INSULATING TAPE APPLIED TO CONDUCTORS AT
<br />EACH CABINET OR JUNCTION POINT. THE COLOR CODING SHALL BE ACCOMPLISHED AS THE
<br />CONDUCTORS ARE INSTALLED. THE FOLLOWING SYSTEMS OF COLOR CODING SHALL BE
<br />STRICTLY ADHERED TO:
<br />A) GROUND LEADS: GREEN
<br />B) 1201208 VOLT UNGROUNDED PHASE WIRES:
<br />PHASE A: BLACK
<br />PHASE B: RED
<br />PHASE C: BLUE
<br />NEUTRAL: WHITE
<br />2. THE COLOR CODE ASSIGNED TO EACH PHASE WIRE SHALL BE CONSISTENTLY FOLLOWED
<br />THROUGHOUT.
<br />3. UNLESS OTHERWISE INDICATED, ALL BRANCH CIRCUIT CONDUCTORS SHALL BE NO. 12 AWG.
<br />ANY BRANCH CIRCUIT RUN OVER 75 FEET IN LENGTH. MEASURING ONE WAY FROM THE FIRST
<br />OUTLET OF THE CIRCUIT TO THE PANEL, SHALL BE NO 10. AWG. FOR THE ENTIRE CIRCUIT.
<br />4. UNLESS OTHERWISE NOTED ALL CONDUCTORS SHALL BE RUN IN THIN WALL CONDUIT AND THIN
<br />WALL CONDUIT SHALL BE UNDERWRITERS' APPROVED GALVANIZED ELECTRICAL METALLIC
<br />TUBING, ZINC OR CADMIUM PLATED. CONDUITS RUN UNDERGROUND SHALL BE SCHEDULE 40
<br />PVC.
<br />5. COMBINING OF CIRCUITS IN SAME RACEWAY FOR HOMERUNS PERMITTED BUT LIMITED TO THREE
<br />(3) CIRCUITS PER NEUTRAL AND MUST CONTAIN GROUND.
<br />6. ALL RACEWAYS SHALL BE PROPERLY ALIGNED, GROUPED AND SUPPORTED BY MECHANICAL
<br />TYPE 'CADDY CLIPS AT INTERVALS NOT EXCEEDING 8 FEET. EXISTING RACEWAYS TO REMAIN
<br />SHALL BE RESUPPORTED WHERE RACEWAY SUPPORTS EXCEED 8 FEET.
<br />7. ALL RACEWAYS WITH NO. 10 OR 12 AWG PHASE CONDUCTORS FOR RECEPTACLES, LIGHTING
<br />FIXTURES AND SIMILAR CIRCUITS SHALL BE PROVIDED WITH A PARITY SIZED GREEN EQUIPMENT
<br />GROUND CONDUCTOR. INCLUDING WALL SWITCHES AND FLEXIBLE CONDUIT TO LIGHT FIXTURES.
<br />EQUIPMENT GROUND CONDUCTOR SIZES FOR CIRCUITS WITH PHASE CONDUCTORS LARGER
<br />THAN NO. 12 AWG. ARE INDICATED ON DRAWINGS. GROUND CONDUCTORS SHALL BE
<br />CONNECTED TO GROUND BUSS IN PANELBOARDS.
<br />8. RACEWAY PENETRATIONS OF FIRE RATED WALLS AND/OR FLOORS SHALL BE SEALED TO
<br />MAINTAIN INTEGRITY OF CONSTRUCTION. ALL PRODUCTS, MATERIALS AND METHODS OF
<br />INSTALLATION SHALL BE UL APPROVED AND MEET NFPA.
<br />9. CONDUIT RUNS SHOWN ARE DIAGRAMMATIC IN NATURE. CONTRACTOR IS RESPONSIBLE FOR
<br />SIZING AND LOCATING ALL PULLBOXES PER LOCAL AND NATIONAL ELECTRICAL CODES. ALL
<br />PULLBOXES SHALL REMAIN ACCESSIBLE AND LOCATIONS COORDINATED WITH ALL OTHER
<br />TRADES.
<br />PAN EL
<br />(EXISTING)
<br />P
<br />CIRCUIT BREAKER TYPE
<br />AIC RATING: 22,000 A
<br />120/208 V., 3 PH., 3W
<br />100A. MAIN LUGS ONLY
<br />SURFACE MOUNTED - NEMA 1
<br />CKT.
<br />NO.
<br />NO. OF
<br />POLES
<br />TRIP
<br />AMPS
<br />VOLT
<br />AMPS
<br />LOAD
<br />AO
<br />BO
<br />CO
<br />CKT.
<br />NO.
<br />NO. OF
<br />POLES
<br />TRIP
<br />AMPS
<br />VOLT
<br />AMPS
<br />LOAD
<br />1
<br />1
<br />20
<br />-
<br />SPARE (E)
<br />1000
<br />2
<br />1
<br />20
<br />1000
<br />REC PHOTO EXPRESS (E)
<br />3
<br />1
<br />20
<br />-
<br />SPARE (E)
<br />1500
<br />4
<br />1
<br />20
<br />1500
<br />OFFICE SERVER
<br />(E)
<br />5
<br />1
<br />20
<br />1500
<br />EXISTING EQUIP. (E)
<br />2500
<br />6
<br />1
<br />20
<br />1000
<br />REC PHOTO EXPRESS (E)
<br />7
<br />1
<br />20
<br />1500
<br />EXISTING EQUIP. (E)
<br />3000
<br />8
<br />1
<br />20
<br />1500
<br />OFFICE RECEPT.
<br />(E)
<br />9
<br />2
<br />30
<br />2000
<br />PROCESSOR (E)
<br />1000
<br />10
<br />1
<br />20
<br />-
<br />SPARE
<br />(E)
<br />11
<br />30
<br />-
<br />PROCESSOR (E)
<br />2500
<br />12
<br />1
<br />20
<br />1500
<br />POWER POLE
<br />(E)
<br />13
<br />1
<br />20
<br />500
<br />PLUGMOLD (E)
<br />2000
<br />14
<br />1
<br />20
<br />1500
<br />POWER POLE
<br />(E)
<br />15
<br />1
<br />20
<br />500
<br />PLUGMOLD (E)
<br />2000
<br />16
<br />1
<br />20
<br />1500
<br />POWER POLE
<br />(E)
<br />17
<br />1
<br />20
<br />1000
<br />REC: CASH WRAP (E)
<br />2500
<br />18
<br />1
<br />20
<br />1500
<br />POWER POLE
<br />(E)
<br />19
<br />1
<br />20
<br />1000
<br />REC: CASH WRAP (E)
<br />2500
<br />20
<br />1
<br />20
<br />1500
<br />EXISTING EQUIPMENT(E)
<br />21
<br />1
<br />40
<br />1500
<br />PRINTER (E)
<br />2000
<br />22
<br />1
<br />20
<br />500
<br />PLUGMOLD
<br />(E)
<br />23
<br />1
<br />40
<br />1500
<br />PRINTER (E)
<br />1500
<br />24
<br />1
<br />20
<br />-
<br />SPARE
<br />(E)
<br />25
<br />1
<br />20
<br />-
<br />SPARE (E)
<br />-
<br />1
<br />26
<br />1
<br />20
<br />-
<br />SPARE
<br />(E)
<br />27
<br />1
<br />20
<br />-
<br />SPARE (E)
<br />-
<br />28
<br />1
<br />20
<br />-
<br />SPARE
<br />(E)
<br />29
<br />1
<br />20
<br />-
<br />SPARE (E)
<br />-
<br />30
<br />1
<br />20
<br />-
<br />SPARE
<br />(E)
<br />31
<br />1
<br />20
<br />500
<br />CABINET RECPT. (E)
<br />2000
<br />32
<br />1
<br />20
<br />1500
<br />PEPSI FLM
<br />(N)
<br />33
<br />1
<br />20
<br />1500
<br />POWER POLE (N)
<br />1500
<br />34
<br />1
<br />20
<br />-
<br />SPARE
<br />(E)
<br />35
<br />1
<br />20
<br />-
<br />SPARE (E)
<br />-
<br />36
<br />1
<br />20
<br />-
<br />SPARE
<br />(E)
<br />37
<br />1
<br />20
<br />-
<br />SPARE (E)
<br />-
<br />38
<br />1
<br />20
<br />-
<br />SPARE
<br />(E)
<br />39
<br />1
<br />20
<br />-
<br />SPARE (E)
<br />-
<br />40
<br />1
<br />20
<br />-
<br />SPARE
<br />(E)
<br />41
<br />1 1
<br />20
<br />-
<br />SPARE (E)
<br />-
<br />42
<br />1
<br />20
<br />-
<br />SPARE
<br />(E)
<br />LIGHTING
<br />RECEPTACLES
<br />RECEPTACLES
<br />HVAC
<br />EQUIPMENT
<br />SUBFEED
<br />LARGEST MOTOR
<br />TOTAL CONNECTED VA
<br />0.0 KVA X 1.25 DEMAND FACTOR
<br />10.0 KVA X 1.00 DEMAND FACTOR
<br />3.5 KVA X 0.50 DEMAND FACTOR
<br />0.0 KVA X 1.00 DEMAND FACTOR
<br />13.2 KVA X 1.00 DEMAND FACTOR
<br />0.0 KVA X 1.00 DEMAND FACTOR
<br />2.2 KVA X 1.00 DEMAND FACTOR
<br />10500 8000 9000
<br />0.0 KVA DEMAND LOAD
<br />10.0 KVA DEMAND LOAD
<br />1.8 KVA DEMAND LOAD
<br />0.0 KVA DEMAND LOAD
<br />13.2 KVA DEMAND LOAD
<br />0.0 KVA DEMAND LOAD
<br />2.2 KVA DEMAND LOAD
<br />PANEL CALCULATION
<br />27.20
<br />TIMES 1000
<br />DIVIDED BY DIVIDED BY 1.7 1.732
<br />AMPS
<br />75.50
<br />NOTES: 1
<br />2.
<br />OR VERIFYDATA ON ALL EQUIPMENT PRIOR TO SELECTING CIRCUIT
<br />E CONTRACTOR
<br />BRCONDUITS.
<br />CONTRACTOR TO VERIFY OTHER OWNER REQUIRED LOADS I.R. WELLS, BLDGS, SITE LIGHTING, ETC...
<br />PRIOR TO BIDDING AND PURCHASE OF ELECTRICAL COMPONENTS.
<br />37943 EI W BLVD.
<br />ZEPHYRHILLS, FL 33542
<br />PRDJ=TM FM AM
<br />DEAL TYPES NIA
<br />06A z I II =xv
<br />I�
<br />Robert Reid Wedding.
<br />Architects & Planners, AIA, Inc.
<br />4112 Cypress Street - Tampa, Florida 33607 - 813-879-6996
<br />612 South Military Trail - Deerfield Beech, Florida 33442 - 954.492-9980
<br />Florida License rs: ArchitectunA lnterior Design: AA-0001123 - Engineering: 00002655
<br />COMLTW..
<br />ENGINUITY
<br />CONSULTING ENGINEERS, LLC
<br />CA NO. 32146
<br />5121 EHRLICH RD, SUITE 104E
<br />TAMPA, FLORIDA 33624
<br />813.358.5550
<br />DEVELOPER
<br />MICHAEL AYERS, P.E.
<br />FL NO 36319
<br />REVISIONS:
<br />1 REVISION 06.12.2018
<br />DRAWING BY: GW
<br />DATE: 03/05/2018
<br />JOB NUMBER: 18027
<br />TITLE:
<br />ELECTRICAL NOTES,
<br />SCHEDULES, & LEGEND
<br />SHEET NUMBER:
<br />E1
<br />COMMENTS:
<br />TAKE OFF / BID SET
<br />
|